- Home
- All Products
- Siemens 6ES7522-1BL01-0AB0 SIMATIC S7-1500 DQ 32x24VDC/0.5A HF Digital Output Module Siemens 6ES7522-1BL01-0AB0 SIMATIC S7-1500 DQ 32x24VDC/0.5A HF Digital Output Module
Siemens 6ES7522-1BL01-0AB0 SIMATIC S7-1500 DQ 32x24VDC/0.5A HF Digital Output Module
Get Quote
- Description
The Siemens 6ES7522-1BL01-0AB0 is a SIMATIC S7-1500 digital output module, DQ 32x24VDC/0.5A HF, with 32 transistor outputs in groups of 8, each group fused to 4 A. It supports safety-oriented shutdown of load groups up to SIL 2 per IEC 62061 and PL d, Category 3, per ISO 13849-1. Short-circuit protection is electronically clocked with a typical 1 A response threshold.
Technical Specifications
| SKU | 6ES7522-1BL01-0AB0 |
| Brand | Siemens |
| Series | SIMATIC S7-1500 |
| Product type designation | DQ 32x24VDC/0.5A HF |
| Supply voltage, rated (DC) | 24 V |
| Digital outputs | 32, transistor, current-sourcing |
| Switching capacity, resistive load, max. | 0.5 A |
| Total current per group, max. | 4 A |
| Total current per module, max. | 16 A |
| Short-circuit protection | Yes, clocked electronically, response threshold typ. 1 A |
| Output delay, 0 to 1, max. | 100 microseconds |
| Output delay, 1 to 0, max. | 500 microseconds |
| Safety performance level | PL d, Category 3, per ISO 13849-1 |
| Safety integrity level | SIL 2 per IEC 62061 |
| Ambient temperature, horizontal, max. | 60 degrees C |
| Dimensions (W x H x D) | 35 x 147 x 129 mm |
| Weight, approx. | 280 g |
Selection Notes
This HF, high-feature, variant is the one to specify when downstream load groups need safety-related shutdown without a separate safety PLC or interposing relay: from HW functional status FS02 it supports safety-oriented tripping of standard modules up to SIL 2, PL d, Category 3. Each output group of 8 is fused to 4 A total, so grouping loads within that budget matters when sizing more than a couple of higher-current actuators per group. Choose a non-safety DQ module instead when the safety-related shutdown feature is not required.
Applications
Typical uses include driving 24 V DC solenoid valves, contactor coils, and indicator loads on S7-1500 machine controls where load groups must be shut down safely up to PL d / SIL 2, such as guard-interlocked actuator groups on packaging or material-handling equipment.