- Description
The Siemens 6ES7407-0DA02-0AA0 SIMATIC S7-400 PS407 power supply is a wide-range unit for 120 or 230 V AC or DC input at 47 to 63 Hz, delivering 5 V DC at 4 A to the backplane bus plus 24 V DC at up to 0.5 A. Typical active power input is 52 W. It occupies one rack slot and weighs 760 g.
Technical Specifications
| SKU | 6ES7407-0DA02-0AA0 |
| Brand | Siemens |
| Series | SIMATIC S7-400 |
| EAN | 4019169141987 |
| Product Type Designation | PS407 |
| Supply Voltage | 120/230 V AC or 120/230 V DC (universal current, wide range) |
| Line Frequency | 50/60 Hz, permissible range 47 to 63 Hz |
| Input Current | 0.42 A at 120 V AC, 0.22 A at 230 V AC (350 mA at 120 V DC, 190 mA at 230 V DC) |
| Inrush Current, max | 8.5 A, 5 ms full width at half maximum |
| Leakage Current, max | 5 mA |
| Output, Backplane Bus (5 V DC) | 4 A, no base load required |
| Output, Backplane Bus (24 V DC) | 0.5 A, idling-proof |
| Short-Circuit Protection | Yes |
| Active Power Input, typ | 52 W |
| Power Loss, typ | 20 W |
| Mains Buffering | 20 ms, per NAMUR recommendation |
| Backup Battery (optional) | 1x lithium AA, 3.6 V / 2.2 Ah |
| Slots Required | 1 |
| Overvoltage Category | II |
| Line Harmonic Distortion Compliance | IEC 61000-3-2, IEC 61000-3-3 |
| Equipment Protection Class | I, with protective conductor |
| Ambient Temperature, Operation | 0 to 60 °C |
| Width | 25 mm |
| Height | 290 mm |
| Depth | 217 mm |
| Weight | 760 g |
Certifications & Standards
- BIS
Selection Notes
The PS407 4 A runs directly from 120/230 V AC or DC mains without a separate 24 V DC source, which makes it the choice when the installation only has AC or DC line power at the rack rather than a regulated DC bus. Its 4 A backplane-bus rating suits a lightly loaded single-segment rack; choose the higher-current wide-range variant when the combined 5 V DC module load exceeds 4 A.
Applications
Its 47 to 63 Hz frequency tolerance and dual 120/230 V AC or DC rating let the same unit run on either voltage without rewiring, useful where a rack ships to sites with different mains standards. Compliance with IEC 61000-3-2 and IEC 61000-3-3 limits its harmonic current draw on the AC supply.