How to Select an Interface Relay for PLC Outputs
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
The Siemens 6ES7515-2RN03-0AB0 is a SIMATIC S7-1500R CPU 1515R-2 PN with 1 MB integrated program memory and 4.5 MB data memory, built for redundant automation. It runs stand-alone or in a system-redundant (S2) pair with bumpless PROFINET IO switchover, using two PROFINET interfaces: X1 with a 2-port switch and X2 as a single port.
The R in CPU 1515R-2 PN marks it as a redundant CPU: it can run stand-alone like a standard 1515-2 PN or paired in S2 system redundancy, where PROFINET IO switches over between the two CPUs without an I/O dropout. Pick it over a non-R CPU when the process cannot tolerate a CPU fault causing a station-wide PROFINET interruption. The 1 MB program / 4.5 MB data split fits mid-size logic; if the application needs a larger retentive data area, a higher-memory R-CPU in the same family is the next step up. MRP ring support on the X1 interface lets the redundant pair also sit on a media-redundant ring without an external switch.
Process lines and continuous production where a PROFINET IO or CPU fault would otherwise stop the line, and applications already using PROFINET MRP ring topology that need CPU-level redundancy added without re-cabling.
| Product type designation | CPU 1515R-2 PN |
|---|---|
| HW functional status | FS05 |
| Firmware version | V4.1 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: SysLog | Yes |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V21 (FW V4.1) / V18 (FW V3.0); with older TIA Portal versions configurable as 6ES7515-2RM00-0AB0 |
| Redundancy: stand-alone operation | Yes |
| Configuration in Run (CiR) possible | Yes; V21.0 (FW V4.1) CiR functions: adding an IO device; reparameterizing an I/O module |
|---|
| Screen diagonal [cm] | 6.1 cm |
|---|
| Part number | 6ES7515-2RN03-0AB0 |
|---|---|
| Type designation | CPU 1515R-2 PN |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623412410 |
| ETIM class | EC000236 |
| eCl@ss | 27242207 |
| Number of keys | 8 |
|---|---|
| Mode buttons | 2 |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Mains buffering: Mains/voltage failure stored energy time | 5 ms |
| Mains buffering: Repeat rate, min. | 1/s |
| Current consumption (rated value) | 0.65 A |
|---|---|
| Current consumption, max. | 0.88 A |
| Inrush current, max. | 1.15 A |
| I2t | 0.6 A2·s |
| Infeed power to the backplane bus | 12 W |
|---|---|
| Power consumption from the backplane bus (balanced) | 6.2 W |
| Power loss, typ. | 3.6 W |
|---|
| Number of slots for SIMATIC memory card | 1 |
|---|---|
| SIMATIC memory card required | Yes |
| Work memory: integrated (for program) | 1 Mbyte |
| Work memory: integrated (for data) | 4.5 Mbyte |
| Load memory: Plug-in (SIMATIC Memory Card), max. | 32 Gbyte |
| Backup: maintenance-free | Yes |
| for bit operations, typ. | 20 ns |
|---|---|
| for word operations, typ. | 24 ns |
| for fixed point arithmetic, typ. | 32 ns |
| for floating point arithmetic, typ. | 128 ns |
| Number of elements (total) | 8 000; Blocks (OB, FB, FC, DB) and UDTs |
|---|---|
| DB: Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 |
| DB: Size, max. | 4.5 Mbyte; For non-optimized block accesses, the max. size of the DB is 64 KB |
| FB: Number range | 0 ... 65 535 |
| FB: Size, max. | 1 Mbyte |
| FC: Number range | 0 ... 65 535 |
| FC: Size, max. | 1 Mbyte |
| OB: Size, max. | 1 Mbyte |
| OB: Number of free cycle OBs | 100 |
| OB: Number of time alarm OBs | 20 |
| OB: Number of delay alarm OBs | 20 |
| OB: Number of cyclic interrupt OBs | 20; with minimum OB 3x cycle of 10 ms |
| OB: Number of process alarm OBs | 50 |
| OB: Number of DPV1 alarm OBs | 3 |
| OB: Number of startup OBs | 100 |
| OB: Number of asynchronous error OBs | 4 |
| OB: Number of synchronous error OBs | 2 |
| OB: Number of diagnostic alarm OBs | 1 |
| Nesting depth: per priority class | 24 |
| S7 counter: Number Retentivity | 2 048 |
|---|---|
| S7 counter: adjustable | Yes |
