SIMATIC S7-400

Siemens 6ES7455-1VS00-0AE0 SIMATIC S7-400 FM 455S 16-Channel Analog/Digital PLC I/O Module

SIMATIC S7-400 FM 455S: 16 analog inputs, 16 DI, 32 DO, 16 onboard closed-loop controllers.

Rated current
0.1 A
Rated operational voltage
24 V AC
EAN
4025515129608
Description

About the 6ES7455-1VS00-0AE0

The Siemens 6ES7455-1VS00-0AE0 is a SIMATIC S7-400 FM 455S control module combining 16 analog inputs (8 or 16 channels, for thermocouple, Pt100, or 2-wire transducer) with 16 digital inputs and 32 digital outputs on one module. It runs up to 16 closed-loop controllers onboard for step-and-pulse control, handling loop calculations without loading the CPU cycle time.

Selection Notes

The FM 455S puts 16 closed-loop control channels and mixed analog/digital I/O on a single module, so PID-type loop math for step-and-pulse actuators runs on the module instead of the S7-400 CPU cycle. That matters when a rack already carries several FMs or CPs and CPU load is a constraint. Choose the Pt100 / 4-wire configuration (8 channels) for resistance-thermometer loops needing higher accuracy, or the thermocouple / 2-wire configuration (16 channels) when channel count matters more than per-channel precision.

Applications

Fits temperature or pressure closed-loop control in process and utility cabinets built around an S7-400 rack, where 16 DI and 32 DO on the same module also handle interlocks and actuator feedback without a separate digital I/O card.

Specification

Full specification

101 values · Last verified 01 Nov 2026

Supply voltage 3

Load voltage L+: Rated value (DC) 24 V
Load voltage L+: permissible range, lower limit (DC) 20.4 V
Load voltage L+: permissible range, upper limit (DC) 28.8 V

Input current 1

from load voltage L+ (without load), max. 400 mA; typ. 330 mA

Power loss 2

Power loss, typ. 10.7 W
Power loss, max. 16.2 W
Show all 101 specifications ↓ Show less ↑95 more values in Identification, Digital inputs, Digital outputs, Analog inputs, Analog value generation for the inputs, Encoder, Errors/accuracies, Interrupts/diagnostics/status information, Integrated Functions, Potential separation, Isolation, Connection method, Dimensions, Weights, Logistics.

Identification 7

Part number 6ES7455-1VS00-0AE0
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Phase-out announced by the manufacturer
EAN 4025515129608

Digital inputs 8

Number of digital inputs 16
Input characteristic curve in accordance with IEC 61131, type 2 Yes
Input voltage: Rated value (DC) 24 V
Input voltage: for signal "0" -3 to +5V
Input voltage: for signal "1" 13 to 30V
Input current: for signal "1", typ. 7 mA
Cable length: shielded, max. 1 000 m
Cable length: unshielded, max. 600 m

Digital outputs 17

Number of digital outputs 32
Short-circuit protection Yes; Electronic
Limitation of inductive shutdown voltage to L+ (-1.5 V)
Controlling a digital input Yes
Switching capacity of the outputs: on lamp load, max. 5 W
Load resistance range: lower limit 240 Ω
Load resistance range: upper limit 4 kΩ
Output voltage: for signal "1", min. L+ (-2.5 V)
Output current: for signal "1" rated value 0.1 A
Output current: for signal "1" permissible range for 0 to 60 °C, min. 5 mA
Output current: for signal "0" residual current, max. 0.5 mA
Parallel switching of two outputs: for logic links Yes
Switching frequency: with resistive load, max. 100 Hz
Switching frequency: with inductive load, max. 0.5 Hz
Switching frequency: on lamp load, max. 100 Hz
Cable length: shielded, max. 1 000 m
Cable length: unshielded, max. 600 m

