- Description
The Siemens 6ES7422-1FH00-0AA0 SIMATIC S7-400 SM 422 module switches 16 isolated 120/230 V AC digital outputs at 2 A per channel, suitable for contactor coils and motor starters up to NEMA size 5. Each group of 4 channels carries its own 8 A, 250 V quick-response spare fuse, and response time is up to 100 ms. Isolation is tested at 1500 V AC.
Technical Specifications
| Load voltage L1 – Rated value (AC) | 230 V; 120/230 V AC |
| Load voltage L1 – permissible range, lower limit (AC) | 79 V |
| Load voltage L1 – permissible range, upper limit (AC) | 264 V |
| Load voltage L1 – permissible frequency range, lower limit | 47 Hz |
| Load voltage L1 – permissible frequency range, upper limit | 63 Hz |
| Input current – from load voltage L+ (without load), max. | 1.5 mA |
| Input current – from backplane bus 5 V DC, max. | 400 mA |
| Power loss – Power loss, typ. | 16 W |
| Digital outputs – Number of digital outputs | 16 |
| Digital outputs – Short-circuit protection | Yes; Clocked electronically: Following a short-circuit, reclosing under a full load cannot be ensured. Countermeasures: change the signal at the output or interrupt the load voltage of the module. Briefly disconnect the load from the output. |
| Digital outputs – required current for fuse shutdown, min. | 100 A |
| Digital outputs – Response time, max. | 100 ms |
| Digital outputs – Controlling a digital input | Yes; possible |
| Digital outputs – Size of motor starters according to NEMA, max. | Size 5 according to NEMA |
| Digital outputs – Spare fuses | Fuse 8 A, 250 V, quick response |
| Switching capacity of the outputs – on lamp load, max. | 50 W |
| Output voltage – for signal 1, min. | L1 (-18.1 V) |
| Output voltage – for signal 1 (at max. current), min. | L1 (-1.3 Vrms) |
| Output voltage – for signal 1 (at min. current), min. | L1 (-18.1 Vrms) |
| Output current – for signal 1 rated value | 2 A |
| Output current – for signal 1 permissible range, min. | 10 mA |
| Output current – for signal 1 permissible range, max. | 2 A |
| Output current – for signal 1 permissible surge current, max. | 50 A; per cycle |
| Output current – for signal 0 residual current, max. | 2.6 mA |
| Output delay with resistive load – 0 to 1, max. | 1 ms |
| Output delay with resistive load – 1 to 0, max. | 1 AC cycle |
| Parallel switching of two outputs – for redundant control of a load | Yes; Possible (only outputs with the same load voltage) |
| Switching frequency – with resistive load, max. | 10 Hz |
| Switching frequency – with inductive load, max. | 0.5 Hz |
| Switching frequency – with inductive load (acc. to IEC 60947-5-1, AC15), max. | 0.5 Hz |
| Switching frequency – on lamp load, max. | 1 Hz |
| all mounting positions – up to 40 °C, max. | 4 A; 6 A with fan assembly |
| all mounting positions – up to 60 °C, max. | 2 A; 5 A with fan subassembly; per 4 adjacent outputs |
| Cable length – shielded, max. | 1 000 m |
| Cable length – unshielded, max. | 600 m |
| Interrupts/diagnostics/status information – Diagnostics function | Not parameterizable |
| Diagnostics indication LED – internal fault INTF (red) | Yes; Fuse blown |
| Diagnostics indication LED – external fault EXTF (red) | Yes; Missing load voltage |
| Potential separation digital outputs – between the channels | Yes |
| Potential separation digital outputs – between the channels, in groups of | 4 |
| Potential separation digital outputs – between the channels and backplane bus | Yes |
| Isolation – Isolation tested with | 1 500 V AC |
| Dimensions – Width | 25 mm |
| Dimensions – Height | 290 mm |
| Dimensions – Depth | 210 mm |
| Weights – Weight, approx. | 800 g |
Selection Notes
Switching 120/230 V AC loads directly, this module suits contactor coils, indicator lamps, and small motor starters rated up to NEMA size 5 without an external relay interface. Each group of 4 channels carries its own 8 A, 250 V quick-response spare fuse, so a single overloaded channel does not necessarily take down the whole module. Response time is up to 100 ms per switching operation – factor that into any application needing fast AC switching. Because outputs are isolated in groups of 4 rather than individually, keep AC loads on the same phase and load-voltage class within one group.