Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Once production ends, supply depends on remaining stock.
No replacement announced yet. Tell us the application and we will propose an alternative.
The Siemens 6ES7332-5RD00-0AB0 is a SIMATIC S7-300 SM 332 isolated analog output module with 4 channels for 0/4 to 20 mA signals, rated for use with equipment in hazardous areas through Ex(i) intrinsic safety. It connects through a 20-pin front connector, provides overrange and wire-break diagnostics, and is PTB-tested (Ex-96.D.2026X) for ATEX [EEx ib] IIC and FM Class I Division 2 applications.
The 15-bit resolution and +/-0.2% basic error limit at 25 C support accurate 4-20 mA loop measurement where analog readback quality matters downstream. Because the module carries [EEx ib] IIC Ex(i) approval (Uo 14 V, Io 70 mA, Po 440 mW), it can drive hazardous-area actuators directly from a standard S7-300 rack without external isolation barriers. The two-wire connection option on the current outputs cuts field wiring versus a four-wire loop, and the wire-break and overrange diagnostics flag faulty loops through the SF and F LEDs without extra wiring effort.
| Load voltage L+: Rated value (DC) | 24 V |
|---|---|
| Load voltage L+: Reverse polarity protection | Yes |
| from load voltage L+ (without load), max. | 200 mA |
|---|---|
| from backplane bus 5 V DC, max. | 80 mA |
| Power loss, typ. | 4 W |
|---|
| Part number | 6ES7332-5RD00-0AB0 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Phase-out announced by the manufacturer |
| EAN | 4025515061304 |
| Number of analog outputs | 4 |
|---|---|
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 70 mA |
| Current output, no-load voltage, max. | 14 V |
| Output ranges, current: 0 to 20 mA | Yes |
| Output ranges, current: 4 mA to 20 mA | Yes |
| Connection of actuators: for current output two-wire connection | Yes |
| Load impedance (in rated range of output): with current outputs, max. | 500 Ω |
| Cable length: shielded, max. | 200 m |
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 15 bit |
|---|
| Operational error limit in overall temperature range: Current, relative to output range, (+/-) | 0.55 % |
|---|---|
| Basic error limit (operational limit at 25 °C): Current, relative to output range, (+/-) | 0.2 % |
| Diagnostics function | Yes |
|---|---|
| Diagnoses: Overrange | Yes |
| Diagnoses: Wire-break in actuator cable | Yes |
| Diagnostics indication LED: Group error SF (red) | Yes |
| Diagnostics indication LED: Channel fault indicator F (red) | Yes |
| Module for Ex(i) protection | Yes |
|---|---|
| maximum values for connecting terminals for gas group IIC: Uo (no-load voltage), max. | 14 V |
| maximum values for connecting terminals for gas group IIC: Io (short-circuit current), max. | 70 mA |
| maximum values for connecting terminals for gas group IIC: Po (power output), max. | 440 mW |
| maximum values for connecting terminals for gas group IIC: Co (permissible external capacity), max. | 850 nF |
| maximum values for connecting terminals for gas group IIC: Lo (permissible external inductivity), max. | 6.6 mH |
| Potential separation analog outputs: between the channels | Yes |
|---|---|
| Potential separation analog outputs: between the channels and backplane bus | Yes |
| Use in hazardous areas: ATEX marking | [EEx ib] IIC |
|---|---|
| Use in hazardous areas: FM marking | Class I, Division 2, Group A, B, C, D T4 |
| Use in hazardous areas: Test number PTB | Ex-96.D.2026X |
| Ambient temperature during operation: max. | 60 °C |
|---|
| required front connector | 20-pin |
|---|
| Width | 40 mm |
|---|---|
| Height | 125 mm |
| Depth | 120 mm |
| Weight, approx. | 280 g |
|---|
| Miscellaneous Manufacturer Declara- Metrological Approval | tion |
|---|
| Net weight | 0.411 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.911 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for 6ES7332-5RD00-0AB0 is 85389091.
The EAN (GTIN) of 6ES7332-5RD00-0AB0 is 4025515061304.
6ES7332-5RD00-0AB0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.