Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens 6ES7532-5NB00-0AB0 is a SIMATIC S7-1500 AQ 2xU/I ST analog output module with 2 channels switchable between voltage (0-10V, 1-5V, +/-10V) and current (0-20mA, +/-20mA, 4-20mA) ranges at 16-bit resolution, and it supports safety-oriented shutdown to SIL2/PL d, Category 3. Conversion time is 0.5 ms per channel with a 3.2 ms minimum cycle time across both channels, linearity error is +/-0.15%, and it runs on 24 V DC supply at 200 g weight.
Each of the 2 channels is field-configurable between voltage and current output, so the same module serves 0-10 V and 4-20 mA actuators from the same rack slot without ordering separate voltage-only or current-only variants. Its safety-oriented shutdown path (PL d, Category 3, SIL2 from FS02) lets it drop a load group to a defined state when paired with an F-CPU, useful for analog actuators that need a certified safe-stop rather than just standard diagnostics. 16-bit resolution and +/-0.15% linearity error suit closed-loop process control where the output drives a proportional valve or VFD reference needing fine step resolution.
Used for proportional valve positioning, VFD speed references, and other closed-loop analog control outputs on S7-1500 racks, including applications needing safety-rated shutdown of the output.
| Product type designation | AQ 2xU/I ST |
|---|---|
| HW functional status | FS01 |
| Firmware version | V1.0.0 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Prioritized startup | No |
| Product function: Output range scalable | No |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V13 / V13.0.2 |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with: PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| Engineering with: PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode: Oversampling | No |
| Operating mode: MSO | Yes |
| Reparameterization possible in RUN | Yes |
|---|---|
| Calibration possible in RUN | Yes |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Part number | 6ES7532-5NB00-0AB0 |
|---|---|
| Type designation | AQ 2xU/I ST |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623403487 |
| ETIM class | EC001420 |
| eCl@ss | 27242201 |
| Current consumption, max. | 110 mA; with 24 V DC supply |
|---|
| Power consumption from the backplane bus | 0.65 W |
|---|
| Power loss, typ. | 2.7 W |
|---|
| Number of analog outputs | 2 |
|---|---|
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 24 mA |
| Current output, no-load voltage, max. | 22 V |
| Cycle time (all channels), min. | 3.2 ms; independent of number of activated channels |
| Output ranges, voltage: 0 to 10 V | Yes |
| Output ranges, voltage: 1 V to 5 V | Yes |
| Output ranges, voltage: -5 V to +5 V | No |
| Output ranges, voltage: -10 V to +10 V | Yes |
| Output ranges, current: 0 to 20 mA | Yes |
| Output ranges, current: -20 mA to +20 mA | Yes |
| Output ranges, current: 4 mA to 20 mA | Yes |
| Connection of actuators: for voltage output two-wire connection | Yes |
| Connection of actuators: for voltage output four-wire connection | Yes |
| Connection of actuators: for current output two-wire connection | Yes |
| Load impedance (in rated range of output): with voltage outputs, min. | 1 kΩ; 0.5 kOhm at 1 to 5 V |
| Load impedance (in rated range of output): with current outputs, max. | 750 Ω |
| Cable length: shielded, max. | 800 m; for current, 200 m for voltage |
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 16 bit |
|---|---|
| Integration and conversion time/resolution per channel: Conversion time (per channel) | 0.5 ms |
| Settling time: for resistive load | 1.5 ms |
| Settling time: for capacitive load | 2.5 ms |
| Settling time: for inductive load | 2.5 ms |
| Output ripple (relative to output range, bandwidth 0 to 50 kHz), | 0.02 % |
|---|
| Linearity error (relative to output range), (+/-) | 0.15 % |
|---|---|
| Temperature error (relative to output range), (+/-) | 0.002 %/K |
| Crosstalk between the outputs, max. | -100 dB |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
| Operational error limit in overall temperature range: Voltage, relative to output range, (+/-) | 0.3 % |
| Operational error limit in overall temperature range: Current, relative to output range, (+/-) | 0.3 % |
| Basic error limit (operational limit at 25 °C): Voltage, relative to output range, (+/-) | 0.2 % |
| Basic error limit (operational limit at 25 °C): Current, relative to output range, (+/-) | 0.2 % |
| Diagnostics function | Yes |
|---|---|
| Substitute values connectable | Yes |
| Alarms: Diagnostic alarm | Yes |
| Diagnoses: Monitoring the supply voltage | Yes |
| Diagnoses: Wire break | Yes; Only for output type "current" |
| Diagnoses: Short-circuit | Yes; Only for output type "voltage" |
| Diagnoses: Overflow/Underflow | Yes |
| Diagnostics indication LED: RUN LED | Yes; green LED |
| Diagnostics indication LED: ERROR LED | Yes; red LED |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | Yes; red LED |
| Diagnostics indication LED: for module diagnostics | Yes; red LED |
| Potential separation channels: between the channels | No |
|---|---|
| Potential separation channels: between the channels, in groups of | 2 |
| Potential separation channels: between the channels and backplane bus | Yes |
| Potential separation channels: Between the channels and load voltage L+ | Yes |
| between S- and MANA (UCM) | 8 V DC |
|---|
| Isolation tested with | 707 V DC (type test) |
|---|
| signed firmware update | No |
|---|---|
| data integrity | No |
| Ambient temperature during operation: horizontal installation, min. | 0 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | 0 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Width | 25 mm |
|---|---|
| Height | 147 mm |
| Depth | 129 mm |
| Weight, approx. | 200 g |
|---|
| Note: | Supplied incl. 40-pole push-in front connectors |
|---|
| Net weight | 0.368 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.868 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of AQ 2xU/I ST is 24 V AC.
The tariff (HS) code on file for AQ 2xU/I ST is 85389091.
The EAN (GTIN) of AQ 2xU/I ST is 4047623403487.
AQ 2xU/I ST ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.