Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens 6ES7523-1BL00-0AA0 is a SIMATIC S7-1500 digital combo module with 16 DI 24VDC and 16 DQ 24VDC/0.5A transistor outputs in groups of 8. Rated for 24 V DC supply (19.2-28.8 V) with reverse-polarity protection, it supports safety-related load-group shutdown up to SIL2 / PL d Cat.3 and ships with 40-pole push-in front connectors.
Combining DI and DQ on one 25 mm module saves backplane slots versus running separate input and output modules where S7-1500 rack space is the constraint. The 0.5 A per-channel output rating (4 A per group of 8, 8 A per module) covers small solenoid valves and indicator loads directly; higher loads need an external relay or contactor stage. The SIL 2 / PL d Cat. 3 safety-related shutdown capability, available from hardware version FS03/FS04, only matters if the load group ties into a safety function - for standard machine I/O without a safety requirement it is unused headroom.
Mixed digital signal panels on SIMATIC S7-1500 controllers: limit switch and pushbutton inputs paired with small actuator or lamp outputs on the same module, including safety-related load groups such as guard-interlocked drives where a separate safety relay isn't otherwise justified.
| Product type designation | DI 16x24VDC / DQ16x24VDC/0.5A BA |
|---|---|
| HW functional status | FS01 |
| Firmware version | V1.0.0 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Prioritized startup | Yes |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V13 / V13 |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with: PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| Engineering with: PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode: DI | Yes |
| Operating mode: Counter | No |
| Operating mode: DQ | Yes |
| Operating mode: DQ with energy-saving function | No |
| Operating mode: PWM | No |
| Operating mode: Oversampling | No |
| Operating mode: MSI | Yes |
| Operating mode: MSO | Yes |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes; through internal protection with 7 A per group |
| Current consumption, max. | 30 mA |
|---|
| Part number | 6ES7523-1BL00-0AA0 |
|---|---|
| Type designation | DI 16x24VDC / DQ16x24VDC/0.5A BA |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623402312 |
| ETIM class | EC001419 |
| eCl@ss | 27242204 |
| Rated value (DC) | 24 V |
|---|
| Power consumption from the backplane bus | 1.1 W |
|---|
| Power loss, typ. | 3.45 W |
|---|
| Number of digital inputs | 16 |
|---|---|
| Digital inputs, parameterizable | No |
| Sourcing/sinking input | P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
| Input voltage: Rated value (DC) | 24 V |
| Input voltage: for signal "0" | -30 to +5 V |
| Input voltage: for signal "1" | +11 to +30V |
| Input current: for signal "1", typ. | 2.7 mA |
| Input delay (for rated value of input voltage) for standard inputs: parameterizable | No |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Type of digital output | Transistor |
|---|---|
| Number of digital outputs | 16 |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | No |
| Short-circuit protection | Yes |
| Response threshold, typ. | 1 A |
| Limitation of inductive shutdown voltage to | L+ (-53 V) |
| Controlling a digital input | Yes |
| Switching capacity of the outputs: with resistive load, max. | 0.5 A |
| Switching capacity of the outputs: on lamp load, max. | 5 W |
| Load resistance range: lower limit | 48 Ω |
| Load resistance range: upper limit | 12 kΩ |
| Output voltage: for signal "1", min. | L+ (-0.8 V) |
| Output current: for signal "1" rated value | 0.5 A |
| Output current: for signal "1" permissible range, max. | 0.5 A |
| Output current: for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load: "0" to "1", max. | 100 µs |
| Output delay with resistive load: "1" to "0", max. | 500 µs |
| Parallel switching of two outputs: for logic links | Yes |
| Parallel switching of two outputs: for uprating | No |
| Parallel switching of two outputs: for redundant control of a load | Yes |
| Switching frequency: with resistive load, max. | 100 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz |
| Switching frequency: on lamp load, max. | 10 Hz |
| Total current of the outputs: Current per channel, max. | 0.5 A; see additional description in the manual |
| Total current of the outputs: Current per group, max. | 4 A; see additional description in the manual |
| Total current of the outputs: Current per module, max. | 8 A; see additional description in the manual |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Connectable encoders: 2-wire sensor | Yes |
|---|---|
| Connectable encoders: permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Diagnostics function | No |
|---|---|
| Substitute values connectable | No |
| Alarms: Diagnostic alarm | No |
| Alarms: Maintenance interrupt | No |
| Alarms: Hardware interrupt | No |
| Diagnoses: Monitoring the supply voltage | No |
| Diagnoses: Wire break | No |
| Diagnoses: short-circuit | No |
| Diagnoses: Group error | No |
| Diagnostics indication LED: RUN LED | Yes; green LED |
| Diagnostics indication LED: ERROR LED | Yes; red LED |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | No |
| Diagnostics indication LED: for module diagnostics | No |
| Potential separation channels: between the channels | No |
|---|---|
| Potential separation channels: between the channels, in groups of | 8 |
| Potential separation channels: between the channels and backplane bus | Yes |
| Isolation tested with | 707 V DC (type test) |
|---|
| signed firmware update | No |
|---|---|
| data integrity | No |
| Ambient temperature during operation: horizontal installation, min. | 0 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | 0 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Width | 25 mm |
|---|---|
| Height | 147 mm |
| Depth | 129 mm |
| Weight, approx. | 280 g |
|---|
| Note: | Supplied incl. 40-pole push-in front connectors |
|---|
| eClass | 9.1 27-24-22-04 |
|---|---|
| ETIM | 10 EC001419 |
| IDEA | 4 3566 |
| UNSPSC | 15 32-15-17-05 |
| Miscellaneous Manufacturer Declara-tion | For use in hazard- |
|---|---|
| General Product Approval | ous locations |
| FM CCC-Ex Type Examination Cer- | tificate |
|---|
| Net weight | 0.36 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.86 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of DI 16x24VDC / DQ16x24VDC/0.5A BA is 0.5 A.
The rated operational voltage of DI 16x24VDC / DQ16x24VDC/0.5A BA is 24 V DC.
The tariff (HS) code on file for DI 16x24VDC / DQ16x24VDC/0.5A BA is 85389091.
The EAN (GTIN) of DI 16x24VDC / DQ16x24VDC/0.5A BA is 4047623402312.
DI 16x24VDC / DQ16x24VDC/0.5A BA ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.