Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens 6ES7521-1BH10-0AA0 is a SIMATIC S7-1500 digital input module, DI 16x24VDC BA, with 16 channels wired in one group and an IEC 61131 type-3 input characteristic. Input delay runs 3-4 ms on standard inputs, and the module ships with its 40-pole push-in front connector included, so it is ready to wire without ordering a connector separately.
16 channels in one potential group with P-reading (sourcing) inputs suit standard 24V DC sensors and pushbuttons wired common-negative; if the application needs channel-level isolation, look at a module with smaller input groups instead. The IEC 61131 type-3 characteristic and 3-4 ms input delay match typical PLC scan-time filtering, and 1000 m shielded cable runs support inputs at the far end of a large machine or line without a remote I/O station. It ships with 40-pole push-in front connectors included, so no separate connector order is needed.
Digital sensor and pushbutton wiring on SIMATIC S7-1500 CPUs — limit switches, proximity sensors, and operator pushbuttons in machine and process control panels.
| Product type designation | DI 16 x 24 V DC BA |
|---|---|
| HW functional status | FS01 |
| Firmware version | V1.0.0 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Prioritized startup | Yes |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V13 / V13 |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with: PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| Engineering with: PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode: DI | Yes |
| Operating mode: Counter | No |
| Operating mode: MSI | Yes |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Power consumption from the backplane bus | 1.05 W |
|---|
| Part number | 6ES7521-1BH10-0AA0 |
|---|---|
| Type designation | DI 16 x 24 V DC BA |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623402497 |
| ETIM class | EC001419 |
| eCl@ss | 27242204 |
| Power loss, typ. | 1.8 W |
|---|
| Number of digital inputs | 16 |
|---|---|
| Digital inputs, parameterizable | No |
| Sourcing/sinking input | P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
| Input voltage: Rated value (DC) | 24 V |
| Input voltage: for signal "0" | -30 to +5 V |
| Input voltage: for signal "1" | +11 to +30V |
| Input current: for signal "1", typ. | 2.7 mA |
| Input delay (for rated value of input voltage) for standard inputs: parameterizable | No |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Connectable encoders: 2-wire sensor | Yes |
|---|---|
| Connectable encoders: permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Diagnostics function | No |
|---|---|
| Alarms: Diagnostic alarm | No |
| Alarms: Hardware interrupt | No |
| Diagnoses: Monitoring the supply voltage | No |
| Diagnoses: Wire break | No |
| Diagnoses: Short-circuit | No |
| Diagnostics indication LED: RUN LED | Yes; green LED |
| Diagnostics indication LED: ERROR LED | Yes; red LED |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | No |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | No |
| Diagnostics indication LED: for module diagnostics | No |
| Potential separation channels: between the channels | No |
|---|---|
| Potential separation channels: between the channels, in groups of | 16 |
| Potential separation channels: between the channels and backplane bus | Yes |
| Isolation tested with | 707 V DC (type test) |
|---|
| Suitable for safety functions | No |
|---|
| signed firmware update | No |
|---|---|
| data integrity | No |
| Ambient temperature during operation: horizontal installation, min. | 0 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | 0 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Width | 25 mm |
|---|---|
| Height | 147 mm |
| eClass | 16 27-24-22-04 |
|---|---|
| ETIM | 10 EC001419 |
| IDEA | 4 3566 |
| UNSPSC | 15 32-15-17-05 |
| CCC-Ex NK / Nippon Kaiji Ky- | okai |
|---|
| Net weight | 0.316 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.816 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of DI 16 x 24 V DC BA is 24 V AC.
The tariff (HS) code on file for DI 16 x 24 V DC BA is 85389091.
The EAN (GTIN) of DI 16 x 24 V DC BA is 4047623402497.
DI 16 x 24 V DC BA ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.