A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
The Siemens 6ES7511-1CL03-0AB0 is a SIMATIC S7-1500 compact CPU 1511C-1 PN with 300 KB of program memory and 1.5 MB of data memory, plus onboard 16 digital inputs, 16 digital outputs, 5 analog inputs and 2 analog outputs. Its PROFINET IRT interface includes a 2-port switch and processes bit operations in 6 ns, and it requires a SIMATIC Memory Card to run.
The compact (C) CPU integrates discrete and analog I/O plus 6 high-speed counters directly on the module, removing the need for a separate signal module in a small or mid-size machine; pick a non-compact CPU such as a plain 1511-1 PN instead when the application needs more distributed I/O or additional communication module slots, since onboard I/O is fixed and cannot be resized. The 4 integrated PTO/PWM channels support direct stepper or servo pulse-train control without adding a positioning module.
Standalone or single-cell machine control that needs integrated discrete and analog I/O together with pulse-train axis control (PTO/PWM) and PROFINET IRT connectivity to distributed I/O or drives, without a separate signal module.
| Product type designation | CPU 1511C-1 PN |
|---|---|
| HW functional status | FS01 |
| Firmware version | V4.1 |
| FW update possible | Yes |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | Yes; with minimal OB 6x cycle of 500 μs (distributed) |
| Product function: SysLog | Yes |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V21 (FW V4.1) / V19 (FW V3.1) or higher; configurable with older TIA Portal versions as 6ES7511-1CK01-0AB0 |
| via dataset | Yes |
|---|
| Screen diagonal [cm] | 3.45 cm |
|---|
| Part number | 6ES7511-1CL03-0AB0 |
|---|---|
| Type designation | CPU 1511C-1 PN |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623412977 |
| ETIM class | EC000236 |
| eCl@ss | 27242207 |
| Number of keys | 8 |
|---|---|
| Mode buttons | 2 |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 19.2 V; 20.4 V DC, for supplying the digital inputs/outputs |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Mains buffering: Mains/voltage failure stored energy time | 5 ms; Refers to the power supply on the CPU section |
| Mains buffering: Repeat rate, min. | 1/s |
| Current consumption (rated value) | 0.62 A; without DI/DO load |
|---|---|
| Current consumption, max. | 0.9 A; without DI/DO load |
| Inrush current, max. | 1.22 A; Rated value |
| I2t | 0.6 A2·s |
| Digital inputs: from load voltage L+ (without load), max. | 20 mA; per group |
| Digital outputs: from load voltage L+, max. | 30 mA; Per group, without load |
| Number of outputs | 1; One common 24 V encoder supply |
|---|---|
| 24 V encoder supply: 24 V | Yes; L+ (-0.8 V) |
| 24 V encoder supply: Short-circuit protection | Yes |
| 24 V encoder supply: Output current, max. | 1 A |
| Infeed power to the backplane bus | 10 W |
|---|---|
| Power consumption from the backplane bus (balanced) | 8.5 W |
| Power loss, typ. | 5 W |
|---|
| Number of slots for SIMATIC memory card | 1 |
|---|---|
| SIMATIC memory card required | Yes |
| Work memory: integrated (for program) | 300 kbyte |
| Work memory: integrated (for data) | 1.5 Mbyte |
| Load memory: Plug-in (SIMATIC Memory Card), max. | 32 Gbyte |
| Backup: maintenance-free | Yes |
| for bit operations, typ. | 6 ns |
|---|---|
| for word operations, typ. | 7 ns |
| for fixed point arithmetic, typ. | 9 ns |
| for floating point arithmetic, typ. | 37 ns |
| Number of elements (total) | 4 000; Blocks (OB, FB, FC, DB) and UDTs |
|---|---|
| DB: Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 |
| DB: Size, max. | 1.5 Mbyte; For DBs with absolute addressing, the max. size is 64 KB |
| FB: Number range | 0 ... 65 535 |
| FB: Size, max. | 300 kbyte |
| FC: Number range | 0 ... 65 535 |
| FC: Size, max. | 300 kbyte |
| OB: Size, max. | 300 kbyte |
| OB: Number of free cycle OBs | 100 |
| OB: Number of time alarm OBs | 20 |
| OB: Number of delay alarm OBs | 20 |
| OB: Number of cyclic interrupt OBs | 20; With minimum OB 3x cycle of 250 µs |
| OB: Number of process alarm OBs | 50 |
| OB: Number of DPV1 alarm OBs | 3 |