| IEC counter: Number Retentivity | Any (only limited by the main memory) |
| IEC counter: adjustable | Yes |
| S7 timer: Number Retentivity | 2 048 |
| S7 timer: adjustable | Yes |
| IEC timer: Number Retentivity | Any (only limited by the main memory) |
| IEC timer: adjustable | Yes |
| Retentive data area (incl. timers, counters, flags), max. | 472 kbyte; in total; for bit memories, timers, counters, DBs, and technology data (axes) |
|---|---|
| Extended retentive data area (incl. timers, counters, flags), max. | 4.5 Mbyte; When using PS 6 0W 24/48/60 V DC HF |
| Flag: Size, max. | 16 kbyte |
| Flag: Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte |
| Data blocks: Retentivity adjustable | Yes |
| Data blocks: Retentivity preset | No |
| Local data: per priority class, max. | 64 kbyte; max. 16 KB per block |
| Number of IO modules | 4 096; max. number of modules / submodules |
|---|---|
| I/O address area: Inputs | 32 kbyte; All inputs are in the process image |
| I/O address area: Outputs per integrated IO subsystem | 32 kbyte; All outputs are in the process image |
| I/O address area: Inputs (volume) | 8 kbyte |
| I/O address area: Outputs (volume) | 8 kbyte |
| Subprocess images: Number of subprocess images, max. | 31 |
| Number of distributed IO systems | 16; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET, but also by the connection of I/O via IE/PB- Links. |
|---|---|
| Number of IO Controllers: Integrated | 1 |
| Rack: Modules per rack, max. | 5; CPU + 2 PS + 2 CP |
| Clock: Type | Hardware clock |
|---|---|
| Clock: Backup time | 6 wk; At 40 °C ambient temperature, typically |
| Clock: Deviation per day, max. | 10 s; Typ.: 2 s |
| Operating hours counter: Number | 64 |
| Clock synchronization: supported | Yes |
| Clock synchronization: on Ethernet via NTP | Yes |
| Number of PROFINET interfaces | 2 |
|---|
| Interface types: RJ 45 (Ethernet) | Yes; X1 |
|---|---|
| Interface types: Number of ports | 2 |
| Interface types: integrated switch | Yes |
| Protocols: IP protocol | Yes; IPv4 |
| Protocols: PROFINET IO Controller | Yes |
| Protocols: PROFINET IO device | No |
| Protocols: SIMATIC communication | Yes; Only Server |
| Protocols: Open IE communication | Yes; Optionally also encrypted |
| Protocols: Web server | Yes |
| Protocols: Media redundancy | Yes |
| PROFINET IO Controller Services: Isochronous mode | No |
| PROFINET IO Controller Services: IRT | No |
| PROFINET IO Controller Services: Dynamic Frame Packing (DFP) | No |
| PROFINET IO Controller Services: PROFIenergy | Yes; per user program |
| PROFINET IO Controller Services: Prioritized startup | No |
| PROFINET IO Controller Services: Number of connectable IO Devices, max. | 64 |
| PROFINET IO Controller Services: Updating times Update time for RT | The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data |
| PROFINET IO Controller Services: for send cycle of 1 ms | 1 ms to 512 ms |
| Interface types: RJ 45 (Ethernet) | Yes; X2 |
|---|---|
| Interface types: Number of ports | 1 |
| Interface types: integrated switch | No |
| Protocols: IP protocol | Yes; IPv4 |
| Protocols: PROFINET IO Controller | No |
| Protocols: PROFINET IO Device | No |
| Protocols: SIMATIC communication | Yes; Only Server |
| Protocols: Open IE communication | Yes; Optionally also encrypted |
| Protocols: Web server | Yes |
| Protocols: Media redundancy | No |
| RJ 45 (Ethernet): 100 Mbps | Yes |
|---|---|
| RJ 45 (Ethernet): Autonegotiation | Yes |
| RJ 45 (Ethernet): Autocrossing | Yes |
| RJ 45 (Ethernet): Industrial Ethernet status LED | Yes |
| PROFIsafe | No |
|---|---|
| Number of connections: Number of connections, max. | 256; via integrated interfaces of the CPU and connected CPs |
| Number of connections: Number of connections reserved for ES/HMI/web | 10 |
| Number of connections: Number of connections via integrated interfaces | 128 |
| Number of connections: Number of S7 routing paths | 16 |
| Redundancy mode: PROFINET system redundancy (S2) | Yes |
| Redundancy mode: PROFINET system redundancy (R1) Media redundancy | No |
