How to Select an Interface Relay for PLC Outputs
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
The Siemens 6ES7193-6BP00-0DU0 is a SIMATIC ET 200SP BaseUnit, type BU20-P16+A0+2D (BU-TYPE U0), that carries push-in terminals for one I/O module slot and opens a new potential group on the station's P1/P2 bus. Rated current is 10 A per bus and per process terminal, with push-in terminals sized for 0.14-2.5 mm² conductors.
The BU-TYPE U0 designation and new potential group flag mean this BaseUnit breaks the power bus into a fresh isolated section, so it belongs at a point in the ET 200SP station where a downstream I/O module needs a different supply or protection zone than the modules upstream. The push-in terminal set (16 process terminals, no AUX terminals) suits standard I/O modules without their own auxiliary voltage requirement; pick a BaseUnit variant with AUX terminals instead for modules that need a separate load or sensor supply.
Provides the mounting slot, bus connection, and potential-group break for a single ET 200SP I/O module in a modular distributed I/O station.
| Product type designation | BU type U0 |
|---|---|
| HW functional status | FS10 and higher |
| Rated value (DC) | See manual |
|---|---|
| For P1 and P2 bus | 120 V |
| For AUX bus | 120 V; Equal potential group to P1/P2 bus or PE |
| for process terminals | 120 V |
| Rated value (AC) | See manual |
| external protection for power supply lines | Yes |
| Mains filter: Integrated | No |
| up to 60 °C, max. | 10 A |
|---|---|
| For P1 and P2 bus, max. | 10 A |
| For AUX bus, max. | 10 A |
| For process terminals, max. | 10 A; Point of contact, derating depends on the module |
| Part number | 6ES7193-6BP00-0DU0 |
|---|---|
| Type designation | BU type U0 |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623409434 |
| ETIM class | EC001598 |
| eCl@ss | 27242603 |
| Automatic encoding | Yes |
|---|---|
| Formation of potential groups: New potential group | Yes |
| Formation of potential groups: Potential group continued from the left | No |
| Slots: Number of slots | 1 |
| between backplane bus and supply voltage | Yes |
|---|---|
| between process terminals and supply voltage | Yes; Not applicable for process terminals 15 and 16 |
| between power bus and supply voltage | No |
| Isolation tested with | 3 100 V DC |
|---|
| Ecological footprint: environmental product declaration Global warming potential | Yes |
|---|---|
| Ecological footprint: global warming potential, (total) [CO2 eq] | 0.873 kg |
| Ecological footprint: global warming potential, (during production) [CO2 eq] | 0.866 kg |
| Ecological footprint: global warming potential, (during operation) [CO2 eq] | 0 kg |
| Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] | -0.0011 kg |
| Ambient temperature during operation: horizontal installation, min. | -30 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | -30 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 3 000 m |
| Absolute humidity: dew point, min. | -60 °C; suitable for dry room applications |
| Terminals: Terminal type | Push-in terminal |
|---|---|
| Terminals: system-integrated shield connection | Yes; Optional |
| Terminals: Conductor cross-section, min. | 0.14 mm2; 0.2 mm2 without wire end ferrule |
| Terminals: Conductor cross-section, max. | 2.5 mm2; 1.5 mm2 with wire end ferrule |
| Terminals: Number of process terminals to I/O module | 16 |
| Terminals: Number of terminals to AUX bus | 0 |
| Terminals: Number of add-on terminals | 0 |
| Terminals: Number of terminals with connection to P1 and P2 bus | 2 |
| Width | 20 mm |
|---|---|
| Height | 117 mm |
| Depth | 35 mm |
| Weight, approx. | 50 g |
|---|
| Net weight | 0.059 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.559 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of BU type U0 is 10 A.
The rated operational voltage of BU type U0 is 277 V AC.
The tariff (HS) code on file for BU type U0 is 85366990.
The EAN (GTIN) of BU type U0 is 4047623409434.
BU type U0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.