Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Once production ends, supply depends on remaining stock.
No replacement announced yet. Tell us the application and we will propose an alternative.
The Siemens 6ES7455-1VS00-0AE0 is a SIMATIC S7-400 FM 455S control module combining 16 analog inputs (8 or 16 channels, for thermocouple, Pt100, or 2-wire transducer) with 16 digital inputs and 32 digital outputs on one module. It runs up to 16 closed-loop controllers onboard for step-and-pulse control, handling loop calculations without loading the CPU cycle time.
The FM 455S puts 16 closed-loop control channels and mixed analog/digital I/O on a single module, so PID-type loop math for step-and-pulse actuators runs on the module instead of the S7-400 CPU cycle. That matters when a rack already carries several FMs or CPs and CPU load is a constraint. Choose the Pt100 / 4-wire configuration (8 channels) for resistance-thermometer loops needing higher accuracy, or the thermocouple / 2-wire configuration (16 channels) when channel count matters more than per-channel precision.
Fits temperature or pressure closed-loop control in process and utility cabinets built around an S7-400 rack, where 16 DI and 32 DO on the same module also handle interlocks and actuator feedback without a separate digital I/O card.
| Load voltage L+: Rated value (DC) | 24 V |
|---|---|
| Load voltage L+: permissible range, lower limit (DC) | 20.4 V |
| Load voltage L+: permissible range, upper limit (DC) | 28.8 V |
| from load voltage L+ (without load), max. | 400 mA; typ. 330 mA |
|---|
| Power loss, typ. | 10.7 W |
|---|---|
| Power loss, max. | 16.2 W |
| Part number | 6ES7455-1VS00-0AE0 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Phase-out announced by the manufacturer |
| EAN | 4025515129608 |
| Number of digital inputs | 16 |
|---|---|
| Input characteristic curve in accordance with IEC 61131, type 2 | Yes |
| Input voltage: Rated value (DC) | 24 V |
| Input voltage: for signal "0" | -3 to +5V |
| Input voltage: for signal "1" | 13 to 30V |
| Input current: for signal "1", typ. | 7 mA |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Number of digital outputs | 32 |
|---|---|
| Short-circuit protection | Yes; Electronic |
| Limitation of inductive shutdown voltage to | L+ (-1.5 V) |
| Controlling a digital input | Yes |
| Switching capacity of the outputs: on lamp load, max. | 5 W |
| Load resistance range: lower limit | 240 Ω |
| Load resistance range: upper limit | 4 kΩ |
| Output voltage: for signal "1", min. | L+ (-2.5 V) |
| Output current: for signal "1" rated value | 0.1 A |
| Output current: for signal "1" permissible range for 0 to 60 °C, min. | 5 mA |
| Output current: for signal "0" residual current, max. | 0.5 mA |
| Parallel switching of two outputs: for logic links | Yes |
| Switching frequency: with resistive load, max. | 100 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz |
| Switching frequency: on lamp load, max. | 100 Hz |
| Cable length: shielded, max. | 1 000 m |
| Cable length: unshielded, max. | 600 m |
| Number of analog inputs | 16; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection |
|---|---|
| permissible input voltage for voltage input (destruction limit), max. | 20 V |
| permissible input current for current input (destruction limit), max. | 40 mA |
| Input ranges: Voltage | Yes |
| Input ranges: Current | Yes |
| Input ranges: Thermocouple | Yes |
| Input ranges: Resistance thermometer | Yes |
| Input ranges (rated values), voltages: 0 to +10 V | Yes |
| Input ranges (rated values), voltages: Input resistance (0 to 10 V) | 100 kΩ |
| Input ranges (rated values), voltages: -1.75 V to +11.75 V | Yes |
| Input ranges (rated values), voltages: Input resistance (-1.75 V to +11.75 V) | 100 kΩ |
| Input ranges (rated values), voltages: -80 mV to +80 mV | Yes |
| Input ranges (rated values), voltages: Input resistance (-80 mV to +80 mV) | 10 MΩ |
