The Siemens 6ES7322-5RD00-0AB0 is a SIMATIC S7-300 SM 322 digital output module with 4 isolated outputs rated 15 V / 20 mA, built to drive actuators located in a hazardous area. It draws 160 mA from the 24 V DC load supply, is PTB tested under number Ex-96.D.2102X, and carries an [EEx ib] IIC hazardous-area marking.
Technical Specifications
| Catalog No / SKU | 6ES7322-5RD00-0AB0 |
| Brand | Siemens |
| Series | SIMATIC S7-300 |
| Product type | SM 322 digital output module, isolated, for hazardous-area signals |
| Load voltage L+ | 24 V DC, reverse polarity protected |
| Current consumption from L+ (no load), max. | 160 mA |
| Current consumption from backplane bus (5 V DC), max. | 85 mA |
| Power loss, typ. | 3 W |
| Digital outputs | 4, electronically short-circuit protected |
| Output voltage, rated | 15 V DC |
| Output current, signal 1 (0-60 degC) | 20 mA +/-10% |
| Load resistance range, upper limit | 200 Ohm, two-wire connection |
| Switching frequency, resistive load, max. | 100 Hz |
| Cable length, unshielded, max. | 200 m |
| Ex(i) gas group IIC limits | Uo 15.75 V, Io 85 mA, Po 335 mW, Co 500 nF, Lo 5 mH |
| Potential separation (channels / backplane / L+) | 60 V DC/30 V AC in hazardous area; 400 V DC/250 V AC in non-hazardous area |
| ATEX marking | [EEx ib] IIC |
| FM marking | AIS CL.1, DIV 1, GP A,B,C,D; CL.I, DIV 2, GP A,B,C,D T4 |
| PTB test number | Ex-96.D.2102X |
| Ambient temperature, operation, max. | 60 degC |
| Connection method | 20-pin front connector required |
| Dimensions (W x H x D) | 40 x 125 x 120 mm |
| Net weight | 0.4 kg |
Selection Notes
At 15 V / 20 mA rated output, this module suits intrinsically safe actuators whose loop is specified for that voltage/current pair rather than the 24 V / 10 mA pair used on the other SM 322 output variant — check the actuator's own Ex(i) entity parameters against Uo 15.75 V / Io 85 mA / Po 335 mW before mixing modules on the same project. The 200 Ohm maximum load resistance sets the longest field-wiring loop the output can drive at rated current; a lower-resistance actuator leaves margin, a higher one will not reach rated current. Short-circuit protection is electronic, so a field fault trips without replacing a fuse.