The ABB OT2500E04P (SKU 1SCA105140R1001) is a 2500 A, 4-pole switch-disconnector for a 1000 V main circuit, certified to IEC 60947-3. It withstands a 55 kA fault current for 1 second (Icw), makes against 176 kA (Icm), and uses 100 mm wide lug terminals on a front-operated, base-mounted frame.
Technical Specifications
| Catalog No | OT2500E04P |
| SKU | 1SCA105140R1001 |
| Brand | ABB |
| Series | Switch Disconnectors |
| EAN | 6417019392493 |
| Number of Poles | 4P |
| Fourth Pole Type | Switched - Simultaneous Function |
| Rated Operational Voltage (Main Circuit) | 1000 V |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Conventional Free-air Thermal Current (Ith) | 2500 A |
| Rated Operational Current AC-22B (Ie) | 2500 A (380-690 V) |
| Rated Short-time Withstand Current (Icw) | 55 kA for 1 s |
| Rated Short-Circuit Making Capacity (Icm) | 176 kA (690 V) |
| Degree of Protection | Front IP00 |
| Pollution Degree | 3 |
| Mounting Type | Base mounting |
| Operating Mode | Front |
| Terminal Type | Lug terminals |
| Terminal Width | 100 mm |
| Power Loss per Pole | 85 W |
| Net Weight | 33.3 kg |
| Net Dimensions (W x H x D) | 598.5 x 376.5 x 145.5 mm |
Certifications & Standards
- IEC/EN 60947-3
Selection Notes
The OT2500E04P shares its 55 kA Icw and 176 kA Icm with the 2000 A switch-disconnector in the same frame family, so stepping up to 2500 A does not change the fault-current duty the switch can handle — only the conventional thermal current and power loss increase. Specify it for isolating a single 2500 A feed rather than transferring between two sources.