| OB: Number of isochronous mode OBs | 1 |
| OB: Number of startup OBs | 100 |
| OB: Number of asynchronous error OBs | 4 |
| OB: Number of synchronous error OBs | 2 |
| OB: Number of diagnostic alarm OBs | 1 |
| Nesting depth: per priority class | 24 |
| S7 counter: Number Retentivity | 2 048 |
|---|---|
| S7 counter: adjustable | Yes |
| IEC counter: Number Retentivity | Any (only limited by the main memory) |
| IEC counter: adjustable | Yes |
| S7 timer: Number Retentivity | 2 048 |
| S7 timer: adjustable | Yes |
| IEC timer: Number Retentivity | Any (only limited by the main memory) |
| IEC timer: adjustable | Yes |
| Retentive data area (incl. timers, counters, flags), max. | 216 kbyte; in total; for bit memories, timers, counters, DBs, and technology data (axes) |
|---|---|
| Extended retentive data area (incl. timers, counters, flags), max. | 1.5 Mbyte; When using PS 6 0W 24/48/60 V DC HF |
| Flag: Size, max. | 16 kbyte |
| Flag: Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte |
| Data blocks: Retentivity adjustable | Yes |
| Data blocks: Retentivity preset | No |
| Local data: per priority class, max. | 64 kbyte; max. 16 KB per block |
| Number of IO modules | 2 048; max. number of modules / submodules |
|---|---|
| I/O address area: Inputs | 32 kbyte; All inputs are in the process image |
| I/O address area: Outputs per integrated IO subsystem | 32 kbyte; All outputs are in the process image |
| I/O address area: Inputs (volume) | 8 kbyte |
| I/O address area: Outputs (volume) per CM/CP | 8 kbyte |
| I/O address area: Outputs (volume) | 8 kbyte |
| Subprocess images: Number of subprocess images, max. | 32 |
| Number of distributed IO systems | 32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) |
|---|---|
| Number of DP masters: Via CM | 4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total |
| Number of IO Controllers: Integrated | 1 |
| Number of IO Controllers: via CM | 4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total |
| Rack: Modules per rack, max. | 32; CPU + 31 modules |
| Rack: Number of lines, max. | 1 |
| PtP CM: Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots |
| Clock: Type | Hardware clock |
|---|---|
| Clock: Backup time | 6 wk; At 40 °C ambient temperature, typically |
| Clock: Deviation per day, max. | 10 s; Typ.: 2 s |
| Operating hours counter: Number | 64 |
| Clock synchronization: supported | Yes |
| Clock synchronization: to DP, master | Yes; via PROFIBUS CM / CP |
| Clock synchronization: on DP, device | Yes; via PROFIBUS CM / CP |
| Clock synchronization: in AS, master | Yes |
| Clock synchronization: in AS, device | Yes |
| Clock synchronization: on Ethernet via NTP | Yes |
| integrated channels (DI) | 16 |
|---|---|
| Digital inputs, parameterizable | Yes |
| Sourcing/sinking input | P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
| Digital input functions, parameterizable: Gate start/stop | Yes |
| Digital input functions, parameterizable: Capture | Yes |
| Digital input functions, parameterizable: Synchronization | Yes |
| Input voltage: Type of input voltage | DC |
| Input voltage: Rated value (DC) | 24 V |
| Input voltage: for signal "0" | -3 to +5V |
| Input voltage: for signal "1" | +11 to +30V |
| Input current: for signal "1", typ. | 2.5 mA |
| Input delay (for rated value of input voltage) for standard inputs: parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms |
| Cable length: shielded, max. | 1 000 m; 600 m for technological functions; depending on input frequency, encoder and cable quality; max. 50 m at 100 kHz |
| Cable length: unshielded, max. | 600 m; for technological functions: No |
| Type of digital output | Transistor |
|---|---|
| integrated channels (DO) | 16 |
| Current-sourcing | Yes; Push-pull output |
| Short-circuit protection | Yes; electronic/thermal |
| Response threshold, typ. | 1.6 A with standard output, 0.5 A with high-speed output; see manual for details |
| Limitation of inductive shutdown voltage to | connector X11: -0.8 V |
| Controlling a digital input | Yes |
| Accuracy of pulse duration | Up to ±100 ppm ±2 μs at high-speed output; see manual for details |