| Redundancy mode: Media redundancy | Yes; only via 1st interface (X1) |
| Redundancy mode: MRP | Yes; MRP Automanager according to IEC 62439-2 Edition 2.0 |
| Redundancy mode: MRP interconnection, supported | Yes; as MRP ring node according to IEC 62439-2 Edition 3.0 |
| Redundancy mode: MRPD | No |
| Redundancy mode: Switchover time on line break, typ. | 200 ms; PROFINET MRP |
| Redundancy mode: Number of stations in the ring, max. | 50; Only 16 are recommended, however |
| SIMATIC communication: PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
| SIMATIC communication: S7 routing | Yes |
| SIMATIC communication: S7 communication, as server | Yes |
| SIMATIC communication: S7 communication, as client | No |
| Open IE communication: TCP/IP | Yes |
| Open IE communication: Data length, max. | 64 kbyte |
| Open IE communication: several passive connections per port, supported | Yes |
| Open IE communication: ISO-on-TCP (RFC1006) | Yes |
| Open IE communication: UDP | Yes |
| Open IE communication: UDP multicast | Yes; max. 118 multicast circuits |
| Open IE communication: DHCP | No |
| Open IE communication: DNS | Yes |
| Open IE communication: SNMP | Yes |
| Open IE communication: DCP | Yes |
| Open IE communication: LLDP | Yes |
| Open IE communication: Encryption | Yes; Optional |
| Web server: HTTP | No |
| Web server: HTTPS | Yes; standard pages |
| Web server: web API | Yes |
| Web server: Number of sessions, max. | 100 |
| Web server: number of simultaneous HTTP calls, max. | 4 |
| Web server: HTTP request body, max. | 131 072 byte |
| OPC UA: Runtime license required | Yes; "Medium" license required per CPU |
| OPC UA: OPC UA Client | No |
| OPC UA: OPC UA Server | Yes; data access (read, write, subscribe), method call, custom address space, role-based access control |
| OPC UA: Application authentication | Yes |
| OPC UA: Security policies | available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256, Aes128Sha256RsaOaep, Aes256Sha256RsaPss |
| OPC UA: User authentication | "anonymous" or by user name & password |
| OPC UA: GDS support (certificate management) | Yes |
| OPC UA: Number of sessions, max. | 24 |
| OPC UA: Number of subscriptions per session, max. | 25 |
| OPC UA: Sampling interval, min. | 250 ms |
| OPC UA: Publishing interval, min. | 250 ms |
| OPC UA: Number of server methods, max. | 500; max. 25 concurrently running jobs each for asynchronous instructions OPC_UA_ServerMethodPre and OPC_UA_ServerMethodPost |
| OPC UA: Number of inputs/outputs per server method, max. | 20 |
| OPC UA: Number of monitored items, recommended max. | 2 000; for 1 s sampling interval and 1 s send interval |
| OPC UA: Number of server interfaces, max. | 10 of each "Server interfaces" / "Companion specification" type and 20 of the type "Reference namespace" |
| OPC UA: Number of nodes for user-defined server interfaces, max. | 30 000 |
| OPC UA: Alarms and Conditions | No |
| Further protocols: MODBUS | Yes; MODBUS TCP |
| Number of login stations for message functions, max. | 64 |
|---|---|
| number of subscriptions, max. | 500 |
| number of tags/attributes for subscriptions, max. | 8 000 |
| Program alarms | Yes |
| Number of configurable program messages, max. | 10 000; Program messages are generated by the "Program_Alarm" block, ProDiag or GRAPH |
| Number of loadable program messages in RUN, max. | 10 000 |
| Number of simultaneously active program alarms: Number of program alarms | 1 000 |
| Number of simultaneously active program alarms: Number of alarms for system diagnostics | 200 |
| Joint commission (Team Engineering) | Yes; Parallel online access possible for up to 10 engineering systems |
|---|---|
| Status block | Yes; up to 8 simultaneously |
| Single step | No |
| Number of breakpoints | 8; Breakpoints are only supported in RUN-Solo status |
| Profiling | Yes |
| Status/control: Status/control variable | Yes |
| Status/control: Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
| Number of variables, max.: of which status variables, max. | 200; per job |
