- Description
The Siemens 6ES7455-1VS00-0AE0 is a SIMATIC S7-400 FM 455S control module combining 16 analog inputs (8 or 16 channels, for thermocouple, Pt100, or 2-wire transducer) with 16 digital inputs and 32 digital outputs on one module. It runs up to 16 closed-loop controllers onboard for step-and-pulse control, handling loop calculations without loading the CPU cycle time.
Technical Specifications
| Catalog No | 6ES7455-1VS00-0AE0 |
| SKU | 6ES7455-1VS00-0AE0 |
| Brand | Siemens |
| Series | SIMATIC S7-400 |
| Product designation | FM 455S control module |
| Digital inputs | 16, IEC 61131 Type 2, 24 V DC (signal 0: -3 to +5V, signal 1: 13 to 30V), 7 mA typ. |
| Digital outputs | 32, electronic short-circuit protection, 0.1 A rated, 5-150 mA range at 0-60C, 5 W max lamp load |
| Output voltage / load resistance | L+ (-2.5V) min at signal 1; load resistance range 240 ohm to 4 kohm |
| Switching frequency | 100 Hz resistive/lamp load, 0.5 Hz inductive load |
| Digital I/O cable length | 1000 m shielded / 600 m unshielded, max |
| Load voltage L+ | 24 V DC rated, 20.4-28.8 V DC range, 400 mA max input current, 330 mA typ. |
| Power loss | 10.7 W typ. / 16.2 W max |
| Analog inputs | 16 channels (thermocouple / 2-wire) or 8 channels (Pt100 / 4-wire) |
| Analog input ranges | Voltage (0-10V, -1.75 to +11.75V, -80 to +80mV), current (0-20mA, 0-23.5mA, -3.5 to +23.5mA, 4-20mA), thermocouple types B, J, K, R, S, and Pt100 |
| Analog input destruction limit | 20 V max voltage input, 40 mA max current input |
| Resolution | 12 bit or 14 bit, parameterizable, with overrange |
| Conversion time per channel | 16.67 ms at 12 bit (50/60 Hz); 100 ms at 14 bit |
| Temperature compensation | Internal, and external via Pt100, both parameterizable |
| Characteristic linearization | Parameterizable for thermocouple types B, J, K, R, S and Pt100 |
| Connectable encoders | 2-wire sensor, 1.5 mA max quiescent current |
| Closed-loop controllers | 16 (thermocouple / 2-wire) or 8 (Pt100 / 4-wire) channels |
| Operational error limit | +/-0.6 to +/-1% of input range (voltage, current, Pt100) |
| Basic error limit at 25C | +/-0.4 to +/-0.6% of input range (voltage, current, Pt100) |
| Channel-to-backplane isolation | Optocoupler, tested at 500 V DC |
| Analog cable length | 200 m shielded max, 50 m at 80mV range or thermocouples |
| Front connector | 2x 48-pin, required |
| Dimensions (W x H x D) | 50 x 290 x 210 mm |
| Weight | 1.4 kg |
Selection Notes
The FM 455S puts 16 closed-loop control channels and mixed analog/digital I/O on a single module, so PID-type loop math for step-and-pulse actuators runs on the module instead of the S7-400 CPU cycle. That matters when a rack already carries several FMs or CPs and CPU load is a constraint. Choose the Pt100 / 4-wire configuration (8 channels) for resistance-thermometer loops needing higher accuracy, or the thermocouple / 2-wire configuration (16 channels) when channel count matters more than per-channel precision.
Applications
Fits temperature or pressure closed-loop control in process and utility cabinets built around an S7-400 rack, where 16 DI and 32 DO on the same module also handle interlocks and actuator feedback without a separate digital I/O card.