Analog inputs 35

Number of analog inputs 16; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection
permissible input voltage for voltage input (destruction limit), max. 20 V
permissible input current for current input (destruction limit), max. 40 mA
Input ranges: Voltage Yes
Input ranges: Current Yes
Input ranges: Thermocouple Yes
Input ranges: Resistance thermometer Yes
Input ranges (rated values), voltages: 0 to +10 V Yes
Input ranges (rated values), voltages: Input resistance (0 to 10 V) 100 kΩ
Input ranges (rated values), voltages: -1.75 V to +11.75 V Yes
Input ranges (rated values), voltages: Input resistance (-1.75 V to +11.75 V) 100 kΩ
Input ranges (rated values), voltages: -80 mV to +80 mV Yes
Input ranges (rated values), voltages: Input resistance (-80 mV to +80 mV) 10 MΩ
Input ranges (rated values), currents: 0 to 20 mA Yes
Input ranges (rated values), currents: Input resistance (0 to 20 mA) 50 Ω
Input ranges (rated values), currents: 0 to 23.5 mA Yes
Input ranges (rated values), currents: Input resistance (0 to 23.5 mA) 50 Ω
Input ranges (rated values), currents: -3.5 mA to +23.5 mA Yes
Input ranges (rated values), currents: Input resistance (-3.5 mA to +23.5 mA) 50 Ω
Input ranges (rated values), currents: 4 mA to 20 mA Yes
Input ranges (rated values), currents: Input resistance (4 mA to 20 mA) 50 Ω
Input ranges (rated values), thermocouples: Type B Yes
Input ranges (rated values), thermocouples: Input resistance (Type B) 10 MΩ
Input ranges (rated values), thermocouples: Type J Yes
Input ranges (rated values), thermocouples: Type K Yes
Input ranges (rated values), thermocouples: Type R Yes
Input ranges (rated values), thermocouples: Type S Yes
Input ranges (rated values), resistance thermometer: Pt 100 Yes
Input ranges (rated values), resistance thermometer: Input resistance (Pt 100) 10 MΩ
Thermocouple (TC) Temperature compensation: internal temperature compensation Yes; Parameterizable
Thermocouple (TC) Temperature compensation: external temperature compensation with Pt100 Yes; Parameterizable
Characteristic linearization: Parameterizable Yes
Characteristic linearization: for thermocouples Type B, J, K, R, S
Characteristic linearization: for resistance thermometer Pt100 (standard)
Cable length: shielded, max. 200 m; 50 m at 80 mV and thermocouples

Analog value generation for the inputs 2

Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. 14 bit; 12 bit or 14 bit, parameterizable
Integration and conversion time/resolution per channel: Conversion time (per channel) 16.67 ms; for 12 bit: 16 2/3 ms for 60 Hz, 20 ms for 50 Hz; for 14 bit: 100 ms for 50 Hz and 60 Hz

Encoder 4

Connection of signal encoders: for voltage measurement Yes
Connection of signal encoders: for current measurement as 4-wire transducer Yes
Connectable encoders: 2-wire sensor Yes
Connectable encoders: permissible quiescent current (2-wire sensor), max. 1.5 mA

Errors/accuracies 6

Operational error limit in overall temperature range: Voltage, relative to input range, (+/-) ±0.6 to ±1%
Operational error limit in overall temperature range: Current, relative to input range, (+/-) ±0.6 to ±1%
Operational error limit in overall temperature range: Resistance thermometer, relative to input range, (+/-) ±0.6 to ±1%
Basic error limit (operational limit at 25 °C): Voltage, relative to input range, (+/-) ±0.4 to ±0.6 %
Basic error limit (operational limit at 25 °C): Current, relative to input range, (+/-) ±0.4 to ±0.6 %
Basic error limit (operational limit at 25 °C): Resistance thermometer, relative to input range, (+/-) ±0.4 to ±0.6 %

Interrupts/diagnostics/status information 1

Substitute values connectable Yes; Parameterizable

Integrated Functions 1

Control technology: Number of closed-loop controllers 16; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection

Potential separation 2

Potential separation controller: between the channels No
Potential separation controller: between the channels and backplane bus Yes; Optocoupler

Isolation 1

Isolation tested with 500 V DC

Connection method 1

required front connector 2x 48-pin

Dimensions 3

Width 50 mm
Height 290 mm
Depth 210 mm

Weights 1

Weight, approx. 1 400 g

Logistics 6

Net weight 1.561 kg
Country of origin DE
Shipping weight 2.061 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6ES7455-1VS00-0AE0

No documents are on file for this part yet.

Ask us for the datasheet
Quick answers

Questions about the 6ES7455-1VS00-0AE0

What is the rated current of 6ES7455-1VS00-0AE0?

The rated current of 6ES7455-1VS00-0AE0 is 0.1 A.

Which supply voltage is 6ES7455-1VS00-0AE0 rated for?

The rated operational voltage of 6ES7455-1VS00-0AE0 is 24 V AC.

What is the HS code of 6ES7455-1VS00-0AE0 for customs?

The tariff (HS) code on file for 6ES7455-1VS00-0AE0 is 85389091.

What is the EAN of 6ES7455-1VS00-0AE0?

The EAN (GTIN) of 6ES7455-1VS00-0AE0 is 4025515129608.

Where does 6ES7455-1VS00-0AE0 ship from, and how fast?

6ES7455-1VS00-0AE0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for PLC & controllers

All guides for PLC & controllers
Reviews

Customer reviews

Series

Siemens SIMATIC S7-400

Brand
Siemens
Series
SIMATIC S7-400
$3,783.96 On request
Get a Quote
Quote

Get a Quote

Genuine parts

Genuine, factory-sealed parts

Siemens · 6ES7455-1VS00-0AE0

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart

View cart