Contactors for Data Center PDU and UPS Systems: Selection Guide
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
The ABB NF31E-11 contactor relay (SKU: 1SBH137001R1131) is a 4-pole auxiliary contactor relay from the ABB NF series, rated at up to 690V IEC / 600V UL and designed for control circuit switching in industrial automation and control panel applications. Featuring a 3NO+1NC contact configuration with a wide-range coil voltage of 24–60V AC (50/60Hz) / 20–60V DC, the NF31E-11 offers flexible integration across diverse control voltage systems. Compact at 87 × 79 × 47 mm and weighing just 0.27 kg, it is well-suited for space-constrained switchgear assemblies.
| Product Net Width | 45 mm |
|---|---|
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.27 kg |
| Number of Auxiliary Contacts NO | 3 |
|---|---|
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-5-1, UL 60335-2-40 LZGH2 A2L, UL 508, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 14-13 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz, Control Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (400 / 440 V) 3 A |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W, (48 V) 2.8 A / 134 W, (72 V) 1 A / 72 W, (110 V) 0.55 A / 60 W, (125 V) 0.55 A / 69 W, (220 V) 0.27 A / 60 W, (250 V) 0.27 A / 68 W, (400 V) 0.15 A / 60 W, (500 V) 0.13 A / 65 W, (600 V) 0.1 A / 60 W |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A, for 1 s 100 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-5-1 690 V, acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-15) 1200 cycles per hour, (DC-13) 900 cycles per hour |
| Maximum Mechanical Switching Frequency | 6000 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 24 ... 60 V, 60 Hz 24 ... 60 V, DC Operation 20 ... 60 V |
| Power Loss | at 6 A per Pole 0.1 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms, Between Coil De-energization and NO Contact Opening 11 ... 95 ms, Between Coil Energization and NC Contact Opening 38 ... 90 ms, Between Coil Energization and NO Contact Closing 40 ... 95 ms |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid Solid 1/2x 1 ... 2.5 mm², Rigid Stranded 1/2x 1 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid Solid 1/2x 1 ... 2.5 mm², Rigid Stranded 1/2x 1 ... 2.5 mm² |
| Wire Stripping Length | Auxiliary Circuit 10 mm, Control Circuit 10 mm |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Tightening Torque | Auxiliary Circuit 1.2 N·m, Control Circuit 1.2 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor Relay |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG, Rigid Stranded 1/2x 18-14 AWG |
|---|---|
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb, Control Circuit 11 in·lb |
| Part number | 1SBH137001R1131 |
|---|---|
| Type designation | NF31E-11 |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 3471523100213 |
| eCl@ss | 27371001 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C, Near Contactor for Operation in Free Air -40 ... 70 °C |
|---|---|
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g, Open, Shock Direction: B1 5 g, Shock Direction: A 30 g, Shock Direction: B2 15 g, Shock Direction: C1 25 g, Shock Direction: C2 25 g |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| REACH Declaration | 2CMT2021-006202 |
|---|---|
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ETIM 7 | EC000196 - Contactor relay |
|---|---|
| eClass | V11.0 : 27371001 |
| UNSPSC | 39121529 |
| E-Number (Sweden) | 3211471 |
| Package Level 1 Units | box 1 piece |
|---|---|
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.27 kg |
| Package Level 1 EAN | 3471523100213 |
| Shipping weight | 0.27 kg |
| Ships from | Türkiye |
| Dispatch | 9 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of NF31E-11 is 690 V AC.
The tariff (HS) code on file for NF31E-11 is 85364900.
The EAN (GTIN) of NF31E-11 is 3471523100213.
NF31E-11 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Master AC3 rating selection with our complete contactor checklist covering load sizing, utilization categories, derating, and coordination. Shop at Stoklink.