| Number of variables, max.: of which control variables, max. | 200; per job |
| Forcing: Forcing | Yes |
| Forcing: Forcing, variables | Peripheral inputs/outputs |
| Forcing: Number of variables, max. | 200 |
| Diagnostic buffer: present | Yes |
| Diagnostic buffer: Number of entries, max. | 3 200 |
| Diagnostic buffer: of which powerfail-proof | 500 |
| Traces: Number of configurable Traces | 4 |
| Traces: Memory size per trace, max. | 512 kbyte |
| Diagnostics indication LED: RUN/STOP LED | Yes |
|---|---|
| Diagnostics indication LED: ERROR LED | Yes |
| Diagnostics indication LED: MAINT LED | Yes |
| Diagnostics indication LED: STOP ACTIVE LED | Yes |
| Diagnostics indication LED: Connection display LINK TX/RX | Yes |
| Motion Control | No |
|---|---|
| Controller: PID_Compact | Yes; Universal PID controller with integrated optimization |
| Controller: PID_3Step | Yes; PID controller with integrated optimization for valves |
| Controller: PID-Temp | Yes; PID controller with integrated optimization for temperature |
| Counting and measuring | Yes |
| Siemens Eco Profile (SEP) | Siemens EcoTech |
|---|---|
| Ecological footprint: environmental product declaration Global warming potential | Yes |
| Ecological footprint: global warming potential, (total) [CO2 eq] | 100 kg |
| Ecological footprint: global warming potential, (during production) [CO2 eq] | 25.8 kg |
| Ecological footprint: global warming potential, (during operation) [CO2 eq] | 75.2 kg |
| Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] | -0.83 kg |
| PROFINET Security Class | 1 |
|---|---|
| signed firmware update | Yes |
| Secure Boot | Yes |
| securely removing data | Yes |
| Ambient temperature during operation: horizontal installation, min. | -30 °C; No condensation |
|---|---|
| Ambient temperature during operation: vertical installation, min. | -30 °C; No condensation |
| Ambient temperature during storage/transportation: min. | -40 °C |
| Ambient temperature during storage/transportation: max. | 70 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Programming Programming language: LAD | Yes |
|---|---|
| Programming Programming language: FBD | Yes |
| Programming Programming language: STL | Yes |
| Programming Programming language: SCL | Yes |
| Programming Programming language: CFC | Yes |
| Programming Programming language: GRAPH | Yes |
| Know-how protection: User program protection/password protection | Yes |
| Know-how protection: Copy protection | No |
| Know-how protection: Block protection | Yes |
| Access protection: protection of confidential configuration data | Yes |
| Access protection: Password for display | Yes |
| Access protection: Protection level: Write protection | Yes |
| Access protection: Protection level: Read/write protection | Yes |
| Access protection: Protection level: Write protection for Failsafe | No |
| Access protection: Protection level: Complete protection | Yes |
| Access protection: User administration | Yes; device-wide and centralized |
| Access protection: Number of users | 100 |
| Access protection: Number of groups | 100 |
| Access protection: Number of roles | 50 |
| Cycle time monitoring: lower limit | adjustable minimum cycle time |
| Cycle time monitoring: upper limit | adjustable maximum cycle time |
| Width | 70 mm |
|---|---|
| Height | 147 mm |
| Depth | 129 mm |
| Weight, approx. | 456 g |
|---|
| Net weight | 0.507 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 1.007 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of CPU 1515R-2 PN is 0.65 A.
The rated operational voltage of CPU 1515R-2 PN is 24 V AC.
The tariff (HS) code on file for CPU 1515R-2 PN is 85371091.
The EAN (GTIN) of CPU 1515R-2 PN is 4047623412410.
CPU 1515R-2 PN ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
Compare the 5 main PLC types, IEC 61131-3 languages, scan-time sizing, and brand options to choose the right controller for your plant. Shop at...
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.