- Home
- All Products
- Siemens 6ES7422-7BL00-0AB0 SIMATIC S7-400 SM 422 32DO 24V DC 0.5A Diagnostics I/O Module Siemens 6ES7422-7BL00-0AB0 SIMATIC S7-400 SM 422 32DO 24V DC 0.5A Diagnostics I/O Module
Siemens 6ES7422-7BL00-0AB0 SIMATIC S7-400 SM 422 32DO 24V DC 0.5A Diagnostics I/O Module
Get Quote
- Description
The Siemens 6ES7422-7BL00-0AB0 SIMATIC S7-400 SM 422 module delivers 32 isolated 24 V DC digital outputs at 0.5 A each with parameterizable diagnostics: diagnostic alarm, hardware interrupt, wire-break detection below 0.15 mA, and short-circuit detection above roughly 1 A typical. Channels are isolated in groups of 8. Two outputs can be paralleled for uprating or redundant load control within the same group.
Technical Specifications
| Load voltage L+ – Rated value (DC) | 24 V |
| Load voltage L+ – permissible range, lower limit (DC) | 20.4 V |
| Load voltage L+ – permissible range, upper limit (DC) | 28.8 V |
| Input current – from load voltage L+ (without load), max. | 120 mA |
| Input current – from backplane bus 5 V DC, max. | 200 mA |
| Power loss – Power loss, typ. | 8 W |
| Digital outputs – Number of digital outputs | 32 |
| Digital outputs – Short-circuit protection | Yes; Clocked electronically |
| Digital outputs – Response threshold, typ. | 0.75 to 1.5 A |
| Digital outputs – Limitation of inductive shutdown voltage to | L+ (-45 V) |
| Digital outputs – Controlling a digital input | Yes; possible |
| Switching capacity of the outputs – on lamp load, max. | 5 W |
| Load resistance range – lower limit | 48 Ω |
| Load resistance range – upper limit | 4 kΩ |
| Output voltage – for signal 1, min. | L+ (-0.8 V) |
| Output current – for signal 1 rated value | 0.5 A |
| Output current – for signal 1 permissible range, min. | 5 mA |
| Output current – for signal 1 permissible range, max. | 600 A |
| Output current – for signal 0 residual current, max. | 0.5 mA |
| Parallel switching of two outputs – for uprating | Yes; possible (only outputs of the same group) |
| Parallel switching of two outputs – for redundant control of a load | Yes; possible (only outputs of the same group) |
| Switching frequency – with resistive load, max. | 100 Hz |
| Switching frequency – with inductive load, max. | 2 Hz |
| Switching frequency – with inductive load (acc. to IEC 60947-5-1, DC13), max. | 2 Hz |
| Switching frequency – on lamp load, max. | 2 Hz |
| all mounting positions – up to 40 °C, max. | 4 A |
| all mounting positions – up to 60 °C, max. | 2 A |
| Cable length – shielded, max. | 1 000 m |
| Cable length – unshielded, max. | 600 m |
| Interrupts/diagnostics/status information – Diagnostics function | Yes; Parameterizable |
| Alarms – Diagnostic alarm | Yes; Parameterizable |
| Alarms – Hardware interrupt | Yes; Parameterizable |
| Diagnoses – Diagnostic information readable | Yes |
| Diagnoses – Wire break | Yes; <0.15 mA |
| Diagnoses > short-circuit: Yes; – 1 A (typ. | 1 A (typ.) |
| Diagnostics indication LED – internal fault INTF (red) | Yes |
| Diagnostics indication LED – external fault EXTF (red) | Yes |
| Diagnostics indication LED – Status indicator digital output (green) | Yes |
| Potential separation digital outputs – between the channels | Yes |
| Potential separation digital outputs – between the channels, in groups of | 8 |
| Potential separation digital outputs – between the channels and backplane bus | Yes |
| Isolation – Isolation tested with | 500 V DC |
| Dimensions – Width | 25 mm |
| Dimensions – Height | 290 mm |
| Dimensions – Depth | 210 mm |
| Weights – Weight, approx. | 600 g |
Selection Notes
This 32-channel, 0.5 A module adds parameterizable diagnostics – diagnostic alarms, a hardware interrupt, wire-break detection below 0.15 mA, and short-circuit detection above roughly 1 A typical – all reported back to the CPU without extra external wiring. Choose it when the application needs to detect an open output wire or a shorted load automatically rather than through periodic manual checks. Parallel switching of two outputs is supported for both uprating current and redundant control within the same group. Channels are isolated in groups of 8, giving better circuit separation across mixed 24 V DC loads.