| minimum pulse duration | 2 µs; With High Speed output |
| Digital output functions, parameterizable: Switching tripped by comparison values | Yes; As output signal of a high-speed counter |
| Digital output functions, parameterizable: PWM output | Yes |
| Digital output functions, parameterizable: Number, max. | 4 |
| Digital output functions, parameterizable: Cycle duration, parameterizable | Yes |
| Digital output functions, parameterizable: ON period, min. | 0% |
| Digital output functions, parameterizable: ON period, max. | 100 % |
| Digital output functions, parameterizable: Resolution of the duty cycle | 0.0036 %; For S7 analog format, min. 40 ns |
| Digital output functions, parameterizable: Frequency output | Yes |
| Switching capacity of the outputs: with resistive load, max. | 0.5 A; 0.1 A with high-speed output, i.e. when using a high-speed output; see manual for details |
| Switching capacity of the outputs: on lamp load, max. | 5 W; 1 W with high-speed output, i.e. when using a high-speed output; see manual for details |
| Load resistance range: lower limit | 48 Ω; 240 ohms with high-speed output, i.e. when using a high-speed output; see manual for details |
| Load resistance range: upper limit | 12 kΩ |
| Output voltage: Type of output voltage | DC |
| Output voltage: for signal "0", max. | 1 V; With high-speed output, i.e. when using a high-speed output; see manual for details |
| Output voltage: for signal "1", min. | 23.2 V; L+ (-0.8 V) |
| Output current: for signal "1" rated value | 0.5 A; 0.1 A with high-speed output, i.e. when using a high-speed output, observe derating; see manual for details |
| Output current: for signal "1" permissible range, min. | 2 mA |
| Output current: for signal "1" permissible range, max. | 0.6 A; 0.12 A with high-speed output, i.e. when using a high-speed output, observe derating; see manual for details |
| Output current: for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load: "0" to "1", max. | 200 µs |
| Output delay with resistive load: "1" to "0", max. for technological functions | 500 µs; Load-dependent |
| Output delay with resistive load: "1" to "0", max. | 5 µs; Depending on the output used, see additional description in manual |
| Parallel switching of two outputs: for logic links | Yes; for technological functions: No |
| Parallel switching of two outputs: for uprating | No |
| Parallel switching of two outputs: for redundant control of a load | Yes; for technological functions: No |
| Switching frequency: with resistive load, max. | 100 kHz; For high-speed output, 100 Hz for standard output |
| Switching frequency: with inductive load, max. | 0.5 Hz; Acc. to IEC 60947-5-1, DC-13; observe derating curve |
| Switching frequency: on lamp load, max. | 10 Hz |
| Total current of the outputs: Current per channel, max. | 0.5 A; see additional description in the manual |
| Total current of the outputs: Current per group, max. | 8 A; see additional description in the manual |
| Total current of the outputs: Current per power supply, max. for technological functions | 4 A; 2 power supplies for each group, current per power supply max. 4 A, see additional description in manual |
| Relay outputs: Number of relay outputs | 0 |
| Cable length: shielded, max. | 1 000 m; 600 m for technological functions; depending on output frequency, load, and cable quality; max. 50 m at 100 kHz |
| Cable length: unshielded, max. | 600 m; for technological functions: No |
| Number of analog inputs | 5; 4x for U/I, 1x for R/RTD |
|---|---|
| For current measurement | 4; max. |
| For voltage measurement | 4; max. |
| For resistance/resistance thermometer measurement | 1 |
| integrated channels (AI) | 5 |
| permissible input voltage for voltage input (destruction limit), max. | 28.8 V |
| permissible input current for current input (destruction limit), max. | 40 mA |
| Cycle time (all channels), min. | 1 ms; Dependent on the parameterized interference frequency suppression; for details, see conversion procedure in manual |
| Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
| Input ranges (rated values), voltages: 0 to +10 V | Yes; Physical measuring range: ± 10 V |
