- ABB 1SDA060210R1 T6N 630 TMA 630-6300 4p F F InN=100%In 630A 4P Fixed Molded Case Circuit Breaker ABB 1SDA060210R1 T6N 630 TMA 630-6300 4p F F InN=100%In 630A 4P Fixed Molded Case Circuit Breaker
Circuit Breakers & Protection
/
Molded Case Circuit Breakers (MCCB)
/
ABB 1SDA060210R1 T6N 630 TMA 630-6300 4p F F InN=100%In 630A 4P Fixed Molded Case Circuit Breaker
% $-1,776.45
ABB 1SDA060210R1 T6N 630 TMA 630-6300 4p F F InN=100%In 630A 4P Fixed Molded Case Circuit Breaker
Brand:
ABB
Reference No:
1SDA060210R1
Catalog No:
T6N 630 TMA 630-6300 4p F F InN=100%In
Series:
Tmax T6
Tariff Code (HS):
85362090
Get Quote
Rated Current:
630
Breaking Capacity:
(400 V AC) 36 kA
Breaking Type:
TMA
Poles:
4P
Stock:
5
Delivery time:
1-2 business day(s)
Shipping Origin:
Türkiye EXW
$1,776.45
- Description
The ABB 1SDA060210R1 (T6N 630 TMA 630-6300 4p F F InN=100%In) is a 630 A, 4-pole, fixed-mounted molded case circuit breaker (MCCB) from the Tmax T6 range of ABB molded case circuit breaker frames. It is fitted with an adjustable thermal-magnetic (TMA) trip unit and is rated 36 kA Icu at 400 V AC. Dimensions (W × H × D) are 280 mm × 268 mm × 103.5 mm and weight is 12 kg.
Technical Specifications
| Catalog Number | T6N 630 TMA 630-6300 4p F F InN=100%In |
| SKU | 1SDA060210R1 |
| Brand | ABB |
| Series | Tmax T6 |
| Product Type | Molded Case Circuit Breaker (MCCB) |
| Model | T6N |
| Rated Current | 630 A |
| Number of Poles | 4P |
| Trip Unit | TMA 630-6300 |
| Neutral Current Rating | 100 % In |
| Mounting Type | Fixed |
| Breaking Capacity (400 V AC) | 36 kA |
| Width | 280 mm |
| Height | 268 mm |
| Depth | 103.5 mm |
| Weight | 12 kg |
| EAN | 8015644626709 |
Certifications & Standards
- CE: Compliant with EU low-voltage and electromagnetic compatibility directives
- IEC: Designed and tested in accordance with IEC standards for low-voltage switchgear and controlgear
- RoHS: Compliant with EU Directive 2011/65/EU on restriction of hazardous substances, including Amendment 2015/863
- REACH: Compliant with EU REACH regulation (EC) No 1907/2006 on chemical substances
- EU Directive 2011/65/EU & Amendment 2015/863: Verified compliance for restriction of hazardous substances in electrical and electronic equipment
- WEEE: Registered under the Waste Electrical and Electronic Equipment directive for responsible end-of-life disposal
Selection Notes
- Rated current is 630 A; check it against the continuous load current of the circuit being protected.
- Icu is 36 kA at 400 V AC; confirm it is equal to or higher than the prospective fault current at the installation point.
- This is a 4-pole version with the neutral pole rated 100 % In; use it where the neutral conductor must be switched, and confirm the pole count matches the system. Mounting is fixed (not plug-in or withdrawable).
- The TMA trip unit has an adjustable thermal threshold, which allows the setting to be matched to the load within the range listed in the table.
Technical Details
Rated Current (Ampere)
630
Breaking Capacity (kA)
(400 V AC) 36 kA
Mounting Type
Fixed
Catalog No
T6N 630 TMA 630-6300 4p F F InN=100%In
Number of Poles
4P
Delivery Date (Days)
1-2 days
Model Number
T6N
Tariff Code
85362090