Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens 6ES7522-5FH00-0AB0 is a SIMATIC S7-1500 digital output module, DQ 16x230VAC/1A ST, switching 16 Triac outputs rated 1 A at 120/230 V AC and wired in groups of 2 channels. Each output carries a 6.3 A slow-blow fuse and a built-in switching cycle counter, and it needs a front connector ordered separately.
ST places this module in the Standard performance class with per-channel diagnostics and an integrated switching-cycle counter, ahead of a Basic-class AC output module but below an HF-class card with tighter output delay. The Triac output stage is the reason to pick this over a relay-output AC module in the same voltage range: solid-state switching gives silent, contact-less operation and a rated 10 Hz switching frequency on resistive loads, at the cost of a lower NEMA motor-starter rating (size 4) than a relay-based card can carry. Because the built-in 6.3 A slow-blow fuse protects each channel individually, a channel fault does not take the whole group down, unlike output modules relying only on group-level external fusing.
Switching 120/230 V AC loads such as solenoid valves, small motor starters, and indicator lamps directly from the PLC, where solid-state Triac switching is preferred over relay contacts for cycle life or noise reasons.
| Product type designation | DQ 16x230VAC/1A ST (Triac) |
|---|---|
| HW functional status | from FS01 |
| Firmware version | V 1.2.0 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Prioritized startup | Yes |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with: PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| Engineering with: PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode: DQ | Yes |
| Operating mode: DQ with energy-saving function | No |
| Operating mode: PWM | No |
| Operating mode: Oversampling | No |
| Operating mode: MSO | Yes |
| Operating mode: Integrated operating cycle counter | Yes; FW V1.2.0 or higher |
| Rated value (AC) | 230 V; 120/230 V AC, 50/60 Hz |
|---|
| Power consumption from the backplane bus | 1.2 W |
|---|
| Part number | 6ES7522-5FH00-0AB0 |
|---|---|
| Type designation | DQ 16x230VAC/1A ST (Triac) |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623404101 |
| ETIM class | EC001419 |
| eCl@ss | 27242204 |
| Power loss, typ. | 11.1 W |
|---|
| Type of digital output | Triac |
|---|---|
| Number of digital outputs | 16 |
| Current-sinking | Yes |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | Yes |
| Short-circuit protection | No |
| built-in fuse | 6.3 A melting fuse, slow-blow |
| Size of motor starters according to NEMA, max. | 4 |
| Switching capacity of the outputs: with resistive load, max. | 1 A |
| Switching capacity of the outputs: on lamp load, max. | 50 W |
| Output voltage: for signal "1", min. | L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current |
| Output current: for signal "1" rated value | 1 A |
| Output current: for signal "1" permissible range, min. | 10 mA |
| Output current: for signal "1" permissible range, max. | 15 A; max. 1 AC cycle |
| Output current: for signal "0" residual current, max. | 2 mA |
| Output delay with resistive load: "0" to "1", max. | 1 AC cycle |
| Output delay with resistive load: "1" to "0", max. | 1 AC cycle |
| Parallel switching of two outputs: for logic links | No |
| Parallel switching of two outputs: for uprating | No |
| Parallel switching of two outputs: for redundant control of a load | Yes |
| Switching frequency: with resistive load, max. | 10 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz |
| Switching frequency: on lamp load, max. | 1 Hz |
| Total current of the outputs: Current per channel, max. | 1 A; see additional description in the manual |
| Total current of the outputs: Current per group, max. | 2 A; see additional description in the manual |
| Total current of the outputs: Current per module, max. | 10 A; see additional description in the manual |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Diagnostics function | No |
|---|---|
| Substitute values connectable | Yes |
| Alarms: Diagnostic alarm | No |
| Alarms: Maintenance interrupt | Yes; maintenance alarm for switching cycle counter |
| Diagnoses: Monitoring the supply voltage | No |
| Diagnoses: Wire break | No |
| Diagnoses: Short-circuit | No |
| Diagnostics indication LED: RUN LED | Yes; green LED |
| Diagnostics indication LED: ERROR LED | Yes; red LED |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | No |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | No |
| Diagnostics indication LED: for module diagnostics | Yes; red LED |
| Potential separation channels: between the channels | No |
|---|---|
| Potential separation channels: between the channels, in groups of | 2 |
| Potential separation channels: between the channels and backplane bus | Yes |
| between different circuits | 250 V AC between the channels and the backplane bus; 500 V AC between the channels |
|---|
| Isolation tested with | 3 100 V DC |
|---|
| Suitable for safety functions | No |
|---|
| signed firmware update | No |
|---|---|
| data integrity | No |
| Ambient temperature during operation: horizontal installation, min. | 0 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | 0 °C |
| Width | 35 mm |
|---|---|
| Height | 147 mm |
| Depth | 129 mm |
| Weight, approx. | 310 g |
|---|
| Miscellaneous Manufacturer Declara- | tion |
|---|
| China RoHS Manufacturer Declara- FM | tion |
|---|---|
| Maritime application | NK / Nippon Kaiji Ky- okai |
| Net weight | 0.358 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.858 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of DQ 16x230VAC/1A ST (Triac) is 1 A.
The rated operational voltage of DQ 16x230VAC/1A ST (Triac) is 230 V AC.
The tariff (HS) code on file for DQ 16x230VAC/1A ST (Triac) is 85389091.
The EAN (GTIN) of DQ 16x230VAC/1A ST (Triac) is 4047623404101.
DQ 16x230VAC/1A ST (Triac) ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.