| Input ranges (rated values), voltages: Input resistance (0 to 10 V) | 100 kΩ |
| Input ranges (rated values), voltages: 1 V to 5 V | Yes; Physical measuring range: ± 10 V |
| Input ranges (rated values), voltages: Input resistance (1 V to 5 V) | 100 kΩ |
| Input ranges (rated values), voltages: -10 V to +10 V | Yes |
| Input ranges (rated values), voltages: Input resistance (-10 V to +10 V) | 100 kΩ |
| Input ranges (rated values), voltages: -5 V to +5 V | Yes; Physical measuring range: ± 10 V |
| Input ranges (rated values), voltages: Input resistance (-5 V to +5 V) | 100 kΩ |
| Input ranges (rated values), currents: 0 to 20 mA | Yes; Physical measuring range: ± 20 mA |
| Input ranges (rated values), currents: Input resistance (0 to 20 mA) | 50 Ω; Plus approx. 55 ohm for overvoltage protection by PTC |
| Input ranges (rated values), currents: -20 mA to +20 mA | Yes |
| Input ranges (rated values), currents: Input resistance (-20 mA to +20 mA) | 50 Ω; Plus approx. 55 ohm for overvoltage protection by PTC |
| Input ranges (rated values), currents: 4 mA to 20 mA | Yes; Physical measuring range: ± 20 mA |
| Input ranges (rated values), currents: Input resistance (4 mA to 20 mA) | 50 Ω; Plus approx. 55 ohm for overvoltage protection by PTC |
| Input ranges (rated values), resistance thermometer: Ni 100 | Yes; Standard/climate |
| Input ranges (rated values), resistance thermometer: Input resistance (Ni 100) | 10 MΩ |
| Input ranges (rated values), resistance thermometer: Pt 100 | Yes; Standard/climate |
| Input ranges (rated values), resistors: 0 to 150 ohms | Yes; Physical measuring range: 0 ... 600 ohms |
| Input ranges (rated values), resistors: Input resistance (0 to 150 ohms) | 10 MΩ |
| Input ranges (rated values), resistors: 0 to 300 ohms | Yes; Physical measuring range: 0 ... 600 ohms |
| Input ranges (rated values), resistors: Input resistance (0 to 300 ohms) | 10 MΩ |
| Input ranges (rated values), resistors: 0 to 600 ohms | Yes |
| Input ranges (rated values), resistors: Input resistance (0 to 600 ohms) | 10 MΩ |
| Cable length: shielded, max. | 800 m; for U/I, 200 m for R/RTD |
| integrated channels (AO) | 2 |
|---|---|
| Voltage output, short-circuit protection | Yes |
| Cycle time (all channels), min. | 1 ms; Dependent on the parameterized interference frequency suppression; for details, see conversion procedure in manual |
| Output ranges, voltage: 0 to 10 V | Yes |
| Output ranges, voltage: 1 V to 5 V | Yes |
| Output ranges, voltage: -10 V to +10 V | Yes |
| Output ranges, current: 0 to 20 mA | Yes |
| Output ranges, current: -20 mA to +20 mA | Yes |
| Output ranges, current: 4 mA to 20 mA | Yes |
| Load impedance (in rated range of output): with voltage outputs, min. | 1 kΩ |
| Load impedance (in rated range of output): with current outputs, max. | 500 Ω |
| Cable length: shielded, max. | 200 m |
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 16 bit |
|---|---|
| Integration and conversion time/resolution per channel: Integration time, parameterizable | Yes; 2.5 / 16.67 / 20 / 100 ms, acts on all channels |
| Integration and conversion time/resolution per channel: Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 |
| Smoothing of measured values: parameterizable | Yes |
| Smoothing of measured values: Step: None | Yes |
| Smoothing of measured values: Step: low | Yes |
| Smoothing of measured values: Step: Medium | Yes |
| Smoothing of measured values: Step: High | Yes |
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 16 bit |
|---|---|
| Settling time: for resistive load | 1.5 ms |
| Settling time: for capacitive load | 2.5 ms |
| Settling time: for inductive load | 2.5 ms |
| Connection of signal encoders: for voltage measurement | Yes |
|---|---|
| Connection of signal encoders: for current measurement as 4-wire transducer | Yes |
| Connection of signal encoders: for resistance measurement with two-wire connection | Yes |
| Connectable encoders: 2-wire sensor | Yes |
| Connectable encoders: permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Encoder signals, incremental encoder (asymmetrical): Input voltage | 24 V |
