How to Select an Interface Relay for PLC Outputs
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
The Siemens CM 1241 (6ES7241-1EA50-0XB0) is a SIMATIC S7-1200 communication module with one switchable RS232/RS422/RS485 interface, supporting Freeport, ASCII, Modbus RTU master and slave, and USS protocols. It connects the S7-1200 to serial field devices such as VFDs, meters, and third-party PLCs over up to 1,000 m on RS422/485, at transmission rates up to 250 kbit/s on RS485 and 115.2 kbit/s on RS232.
The single switchable RS232/422/485 port lets one module serve either a short point-to-point RS232 link or a 1,000 m multidrop RS422/485 segment, covering both a nearby HMI or printer connection and a longer Modbus RTU field bus without ordering two different modules. Choose the Modbus RTU master function when the S7-1200 needs to poll VFDs or meters directly; the built-in USS driver is the alternative when the field devices are Siemens drives instead of generic Modbus slaves.
Fits S7-1200 stations that need to talk to serial VFDs, energy meters, barcode scanners, or legacy RS232/485 equipment alongside the CPU's onboard PROFINET port.
| Product type designation | CM 1241 RS 232 / 422 / 485 |
|---|
| from backplane bus 5 V DC, typ. | 170 mA |
|---|
| Power loss, typ. | 0.9 W |
|---|
| Part number | 6ES7241-1EA50-0XB0 |
|---|---|
| Type designation | CM 1241 RS 232 / 422 / 485 |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4034106035709 |
| ETIM class | EC001423 |
| eCl@ss | 27242208 |
| Interfaces/bus type | RS 232 (full duplex) / 422 / 485 |
|---|---|
| Number of interfaces | 1 |
| Point-to-point connection: Cable length, max. Integrated protocol driver | 1 000 m; RS 232 10 m shielded max., RS 422/485 1 000 m shielded max. |
| Point-to-point connection: Freeport | Yes |
| Point-to-point connection: ASCII | Yes; Available as library function |
| Point-to-point connection: Modbus RTU master | Yes |
| Point-to-point connection: Modbus RTU device | Yes |
| Point-to-point connection: USS | Yes; Available as library function |
| RS 232: Transmission rate, max. | 115.2 kbit/s |
|---|---|
| RS 485: Transmission rate, max. | 250 kbit/s |
| Integrated protocols Freeport: Telegram length, max. | 4 kbyte |
|---|---|
| Integrated protocols Freeport: Bits per character | 7 or 8 |
| Integrated protocols Freeport: Number of stop bits | 1 (Standard), 2 |
| Integrated protocols Freeport: Parity Modbus RTU master | no parity (standard); even, odd, mark (parity bit always 1); space (parity bit always 0) |
| Integrated protocols Freeport: Address area | 1 through 65535 (Standard Modbus addressing) |
| Integrated protocols Freeport: max. number of devices Modbus RTU device | 247; slave numbers 1 through 247, per MODBUS network segment maximum 32 devices, additional repeaters needed to expand the network to maximum configuration |
| Diagnostics function | Yes |
|---|---|
| Diagnostics indication LED: DIAG LED | Yes |
| Diagnostics indication LED: for status of the outputs | Yes |
| IP degree of protection | IP20 |
|---|
| CE mark | Yes |
|---|---|
| CSA approval | No |
| UL approval | Yes |
| cULus | Yes |
| FM approval | No |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| Marine approval | No |
| Free fall: Fall height, max. | 0.3 m; five times, in product package |
|---|---|
| Ambient temperature during operation: horizontal installation, min. | -20 °C |
| Ambient temperature during operation: vertical installation, min. | -20 °C |
| Ambient temperature during storage/transportation: min. | -40 °C |
| Ambient temperature during storage/transportation: max. | 70 °C |
| Air pressure acc. to IEC 60068-2-13: Operation, min. | 540 hPa |
| Air pressure acc. to IEC 60068-2-13: Operation, max. | 1 140 hPa |
| Air pressure acc. to IEC 60068-2-13: Storage/transport, min. | 540 hPa |
| Air pressure acc. to IEC 60068-2-13: Storage/transport, max. | 1 140 hPa |
| Altitude during operation relating to sea level: Installation altitude, min. | -1 000 m |
| Relative humidity: Operation, max. | 95 %; no condensation |
| Vibrations: Vibration resistance during operation acc. to IEC 60068-2-6 | 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz |
| Vibrations: Operation, tested according to IEC 60068-2-6 | Yes |
| Shock testing: tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
| Pollutant concentrations: SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free |
| Enclosure material (front): Plastic | Yes |
|---|
| Width | 30 mm |
|---|---|
| Height | 125 mm |
| Depth | 100 mm |
| Weight, approx. | 178 g |
|---|
| eClass | 9 27-24-22-08 |
|---|---|
| ETIM | 10 EC001423 |
| IDEA | 4 3564 |
| UNSPSC | 15 32-15-17-05 |
| Net weight | 0.178 kg |
|---|---|
| Package dimensions | 152 × 50 × 110 mm |
| Country of origin | CN |
| Shipping weight | 0.678 kg |
| Ships from | Türkiye |
| Dispatch | 12 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for CM 1241 RS 232 / 422 / 485 is 85176200.
The EAN (GTIN) of CM 1241 RS 232 / 422 / 485 is 4034106035709.
CM 1241 RS 232 / 422 / 485 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
Compare the 5 main PLC types, IEC 61131-3 languages, scan-time sizing, and brand options to choose the right controller for your plant. Shop at...
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.