- Home
- All Products
- Siemens 6ES7405-0KR02-0AA0 SIMATIC S7-400 PS405 10A DC Redundant Power Supply Siemens 6ES7405-0KR02-0AA0 SIMATIC S7-400 PS405 10A DC Redundant Power Supply
Siemens 6ES7405-0KR02-0AA0 SIMATIC S7-400 PS405 10A DC Redundant Power Supply
Get Quote
- Description
The Siemens 6ES7405-0KR02-0AA0 SIMATIC S7-400 PS405 power supply accepts 24, 48 or 60 V DC input and delivers 5 V DC at 10 A to the backplane bus plus 24 V DC at up to 1 A, and it is built for redundant use alongside a second unit. Typical active power input is 95 W. It occupies two rack slots and weighs 1.2 kg.
Technical Specifications
| SKU | 6ES7405-0KR02-0AA0 |
| Brand | Siemens |
| Series | SIMATIC S7-400 |
| EAN | 4019169142212 |
| Product Type Designation | PS405 |
| Supply Voltage (DC) | 24 / 48 / 60 V DC |
| Input Current | 4 A at 24 V DC, 2 A at 48 V DC, 1.6 A at 60 V DC |
| Inrush Current, max | 18 A, 20 ms full width at half maximum |
| Output, Backplane Bus (5 V DC) | 10 A, no base load required |
| Output, Backplane Bus (24 V DC) | 1 A, idling-proof |
| Short-Circuit Protection | Yes |
| Active Power Input, typ | 95 W |
| Power Loss, typ | 20 W |
| Mains Buffering | 20 ms, per NAMUR recommendation |
| Backup Battery (optional) | 2x lithium AA, 3.6 V / 2.2 Ah |
| Slots Required | 2 |
| Overvoltage Category | II |
| Equipment Protection Class | I, with protective conductor |
| Ambient Temperature, Operation | 0 to 60 °C |
| Width | 50 mm |
| Height | 290 mm |
| Depth | 217 mm |
| Weight | 1.2 kg |
Certifications & Standards
- CCC
- BIS
Selection Notes
Built for redundant use, the PS405 10 A pairs with a second unit so the rack stays powered if one supply fails; specify two of this model rather than one when redundancy is the goal. Its 10 A backplane-bus rating covers a mid-size module count, above the smallest PS405 in this range and below the highest-current version.
Applications
The two-slot footprint and 1.6 to 4 A input current across the 24/48/60 V DC range fit a DC-bus-fed rack carrying a moderate module count where a supply failure must not interrupt the process. The optional lithium backup battery keeps retentive memory alive through a supply interruption.