| Encoder signals, incremental encoder (asymmetrical): Input frequency, max. | 100 kHz |
| Encoder signals, incremental encoder (asymmetrical): Counting frequency, max. | 400 kHz; with quadruple evaluation |
| Encoder signals, incremental encoder (asymmetrical): Signal filter, parameterizable | Yes |
| Encoder signals, incremental encoder (asymmetrical): Incremental encoder with A/B tracks, 90° phase offset | Yes |
| Encoder signals, incremental encoder (asymmetrical): pulse encoder | Yes |
| Linearity error (relative to input range), (+/-) | 0.1 % |
|---|---|
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, max. | -60 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
| Output ripple (relative to output range, bandwidth 0 to 50 kHz), | 0.02 % |
| Linearity error (relative to output range), (+/-) | 0.15 % |
|---|---|
| Temperature error (relative to output range), (+/-) | 0.005 %/K |
| Crosstalk between the outputs, max. | -80 dB |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
| Operational error limit in overall temperature range: Voltage, relative to input range, (+/-) | 0.3 % |
| Operational error limit in overall temperature range: Current, relative to input range, (+/-) | 0.3 % |
| Operational error limit in overall temperature range: Resistance, relative to input range, (+/-) | 0.3 % |
| Basic error limit (operational limit at 25 °C): Voltage, relative to input range, (+/-) | 0.2 % |
| Basic error limit (operational limit at 25 °C): Current, relative to input range, (+/-) | 0.2 % |
| Basic error limit (operational limit at 25 °C): Resistance, relative to input range, (+/-) | 0.2 % |
| Basic error limit (operational limit at 25 °C): Resistance thermometer, relative to input range, (+/-) | Pt100 Standard: ±1 K, Pt100 Climate: ±0.5 K, Ni100 Standard: ±0.6 K, Ni100 Climate: ±0.5 K |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency: Series mode interference (peak value of interference < rated value of input range), min. | 30 dB |
| Number of PROFINET interfaces 1. Interface | 1 |
|---|---|
| Interface types: RJ 45 (Ethernet) | Yes; X1 |
| Interface types: Number of ports | 2 |
| Interface types: integrated switch | Yes |
| Protocols: IP protocol | Yes; IPv4 |
| Protocols: PROFINET IO Controller | Yes |
| Protocols: PROFINET IO Device | Yes |
| Protocols: SIMATIC communication | Yes |
| Protocols: Open IE communication | Yes; Optionally also encrypted |
| Protocols: Web server | Yes |
| Protocols: Media redundancy | Yes |
| PROFINET IO Controller Services: Isochronous mode | Yes |
| PROFINET IO Controller Services: Direct data exchange | Yes; Requirement: IRT and isochronous mode (MRPD optional) |
| PROFINET IO Controller Services: IRT | Yes |
| PROFINET IO Controller Services: Dynamic Frame Packing (DFP) | Yes |
| PROFINET IO Controller Services: PROFIenergy | Yes; per user program |
| PROFINET IO Controller Services: Prioritized startup | Yes; Max. 32 PROFINET devices |
| PROFINET IO Controller Services: Number of connectable IO Devices, max. | 128; In total, up to 512 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET |
| PROFINET IO Controller Services: Of which IO devices with IRT, max. | 64 |
| PROFINET IO Controller Services: of which in line, max. | 128 |
| PROFINET IO Controller Services: Number of IO Devices that can be simultaneously activated/deactivated, max. | 8; in total across all interfaces |
| PROFINET IO Controller Services: Number of IO Devices per tool, max. | 8 |
| PROFINET IO Controller Services: Updating times Update time for IRT | The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data |
| PROFINET IO Controller Services: for send cycle of 250 µs | 250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 500 µs of the isochronous OB is decisive |
| PROFINET IO Controller Services: for send cycle of 500 µs | 500 µs to 8 ms |
| PROFINET IO Controller Services: for send cycle of 1 ms | 1 ms to 16 ms |
| PROFINET IO Controller Services: for send cycle of 2 ms | 2 ms to 32 ms |
| PROFINET IO Controller Services: for send cycle of 4 ms | 4 ms to 64 ms |
