Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens 6ES7522-5FF00-0AB0 is a SIMATIC S7-1500 digital output module, type DQ 8x230VAC/2A ST, with 8 Triac outputs rated 120/230 V AC and 2 A per channel. Each channel carries a built-in 6.3 A slow-blow fuse, and total module current is limited to 10 A. Front connectors are ordered separately.
Each of the 8 channels is isolated individually (groups of 1), so a fault on one output does not affect the others, unlike modules that isolate in larger groups. The 6.3 A slow-blow fuse per channel is sized above the 2 A rated output to absorb inrush from lamp or small-motor loads without nuisance tripping, and two outputs can be paralleled for redundant control of a single load. The 10 Hz maximum switching frequency on resistive loads and 0.5 Hz on inductive loads mark this as a standard switching module, not suited to high-frequency PWM-style control; use a DC or solid-state output module for that. Front connectors (screw-terminal or push-in) are not included.
Switching 230 V AC loads such as contactor coils, indicator lamps, and solenoid valves directly from an S7-1500 station, including redundant shutdown paths using the paralleled-output function.
| Product type designation | DQ 8x230 V AC/2A ST (triac) |
|---|---|
| HW functional status | from FS01 |
| Firmware version | V2.2.0 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Prioritized startup | Yes |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V12 / V12 |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with: PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| Engineering with: PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode: DQ | Yes |
| Operating mode: DQ with energy-saving function | No |
| Operating mode: PWM | No |
| Operating mode: Oversampling | No |
| Operating mode: MSO | Yes |
| Operating mode: Integrated operating cycle counter | Yes; FW V2.2.0 or higher |
| Rated value (AC) | 230 V; 120/230 V AC, 50/60 Hz |
|---|
| Power consumption from the backplane bus | 0.9 W |
|---|
| Part number | 6ES7522-5FF00-0AB0 |
|---|---|
| Type designation | DQ 8x230 V AC/2A ST (triac) |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515079873 |
| ETIM class | EC001419 |
| eCl@ss | 27242204 |
| Power loss, typ. | 10.8 W |
|---|
| Type of digital output | Triac |
|---|---|
| Number of digital outputs | 8 |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | Yes |
| Short-circuit protection | No |
| built-in fuse | 6.3 A melting fuse, slow-blow |
| Size of motor starters according to NEMA, max. | 5 |
| Switching capacity of the outputs: with resistive load, max. | 2 A |
| Switching capacity of the outputs: on lamp load, max. | 50 W |
| Output voltage: for signal "1", min. | L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current |
| Output current: for signal "1" rated value | 2 A |
| Output current: for signal "1" permissible range, min. | 10 mA |
| Output current: for signal "1" permissible range, max. | 15 A; max. 1 AC cycle |
| Output current: for signal "0" residual current, max. | 2 mA |
| Output delay with resistive load: "0" to "1", max. | 1 AC cycle |
| Output delay with resistive load: "1" to "0", max. | 1 AC cycle |
| Parallel switching of two outputs: for logic links | No |
| Parallel switching of two outputs: for uprating | No |
| Parallel switching of two outputs: for redundant control of a load | Yes |
| Switching frequency: with resistive load, max. | 10 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz |
| Switching frequency: on lamp load, max. | 1 Hz |
| Total current of the outputs: Current per channel, max. | 2 A; see additional description in the manual |
| Total current of the outputs: Current per group, max. | 2 A; see additional description in the manual |
| Total current of the outputs: Current per module, max. | 10 A; see additional description in the manual |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Diagnostics function | No |
|---|---|
| Substitute values connectable | Yes |
| Alarms: Diagnostic alarm | No |
| Alarms: Maintenance interrupt | Yes; maintenance alarm for switching cycle counter |
| Diagnoses: Monitoring the supply voltage | No |
| Diagnoses: Wire break | No |
| Diagnoses: Short-circuit | No |
| Diagnostics indication LED: RUN LED | Yes; green LED |
| Diagnostics indication LED: ERROR LED | Yes; red LED |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | No |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | No |
| Diagnostics indication LED: for module diagnostics | Yes; red LED |
| Potential separation channels: between the channels | Yes |
|---|---|
| Potential separation channels: between the channels, in groups of | 1 |
| Potential separation channels: between the channels and backplane bus | Yes |
| Potential separation channels: Between the channels and load voltage L1 | Yes |
| between different circuits | 250 V AC between the channels and the backplane bus; 500 V AC between the channels |
|---|
| Isolation tested with | 3 100 V DC |
|---|
| Suitable for safety functions | No |
|---|
| signed firmware update | No |
|---|---|
| data integrity | No |
| Ambient temperature during operation: horizontal installation, min. | 0 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | 0 °C |
| Width | 35 mm |
|---|---|
| Height | 147 mm |
| Depth | 129 mm |
| Weight, approx. | 290 g |
|---|
| Miscellaneous Manufacturer Declara- | tion For use in hazard- |
|---|---|
| General Product Approval | ous locations |
| China RoHS Manufacturer Declara- FM | tion |
| Net weight | 0.34 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.84 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | Critical stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of DQ 8x230 V AC/2A ST (triac) is 2 A.
The rated operational voltage of DQ 8x230 V AC/2A ST (triac) is 120–230 V AC.
The tariff (HS) code on file for DQ 8x230 V AC/2A ST (triac) is 85389091.
The EAN (GTIN) of DQ 8x230 V AC/2A ST (triac) is 4025515079873.
DQ 8x230 V AC/2A ST (triac) ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.