Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens SIMATIC S7-1500 DQ 64x24VDC/0.3A BA (6ES7522-1BP00-0AA0) is a 64-channel digital output module rated 24V DC / 0.3A per output, grouped in 16 channels with 2A per group at 60°C. It supports safety-related shutdown of load groups up to SIL2 per IEC 62061:2021 and PL d / Category 3 per ISO 13849-1:2015, and mounts in a 35 mm wide housing in the S7-1500 rack.
The BA suffix marks this as the basic variant, with diagnostics limited to the module's RUN/ERROR LEDs — per-channel status display requires a SIMATIC TOP connect connection module. The SIL2 / PL d / Cat. 3 safety rating applies to shutting down an entire 16-channel load group, not individual-channel diagnostics, so it fits designs where a group of outputs needs a certified emergency-stop path without a separate safety I/O module. Size connected loads against the 2 A group limit, not just the 0.3 A per-channel rating — 16 channels loaded at 0.3 A each would exceed the group ceiling.
Drives 24V DC loads such as solenoid valves, contactor coils, and indicator lamps from an S7-1500 rack, including machine zones where a load group must be safely de-energized to SIL2 / PL d without a dedicated safety I/O module. Cables and TOP connect connection modules are ordered separately.
| Product type designation | DQ 64x24VDC/0.3A BA |
|---|---|
| HW functional status | from FS01 |
| Firmware version | V1.0.0 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Prioritized startup | No |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V16 with HSP 0319 / V17 |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with: PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| Engineering with: PROFINET from GSD version/GSD revision | V2.35 / - |
| Operating mode: DQ | Yes |
| Operating mode: DQ with energy-saving function | No |
| Operating mode: PWM | No |
| Operating mode: Cam control (switching at comparison values) | No |
| Operating mode: Oversampling | No |
| Operating mode: MSO | Yes |
| Operating mode: Integrated operating cycle counter | No |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes; through internal protection with 7 A per group |
| external protection for power supply lines (recommendation) | 24 V DC/6 A miniature circuit breaker with type B tripping characteristic |
| Current consumption, max. | 90 mA; without load |
|---|
| Part number | 6ES7522-1BP00-0AA0 |
|---|---|
| Type designation | DQ 64x24VDC/0.3A BA |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623411017 |
| ETIM class | EC001419 |
| eCl@ss | 27242204 |
| Rated value (DC) | 24 V |
|---|
| Power consumption from the backplane bus | 0.6 W |
|---|
| Power loss, typ. | 3.5 W |
|---|
| Type of digital output | Transistor |
|---|---|
| Number of digital outputs | 64 |
| Current-sinking | No |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | No |
| Short-circuit protection | Yes |
| Limitation of inductive shutdown voltage to | L+ (-53 V) |
| Controlling a digital input | Yes |
| Switching capacity of the outputs: with resistive load, max. | 0.3 A |
| Switching capacity of the outputs: on lamp load, max. | 5 W |
| Load resistance range: lower limit | 80 Ω |
| Load resistance range: upper limit | 10 kΩ |
| Output voltage: for signal "1", min. | L+ (-0.8 V) |
| Output current: for signal "1" rated value | 0.3 A |
| Output current: for signal "1" permissible range, max. | 0.3 A |
| Output current: for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load: "0" to "1", max. | 100 µs |
| Output delay with resistive load: "1" to "0", max. | 500 µs |
| Parallel switching of two outputs: for logic links | Yes |
| Parallel switching of two outputs: for uprating | No |
| Parallel switching of two outputs: for redundant control of a load | Yes |
| Switching frequency: with resistive load, max. | 100 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 |
| Switching frequency: on lamp load, max. | 10 Hz |
| Total current of the outputs: Current per channel, max. | 0.3 A |
| Total current of the outputs: Current per group, max. | 2 A |
| Total current of the outputs: Current per module, max. | 8 A |
| Total current of the outputs (per module) horizontal installation: up to 60 °C, max. vertical installation | 8 A |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Diagnostics function | No |
|---|---|
| Substitute values connectable | No |
| Alarms: Diagnostic alarm | No |
| Alarms: Maintenance interrupt | No |
| Diagnoses: Monitoring the supply voltage | No |
| Diagnoses: Wire break | No |
| Diagnoses: Short-circuit | No |
| Diagnoses: Group error | No |
| Diagnostics indication LED: RUN LED | Yes; green LED |
| Diagnostics indication LED: ERROR LED | Yes; red LED |
| Diagnostics indication LED: MAINT LED | No |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | Yes; via SIMATIC TOP connect connection module |
| Diagnostics indication LED: Channel status display | Yes; via SIMATIC TOP connect connection module |
| Diagnostics indication LED: for channel diagnostics | No |
| Diagnostics indication LED: for module diagnostics | No |
| Potential separation channels: between the channels | No |
|---|---|
| Potential separation channels: between the channels, in groups of | 16; 32 when using SIMATIC TOP connect connection module |
| Potential separation channels: between the channels and backplane bus | Yes |
| Isolation tested with | 707 V DC (type test) |
|---|
| Suitable for safety functions | No |
|---|---|
| Suitable for safety-related tripping of standard modules | No |
| Ambient temperature during operation: horizontal installation, min. | -30 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | -30 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m |
| Width | 35 mm |
|---|---|
| Height | 147 mm |
| Depth | 129 mm |
| Weight, approx. | 270 g |
|---|
| Note: | Please order cable and connection modules separately |
|---|
| Miscellaneous Manufacturer Declara- | tion For use in hazard- |
|---|---|
| General Product Approval | ous locations |
| Net weight | 0.321 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.821 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | Low stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of DQ 64x24VDC/0.3A BA is 0.3 A.
The rated operational voltage of DQ 64x24VDC/0.3A BA is 24 V AC.
The tariff (HS) code on file for DQ 64x24VDC/0.3A BA is 85389091.
The EAN (GTIN) of DQ 64x24VDC/0.3A BA is 4047623411017.
DQ 64x24VDC/0.3A BA ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.