| PROFINET IO Controller Services: With IRT and parameterization of "odd" send cycles Update time for RT | Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs) |
| PROFINET IO Device Services: Isochronous mode | No |
| PROFINET IO Device Services: IRT | Yes |
| PROFINET IO Device Services: Dynamic Frame Packing (DFP) | No |
| PROFINET IO Device Services: PROFIenergy | Yes; per user program |
| PROFINET IO Device Services: Prioritized startup | Yes |
| PROFINET IO Device Services: Shared device | Yes |
| PROFINET IO Device Services: Number of IO Controllers with shared device, max. | 4 |
| PROFINET IO Device Services: activation/deactivation of I-devices | Yes; per user program |
| PROFINET IO Device Services: Asset management record | Yes; per user program |
| RJ 45 (Ethernet): 100 Mbps | Yes |
|---|---|
| RJ 45 (Ethernet): Autonegotiation | Yes |
| RJ 45 (Ethernet): Autocrossing | Yes |
| RJ 45 (Ethernet): Industrial Ethernet status LED | Yes |
| Number of connections: Number of connections, max. | 128; via integrated interfaces of the CPU and connected CPs / CMs |
|---|---|
| Number of connections: Number of connections reserved for ES/HMI/web | 10 |
| Number of connections: Number of connections via integrated interfaces | 88 |
| Number of connections: Number of S7 routing paths | 16 |
| Redundancy mode: PROFINET system redundancy (S2) | No |
| Redundancy mode: PROFINET system redundancy (R1) | No |
| Redundancy mode: H-Sync forwarding Media redundancy | Yes |
| Redundancy mode: Media redundancy | only via 1st interface (X1) |
| Redundancy mode: MRP | Yes; MRP Automanager according to IEC 62439-2 Edition 2.0, MRP Manager; MRP Client |
| Redundancy mode: MRP interconnection, supported | Yes; as MRP ring node according to IEC 62439-2 Edition 3.0 |
| Redundancy mode: MRPD | Yes; Requirement: IRT |
| Redundancy mode: Switchover time on line break, typ. | 200 ms; For MRP, bumpless for MRPD |
| Redundancy mode: Number of stations in the ring, max. | 50 |
| SIMATIC communication: PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
| SIMATIC communication: S7 routing | Yes |
| SIMATIC communication: Data record routing | Yes |
| SIMATIC communication: S7 communication, as server | Yes |
| SIMATIC communication: S7 communication, as client | Yes |
| SIMATIC communication: User data per job, max. | See online help (S7 communication, user data size) |
| Open IE communication: TCP/IP | Yes |
| Open IE communication: Data length, max. | 64 kbyte |
| Open IE communication: several passive connections per port, supported | Yes |
| Open IE communication: ISO-on-TCP (RFC1006) | Yes |
| Open IE communication: UDP | Yes |
| Open IE communication: UDP multicast | Yes; max. 78 multicast circuits |
| Open IE communication: DHCP | Yes |
| Open IE communication: DNS | Yes |
| Open IE communication: SNMP | Yes |
| Open IE communication: DCP | Yes |
| Open IE communication: LLDP | Yes |
| Open IE communication: Encryption | Yes; Optional |
| Web server: HTTP | Yes; Standard and user pages |
| Web server: HTTPS | Yes; Standard and user pages |
| web API: Number of sessions, max. | 50 |
| web API: number of simultaneous HTTP calls, max. | 4 |
| web API: HTTP request body, max. | 131 072 byte |
| OPC UA: Runtime license required | Yes; "Small" license required |
| OPC UA: OPC UA Client | Yes; Data Access (registered Read/Write), Method Call |
| OPC UA: Application authentication | Yes |
| OPC UA: Security policies | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 |
| OPC UA: User authentication | "anonymous" or by user name & password |
| OPC UA: Number of connections, max. | 4 |
| OPC UA: Number of nodes of the client interfaces, recommended max. | 1 000 |
| Number of elements for one call of 300 OPC_UA_NodeGetHandleList/OPC_UA_ReadList/OPC_UA_WriteList, max.: Number of elements for one call of OPC_UA_NameSpaceGetIndexList, max. | 20 |
| Further protocols: MODBUS | Yes; MODBUS TCP |
| Number of login stations for message functions, max. | 32 |
|---|---|
| number of subscriptions, max. | 250 |
| number of tags/attributes for subscriptions, max. | 2 000 |
| Program alarms | Yes |
