- Home
- ABB
- ABB 1SCA022744R2240 OA8G01 1NC 16A 690V Transfer Switch Accessory ABB 1SCA022744R2240 OA8G01 1NC 16A 690V Transfer Switch Accessory
ABB 1SCA022744R2240 OA8G01 1NC 16A 690V Transfer Switch Accessory
ABB 1SCA022744R2240 OA8G01 1NC 16A 690V Transfer Switch Accessory
Get Quote
- Description
Rated 16 A conventional thermal current and 690 V, the ABB 1SCA022744R2240 OA8G01 is a single normally-closed auxiliary contact block for enclosed change-over and transfer switches. Its NC contact opens when the monitored switch position changes, giving a fail-safe signal for interlocking or alarm circuits. It measures 11 x 37 x 21 mm and weighs 0.015 kg.
Technical Specifications
| SKU | 1SCA022744R2240 |
| Brand | ABB |
| Series | Accessories for Enclosed Change-over and Transfer Switches |
| Catalog designation | OA8G01 |
| EAN | 6417019241302 |
| Number of Auxiliary Contacts NC | 1 |
| Conventional Free-air Thermal Current (Ith) | 16 A |
| Conventional Thermal Current (Ithe), Fully Enclosed | 16 A |
| Rated Voltage (Ur) | 690 V |
| Rated Insulation Voltage (Ui) | 690 V |
| Net Width | 11 mm |
| Net Height | 37 mm |
| Net Depth / Length | 21 mm |
| Net Weight | 0.015 kg |
Selection Notes
An NC auxiliary contact is the fail-safe choice for interlocks, since loss of signal wiring or power reads the same as a change of switch state; pick the NO auxiliary contact variant in the same accessory range instead when the control logic needs a positive 'switch is in this position' signal rather than a loss-of-signal alarm. Both the Ith and Ui/Ur ratings match the enclosed transfer switch range this block is built for.