The Siemens 6ES7431-7KF00-0AB0 is a SIMATIC S7-400 SM 431 analog input module with 8 isolated channels for voltage, current, and thermocouple measurement at up to 16-bit resolution. It supports ten thermocouple types with internal or external cold-junction compensation, and it reports diagnostic and limit-value alarms plus a hardware interrupt back to the CPU whenever a reading leaves its parameterized range.
Pick this SM 431 variant over the resistance-input sibling in the same family when the loop needs thermocouple inputs or 16-bit resolution, since this module trades resistance-input ranges for ten thermocouple types and a finer 16-bit conversion. The parameterizable diagnostic alarm and hardware interrupt let a broken sensor wire or an out-of-range reading trigger a CPU interrupt instead of waiting for a cyclic scan, which matters for temperature loops where a stuck reading can mask a real fault.
The mixed voltage, current, and thermocouple ranges on 8 isolated channels suit furnace, oven, and process-temperature monitoring on an S7-400 backplane, where several sensor types share one rack slot. The 10/16.7/20/100 ms conversion time is parameterizable per channel to trade speed for interference-frequency suppression at 50 Hz or 60 Hz.
| from backplane bus 5 V DC, max. | 1 200 mA |
|---|
| Power loss, typ. | 4.6 W |
|---|
| Number of analog inputs | 8 |
|---|---|
| For voltage/current measurement | 8 |
| permissible input voltage for voltage input (destruction limit), max. | 35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) |
| permissible input current for current input (destruction limit), max. | 32 mA |
| Input ranges: Voltage | Yes |
| Input ranges: Current | Yes |
| Input ranges: Thermocouple | Yes |
| Input ranges: Resistance thermometer | No |
| Input ranges: Resistance | No |
| Input ranges (rated values), voltages: 1 V to 5 V | Yes |
| Input ranges (rated values), voltages: Input resistance (1 V to 5 V) | > 2 000 ohms |
| Input ranges (rated values), voltages: -1 V to +1 V | Yes |
| Input ranges (rated values), voltages: -10 V to +10 V | Yes |
| Input ranges (rated values), voltages: -100 mV to +100 mV | Yes |
| Input ranges (rated values), voltages: -2.5 V to +2.5 V | Yes |
| Input ranges (rated values), voltages: -20 mV to +20 mV | Yes |
| Input ranges (rated values), voltages: -250 mV to +250 mV | Yes |
| Input ranges (rated values), voltages: -5 V to +5 V | Yes |
| Input ranges (rated values), voltages: -50 mV to +50 mV | Yes |
| Input ranges (rated values), voltages: -500 mV to +500 mV | Yes |
| Input ranges (rated values), voltages: -80 mV to +80 mV | Yes |
| Input ranges (rated values), currents: 0 to 20 mA | Yes |
| Input ranges (rated values), currents: -10 mA to +10 mA | Yes |
| Input ranges (rated values), currents: -20 mA to +20 mA | Yes |
| Input ranges (rated values), currents: -3.2 mA to +3.2 mA | Yes |
| Input ranges (rated values), currents: 4 mA to 20 mA | Yes |
| Input ranges (rated values), currents: Input resistance (4 mA to 20 mA) | 50 Ω |
| Input ranges (rated values), currents: -5 mA to +5 mA | Yes |
| Input ranges (rated values), thermocouples: Type B | Yes |
| Input ranges (rated values), thermocouples: Input resistance (Type B) | > 2 000 ohms |
| Input ranges (rated values), thermocouples: Type E | Yes |
| Input ranges (rated values), thermocouples: Type J | Yes |
| Input ranges (rated values), thermocouples: Type K | Yes |
| Input ranges (rated values), thermocouples: Type L | Yes |
| Input ranges (rated values), thermocouples: Type N | Yes |
| Input ranges (rated values), thermocouples: Type R | Yes |
| Input ranges (rated values), thermocouples: Type S | Yes |
| Input ranges (rated values), thermocouples: Type T | Yes |
| Input ranges (rated values), thermocouples: Type U | Yes |
| Thermocouple (TC) Temperature compensation: connection for compensating the cold junction | 6ES7431-7KF00-6AA0 |
| Thermocouple (TC) Temperature compensation: Parameterizable | Yes |
| Thermocouple (TC) Temperature compensation: internal temperature compensation | Yes |
| Thermocouple (TC) Temperature compensation: external temperature compensation with compensations socket | Yes |
| Thermocouple (TC) Temperature compensation: dynamic reference temperature value | Yes |
| Characteristic linearization: Parameterizable | Yes |
| Characteristic linearization: for thermocouples | Type B, E, J, K, L, N, R, S, T, U |
| Cable length: shielded, max. | 200 m |
| Part number | 6ES7431-7KF00-0AB0 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Phase-out announced by the manufacturer |
| EAN | 4019169026857 |
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 16 bit |
|---|---|
| Integration and conversion time/resolution per channel: Integration time, parameterizable | Yes |
| Integration and conversion time/resolution per channel: Basic conversion time (ms) | 10 / 16,7 / 20 / 100 |
| Integration and conversion time/resolution per channel: Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 Hz |
| Connection of signal encoders: for voltage measurement | Yes; possible |
|---|---|
| Connection of signal encoders: for current measurement as 4-wire transducer | Yes |
| Connection of signal encoders: for resistance measurement with four-wire connection | Yes |
| Operational error limit in overall temperature range: Voltage, relative to input range, (+/-) | 0.3 % |
|---|---|
| Operational error limit in overall temperature range: Current, relative to input range, (+/-) | 0.5 % |
| Basic error limit (operational limit at 25 °C): Voltage, relative to input range, (+/-) | 0.1 % |
| Basic error limit (operational limit at 25 °C): Current, relative to input range, (+/-) | 0.17 % |
| Diagnostics function | Yes; Parameterizable |
|---|---|
| Alarms: Diagnostic alarm | Yes; Parameterizable |
| Alarms: Limit value alarm | Yes |
| Alarms: Hardware interrupt | Yes; Parameterizable |
| Diagnoses: Diagnostic information readable | Yes; possible |
| Potential separation analog inputs: Potential separation analog inputs | Yes; internal/external |
|---|---|
| Potential separation analog inputs: between the channels | Yes |
| Potential separation analog inputs: between the channels and backplane bus | Yes |
| eClass | 16 27-24-22-01 |
|---|---|
| ETIM | 10 EC001420 |
| IDEA | 4 3562 |
| UNSPSC | 15 32-15-17-05 |
| China RoHS Miscellaneous Manufacturer Declara- | tion |
|---|
| Net weight | 1.006 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 1.506 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for 6ES7431-7KF00-0AB0 is 85389091.
The EAN (GTIN) of 6ES7431-7KF00-0AB0 is 4019169026857.
6ES7431-7KF00-0AB0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.