Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens SIMATIC S7-1500 6ES7522-1BF00-0AB0 (DQ 8x24VDC/2A HF) is an 8-channel transistor digital output module rated 24 V DC at 2 A per channel, 8 A per group, with PWM output on up to 2 channels and short-circuit protection. It supports safety-related shutdown of load groups to SIL 2 / PL d (Category 3) when tripped by an F-CPU, and mounts in a 35 mm wide S7-1500 backplane slot.
HF in the designation denotes the high-feature output module - the PWM function (2 channels, 2-100 ms cycle, 0.1% duty resolution) and the SIL 2 / PL d safety-related tripping support are features a standard (non-HF) 8x24VDC output module does not carry, so choose this variant specifically when a load needs PWM-controlled dimming or positioning, or when the output group must be safely shut down by an F-CPU. At 2 A per channel / 8 A per group, it suits DC solenoids, contactor coils, and small motor starters; group loads that together exceed 8 A need a second output group or a higher-current module.
Drives 24 V DC loads such as valve solenoids, indicator lamps, small DC motors, and contactor coils, including PWM-based dimming or positioning outputs and load groups requiring SIL 2 / PL d safety-related shutdown.
| Product type designation | DQ 8x24VDC/2A HF |
|---|---|
| HW functional status | FS03 |
| Firmware version | V2.2.0 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Prioritized startup | Yes |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with: PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| Engineering with: PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode: DQ | Yes |
| Operating mode: DQ with energy-saving function | Yes; with an application |
| Operating mode: PWM | Yes; FS02 and FW V2.1.0 or higher; two outputs can be operated with max. 500 Hz PWM |
| Operating mode: Cam control (switching at comparison values) | No |
| Operating mode: Oversampling | No |
| Operating mode: MSO | Yes |
| Operating mode: Integrated operating cycle counter | Yes |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes; through internal protection with 10 A per group |
| Current consumption, max. | 40 mA; 20 mA per group, no output is activated. |
|---|
| Part number | 6ES7522-1BF00-0AB0 |
|---|---|
| Type designation | DQ 8x24VDC/2A HF |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515079880 |
| ETIM class | EC001419 |
| eCl@ss | 27242204 |
| Rated value (DC) | 24 V |
|---|
| Power consumption from the backplane bus | 0.9 W |
|---|
| Power loss, typ. | 5.6 W; 6.8 W for PWM operation |
|---|
| Type of digital output | Transistor |
|---|---|
| Number of digital outputs | 8 |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | Yes |
| Short-circuit protection | Yes |
| Response threshold, typ. | 3 A |
| Limitation of inductive shutdown voltage to | -17 V |
| Controlling a digital input | Yes |
| Digital output functions, parameterizable: Freely usable digital output | Yes |
| Digital output functions, parameterizable: PWM output | Yes; FS02 and FW V2.1.0 or higher |
| Digital output functions, parameterizable: Number, max. | 2 |
| Digital output functions, parameterizable: Cycle duration, parameterizable | Yes; 2 ... 100 ms continuous |
| Digital output functions, parameterizable: ON period, min. | 0% |
| Digital output functions, parameterizable: ON period, max. | 100 % |
| Digital output functions, parameterizable: Resolution of the duty cycle | 0.1 % |
| Digital output functions, parameterizable: Minimum pulse duration | 300 µs |
| Switching capacity of the outputs: on lamp load, max. | 10 W |
| Load resistance range: lower limit | 12 Ω |
| Load resistance range: upper limit | 4 kΩ |
| Output voltage: for signal "1", min. | L+ (-0.8 V) |
| Output current: for signal "1" rated value | 2 A |
| Output current: for signal "1" permissible range, max. | 2.4 A; note derating specification for PWM operation |
| Output current: for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load: "0" to "1", typ. | 80 µs |
| Output delay with resistive load: "0" to "1", max. | 100 µs |
| Output delay with resistive load: "1" to "0", typ. | 300 µs |
| Output delay with resistive load: "1" to "0", max. | 500 µs |
| Parallel switching of two outputs: for logic links | Yes |
| Parallel switching of two outputs: for uprating | No |
| Parallel switching of two outputs: for redundant control of a load | Yes |
| Switching frequency: with resistive load, max. | 100 Hz; With PWM operation: 500 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13; max. 500 Hz with PWM operation only with external circuit; see additional description in the manual |
| Switching frequency: on lamp load, max. | 10 Hz |
| Total current of the outputs: Current per channel, max. | 2 A; see additional description in the manual |
| Total current of the outputs: Current per group, max. | 8 A; see additional description in the manual |
| Total current of the outputs: Current per module, max. | 16 A; see additional description in the manual |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Diagnostics function | Yes |
|---|---|
| Substitute values connectable | Yes |
| Alarms: Diagnostic alarm | Yes |
| Alarms: Maintenance interrupt | Yes |
| Diagnoses: Monitoring the supply voltage | Yes |
| Diagnoses: Wire break | No |
| Diagnoses: Short-circuit | Yes |
| Diagnoses: Group error | Yes |
| Diagnostics indication LED: RUN LED | Yes; green LED |
| Diagnostics indication LED: ERROR LED | Yes; red LED |
| Diagnostics indication LED: MAINT LED | Yes; Yellow LED |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | Yes; red LED |
| Diagnostics indication LED: for module diagnostics | Yes; red LED |
| Potential separation channels: between the channels | No |
|---|---|
| Potential separation channels: between the channels, in groups of | 4 |
| Potential separation channels: between the channels and backplane bus | Yes |
| Isolation tested with | 707 V DC (type test) |
|---|
| Suitable for safety functions | No |
|---|---|
| Suitable for safety-related tripping of standard modules | Yes; From FS03 |
| Highest safety class achievable for safety-related tripping of standard modules: Performance level according to ISO 13849-1 | PL d |
| signed firmware update | No |
|---|---|
| data integrity | No |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
|---|
| Width | 35 mm |
|---|---|
| Height | 147 mm |
| Depth | 129 mm |
| Weight, approx. | 240 g |
|---|
| Net weight | 0.282 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.782 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | Low stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of DQ 8x24VDC/2A HF is 2 A.
The rated operational voltage of DQ 8x24VDC/2A HF is 24 V DC.
The tariff (HS) code on file for DQ 8x24VDC/2A HF is 85389091.
The EAN (GTIN) of DQ 8x24VDC/2A HF is 4025515079880.
DQ 8x24VDC/2A HF ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.