How to Select an Interface Relay for PLC Outputs
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
The Siemens PS407 (6ES7407-0RA02-0AA0) is a wide-range SIMATIC S7-400 power supply module that converts 120/230V AC or DC input into a regulated 5V DC backplane rail rated at 20A, plus a 24V DC output at 1A. It occupies two rack slots and includes short-circuit protection, with an optional lithium backup battery for buffered timekeeping during power loss.
At 20A on the 5V DC backplane bus, this PS407 covers denser S7-400 racks: redundant CPUs, several communication processors, or a high signal-module count that would exceed the 10A sibling's headroom. The trade-off is higher typical power draw, 158W input versus 95W, and 35W power loss instead of 20W, so plan panel cooling accordingly. Backplane current stays idling-proof on the 24V DC rail regardless of which 5V variant is fitted, and the same 20 ms NAMUR-compliant buffering time applies to both.
| Rated value (DC): 120 V DC | Yes |
|---|---|
| Rated value (DC): 230 V DC | Yes |
| Rated value (AC): 120 V AC | Yes |
| Rated value (AC): 230 V AC | Yes |
| Line frequency: Rated value 50 Hz | Yes |
| Line frequency: Rated value 60 Hz | Yes |
| Line frequency: permissible range, lower limit | 47 Hz |
| Line frequency: permissible range, upper limit | 63 Hz |
| Mains buffering: Mains/voltage failure stored energy time | 20 ms |
| Mains buffering: Mains buffering according to NAMUR recommendation | Yes |
| Rated value at 120 V DC | 1.4 A |
|---|---|
| Rated value at 230 V DC | 0.7 A |
| Rated value at 120 V AC | 1.4 A |
| Rated value at 230 V AC | 0.7 A |
| Inrush current, max. | 88 A; Full width at half maximum 1.1 ms |
| Leakage current, max. | 5 mA |
| Type of output voltage | DC |
|---|---|
| Rated value (DC): 5 V DC | Yes |
| Rated value (DC): 24 V DC | Yes |
| Part number | 6ES7407-0RA02-0AA0 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4019169144308 |
| ETIM class | EC000599 |
| eCl@ss | 27242209 |
| for backplane bus (5 V DC), max. | 20 A; no base load required |
|---|---|
| for backplane bus (24 V DC), max. | 1 A; idling-proof |
| Short-circuit protection | Yes |
| Active power input, typ. | 158 W |
|---|
| Power loss, typ. | 35 W |
|---|
| Backup battery: Backup battery (optional) | Yes; 1x lithium AA; 3.6 V / 2.2 Ah |
|---|
| Slots: required slots | 2 |
|---|
| primary/secondary | Yes |
|---|
| Overvoltage category | II |
|---|
| Compliance with line harmonic distortion limits: Compliance with line harmonic distortion acc. to IEC 61000-3-2, IEC 61000-3-3 | Yes |
|---|
| Equipment protection class | I, with protective conductor |
|---|
| FM approval | Yes; Ta: 0 °C to 70 °C T4 |
|---|---|
| BIS | Yes |
| Ambient temperature during operation: min. | 0 °C |
|---|---|
| Ambient temperature during operation: max. | 60 °C |
| Design of electrical connection | 3x 1.5 mm2, solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm |
|---|
| Width | 50 mm |
|---|---|
| Height | 290 mm |
| Depth | 217 mm |
| Weight, approx. | 1 300 g |
|---|
| General Product Approval Miscellaneous | For use in hazard- |
|---|---|
| General Product Approval EMV | ous locations |
| Net weight | 1.402 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 1.902 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 6ES7407-0RA02-0AA0 is 20 A.
The rated operational voltage of 6ES7407-0RA02-0AA0 is 120–230 V AC.
The tariff (HS) code on file for 6ES7407-0RA02-0AA0 is 85044095.
The EAN (GTIN) of 6ES7407-0RA02-0AA0 is 4019169144308.
6ES7407-0RA02-0AA0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
Compare the 5 main PLC types, IEC 61131-3 languages, scan-time sizing, and brand options to choose the right controller for your plant. Shop at...
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.