| Number of configurable program messages, max. | 5 000; Program messages are generated by the "Program_Alarm" block, ProDiag or GRAPH |
| Number of loadable program messages in RUN, max. | 5 000 |
| Number of simultaneously active program alarms: Number of program alarms | 600 |
| Number of simultaneously active program alarms: Number of alarms for system diagnostics | 100 |
| Joint commission (Team Engineering) | Yes; Parallel online access possible for up to 5 engineering systems |
|---|---|
| Status block | Yes; Up to 8 simultaneously (in total across all ES clients) |
| Single step | No |
| Number of breakpoints | 8 |
| Profiling | Yes |
| Status/control: Status/control variable | Yes |
| Status/control: Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
| Number of variables, max.: of which status variables, max. | 200; per job |
| Number of variables, max.: of which control variables, max. | 200; per job |
| Forcing: Forcing | Yes |
| Forcing: Forcing, variables | Peripheral inputs/outputs |
| Forcing: Number of variables, max. | 200 |
| Diagnostic buffer: present | Yes |
| Diagnostic buffer: Number of entries, max. | 1 000 |
| Diagnostic buffer: of which powerfail-proof | 500 |
| Traces: Number of configurable Traces | 4 |
| Traces: Memory size per trace, max. | 512 kbyte |
| Alarms: Diagnostic alarm | Yes |
|---|---|
| Alarms: Hardware interrupt | Yes |
| Diagnoses: Monitoring the supply voltage | Yes |
| Diagnoses: Wire break | Yes; for analog inputs/outputs, see description in manual |
| Diagnoses: Short-circuit | Yes; for analog outputs, see description in manual |
| Diagnoses: A/B transition error at incremental encoder | Yes |
| Diagnostics indication LED: RUN/STOP LED | Yes |
| Diagnostics indication LED: ERROR LED | Yes |
| Diagnostics indication LED: MAINT LED | Yes |
| Diagnostics indication LED: STOP ACTIVE LED | Yes |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | Yes |
| Diagnostics indication LED: Channel status display | Yes |
| Diagnostics indication LED: for channel diagnostics | Yes; For analog inputs/outputs |
| Diagnostics indication LED: Connection display LINK TX/RX | Yes |
| Motion Control | Yes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool |
|---|---|
| Number of available Motion Control resources for technology objects | 1 120 |
| Required Motion Control resources: per speed-controlled axis | 40 |
| Required Motion Control resources: per positioning axis | 80 |
| Required Motion Control resources: per synchronous axis | 160 |
| Required Motion Control resources: per external encoder | 80 |
| Required Motion Control resources: per output cam | 20 |
| Required Motion Control resources: per cam track | 160 |
| Required Motion Control resources: per probe | 40 |
| Positioning axis: Number of positioning axes at motion control cycle of 4 ms (typical value) | 11 |
| Controller: PID_Compact | Yes; Universal PID controller with integrated optimization |
| Controller: PID_3Step | Yes; PID controller with integrated optimization for valves |
| Controller: PID-Temp | Yes; PID controller with integrated optimization for temperature |
| Counting and measuring: High-speed counter | Yes |
| Counter: Number of counters | 6; Of which max. 4x A/B/N |
|---|---|
| Counter: Counting frequency, max. | 400 kHz; with quadruple evaluation |
| Counting functions: Continuous counting | Yes |
| Counting functions: Counter response parameterizable | Yes |
| Counting functions: Hardware gate via digital input | Yes |
| Counting functions: Software gate | Yes |
| Counting functions: Event-controlled stop | Yes |
| Counting functions: Synchronization via digital input | Yes |
| Counting functions: Counting range, parameterizable Comparator | Yes |
| Counting functions: Number of comparators | 2; per count channel; see manual for details |
| Counting functions: Direction dependency | Yes |
| Counting functions: Can be changed from user program | Yes |
| Position detection: Incremental acquisition | Yes |
| Position detection: Suitable for S7-1500 Motion Control | Yes |
| Measuring functions: Measuring time, parameterizable | Yes |
| Measuring functions: Dynamic measurement period adjustment | Yes |