| Input ranges (rated values), currents: 0 to 20 mA | Yes |
| Input ranges (rated values), currents: Input resistance (0 to 20 mA) | 50 Ω |
| Input ranges (rated values), currents: 0 to 23.5 mA | Yes |
| Input ranges (rated values), currents: Input resistance (0 to 23.5 mA) | 50 Ω |
| Input ranges (rated values), currents: -3.5 mA to +23.5 mA | Yes |
| Input ranges (rated values), currents: Input resistance (-3.5 mA to +23.5 mA) | 50 Ω |
| Input ranges (rated values), currents: 4 mA to 20 mA | Yes |
| Input ranges (rated values), currents: Input resistance (4 mA to 20 mA) | 50 Ω |
| Input ranges (rated values), thermocouples: Type B | Yes |
| Input ranges (rated values), thermocouples: Input resistance (Type B) | 10 MΩ |
| Input ranges (rated values), thermocouples: Type J | Yes |
| Input ranges (rated values), thermocouples: Type K | Yes |
| Input ranges (rated values), thermocouples: Type R | Yes |
| Input ranges (rated values), thermocouples: Type S | Yes |
| Input ranges (rated values), resistance thermometer: Pt 100 | Yes |
| Input ranges (rated values), resistance thermometer: Input resistance (Pt 100) | 10 MΩ |
| Thermocouple (TC) Temperature compensation: internal temperature compensation | Yes; Parameterizable |
| Thermocouple (TC) Temperature compensation: external temperature compensation with Pt100 | Yes; Parameterizable |
| Characteristic linearization: Parameterizable | Yes |
| Characteristic linearization: for thermocouples | Type B, J, K, R, S |
| Characteristic linearization: for resistance thermometer | Pt100 (standard) |
| Cable length: shielded, max. | 200 m; 50 m at 80 mV and thermocouples |
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 14 bit; 12 bit or 14 bit, parameterizable |
|---|---|
| Integration and conversion time/resolution per channel: Conversion time (per channel) | 16.67 ms; for 12 bit: 16 2/3 ms for 60 Hz, 20 ms for 50 Hz; for 14 bit: 100 ms for 50 Hz and 60 Hz |
| Connection of signal encoders: for voltage measurement | Yes |
|---|---|
| Connection of signal encoders: for current measurement as 4-wire transducer | Yes |
| Connectable encoders: 2-wire sensor | Yes |
| Connectable encoders: permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Operational error limit in overall temperature range: Voltage, relative to input range, (+/-) | ±0.6 to ±1% |
|---|---|
| Operational error limit in overall temperature range: Current, relative to input range, (+/-) | ±0.6 to ±1% |
| Operational error limit in overall temperature range: Resistance thermometer, relative to input range, (+/-) | ±0.6 to ±1% |
| Basic error limit (operational limit at 25 °C): Voltage, relative to input range, (+/-) | ±0.4 to ±0.6 % |
| Basic error limit (operational limit at 25 °C): Current, relative to input range, (+/-) | ±0.4 to ±0.6 % |
| Basic error limit (operational limit at 25 °C): Resistance thermometer, relative to input range, (+/-) | ±0.4 to ±0.6 % |
| Substitute values connectable | Yes; Parameterizable |
|---|
| Control technology: Number of closed-loop controllers | 16; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection |
|---|
| Potential separation controller: between the channels | No |
|---|---|
| Potential separation controller: between the channels and backplane bus | Yes; Optocoupler |
| Isolation tested with | 500 V DC |
|---|
| required front connector | 2x 48-pin |
|---|
| Width | 50 mm |
|---|---|
| Height | 290 mm |
| Depth | 210 mm |
| Weight, approx. | 1 400 g |
|---|
| Net weight | 1.561 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 2.061 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 6ES7455-1VS00-0AE0 is 0.1 A.
The rated operational voltage of 6ES7455-1VS00-0AE0 is 24 V AC.
The tariff (HS) code on file for 6ES7455-1VS00-0AE0 is 85389091.
The EAN (GTIN) of 6ES7455-1VS00-0AE0 is 4025515129608.
6ES7455-1VS00-0AE0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.