| Measuring functions: Number of thresholds, parameterizable Measuring range | 2 |
| Measuring functions: Frequency measurement, min. | 0.04 Hz |
| Measuring functions: Frequency measurement, max. | 400 kHz; with quadruple evaluation |
| Measuring functions: Cycle duration measurement, min. | 2.5 µs |
| Measuring functions: Cycle duration measurement, max. Accuracy | 25 s |
| Measuring functions: Frequency measurement | 100 ppm; depending on measuring interval and signal evaluation |
| Measuring functions: Cycle duration measurement | 100 ppm; depending on measuring interval and signal evaluation |
| Measuring functions: Velocity measurement | 100 ppm; depending on measuring interval and signal evaluation |
| Potential separation digital inputs: between the channels | No |
|---|---|
| Potential separation digital inputs: between the channels, in groups of | 16 |
| Potential separation digital outputs: between the channels | No |
| Potential separation digital outputs: between the channels, in groups of | 16 |
| Potential separation channels: between the channels and backplane bus | Yes |
| Potential separation channels: Between the channels and load voltage L+ | No |
| Recycler Guide available | Yes |
|---|---|
| Ecological footprint: environmental product declaration Global warming potential | Yes |
| Ecological footprint: global warming potential, (total) [CO2 eq] | 130 kg |
| Ecological footprint: global warming potential, (during production) [CO2 eq] | 46.7 kg |
| Ecological footprint: global warming potential, (during operation) [CO2 eq] | 86.9 kg |
| Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] | -4.29 kg |
| PROFINET Security Class | 1 |
|---|---|
| signed firmware update | Yes |
| Secure Boot | Yes |
| securely removing data | Yes |
| Ambient temperature during operation: horizontal installation, min. | -30 °C; No condensation |
|---|---|
| Ambient temperature during operation: vertical installation, min. | -30 °C; No condensation |
| Ambient temperature during storage/transportation: min. | -40 °C |
| Ambient temperature during storage/transportation: max. | 70 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Programming Programming language: LAD | Yes |
|---|---|
| Programming Programming language: FBD | Yes |
| Programming Programming language: STL | Yes |
| Programming Programming language: SCL | Yes |
| Programming Programming language: GRAPH | Yes |
| Know-how protection: User program protection/password protection | Yes |
| Know-how protection: Copy protection | Yes |
| Know-how protection: Block protection | Yes |
| Access protection: protection of confidential configuration data | Yes |
| Access protection: Password for display | Yes |
| Access protection: Protection level: Write protection | Yes |
| Access protection: Protection level: Read/write protection | Yes |
| Access protection: Protection level: Write protection for Failsafe | No |
| Access protection: Protection level: Complete protection | Yes |
| Access protection: User administration | Yes; device-wide and centralized |
| Access protection: Number of users | 100 |
| Access protection: Number of groups | 100 |
| Access protection: Number of roles | 50 |
| Cycle time monitoring: lower limit | adjustable minimum cycle time |
| Cycle time monitoring: upper limit | adjustable maximum cycle time |
| Width | 85 mm |
|---|---|
| Height | 147 mm |
| Depth | 129 mm |
| Weight, approx. | 943 g; with front connector |
|---|
| Net weight | 1.229 kg |
|---|---|
| Country of origin | CN |
| Shipping weight | 1.729 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | Low stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of CPU 1511C-1 PN is 0.5 A.
The rated operational voltage of CPU 1511C-1 PN is 24 V AC.
The tariff (HS) code on file for CPU 1511C-1 PN is 85371091.
The EAN (GTIN) of CPU 1511C-1 PN is 4047623412977.
CPU 1511C-1 PN ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
Compare the 5 main PLC types, IEC 61131-3 languages, scan-time sizing, and brand options to choose the right controller for your plant. Shop at...
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.