How to Select an Interface Relay for PLC Outputs
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
The Siemens 6ES7193-6BP00-0DA1 is a SIMATIC ET 200SP BaseUnit type A1 (BU15-P16+A0+2D/T) for mounting one I/O module with 16 push-in process terminals, rated 24 V DC and up to 10 A on the P1/P2 potential bus. It starts a new, electrically separated potential group and includes a temperature sensor for local diagnostics.
This BaseUnit starts a fresh, electrically separated potential group rather than continuing the incoming one - use it at a break point where a different zone needs its own 24 V feed and fusing. A bridged-continuation BaseUnit variant in the same A1 slot type continues the existing potential group instead when no new feed is required. Both variants accept the same 16-terminal Type A1 I/O modules, so the choice is purely about potential-group segmentation, not I/O compatibility.
Forming a new 24 V potential and fusing zone within an ET 200SP station, for example separating machine sections for isolated fault protection.
| Product type designation | BU type A1 |
|---|---|
| HW functional status | FS10 and higher |
| Rated value (DC) | 24 V |
|---|---|
| external protection for power supply lines | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic |
| For P1 and P2 bus, max. | 10 A |
|---|---|
| For process terminals, max. | 2 A |
| Part number | 6ES7193-6BP00-0DA1 |
|---|---|
| Type designation | BU type A1 |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515080893 |
| ETIM class | EC001598 |
| eCl@ss | 27242603 |
| Temperature sensor | Yes |
|---|---|
| Formation of potential groups: New potential group | Yes |
| Formation of potential groups: Potential group continued from the left | No |
| Slots: Number of slots | 1; Type A1 |
| between the potential groups | Yes |
|---|
| Isolation tested with | 707 V DC (type test) |
|---|
| Ecological footprint: environmental product declaration Global warming potential | Yes |
|---|---|
| Ecological footprint: global warming potential, (total) [CO2 eq] | 0.873 kg |
| Ecological footprint: global warming potential, (during production) [CO2 eq] | 0.866 kg |
| Ecological footprint: global warming potential, (during operation) [CO2 eq] | 0 kg |
| Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] | -0.0011 kg |
| Ambient temperature during operation: horizontal installation, min. | -30 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | -30 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Absolute humidity: dew point, min. | -60 °C; suitable for dry room applications |
| Color coding labels: for process terminals | CC00 to CC09 |
|---|---|
| Color coding labels: for AUX terminals | does not exist |
| Color coding labels: for add-on terminals | does not exist |
| Terminals: Terminal type | Push-in terminal |
|---|---|
| Terminals: system-integrated shield connection | Yes; Optional |
| Terminals: Conductor cross-section, min. | 0.14 mm2; AWG 26 |
| Terminals: Conductor cross-section, max. | 2.5 mm2; AWG 14 |
| Terminals: Number of process terminals to I/O module | 16 |
| Terminals: Number of terminals to AUX bus | 0 |
| Terminals: Number of add-on terminals | 0 |
| Terminals: Number of terminals with connection to P1 and P2 bus | 2 |
| Width | 15 mm |
|---|---|
| Height | 117 mm |
| Depth | 35 mm |
| Weight, approx. | 40 g |
|---|
| Manufacturer Declara- CCC-Ex | tion |
|---|
| Net weight | 0.048 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.548 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of BU type A1 is 10 A.
The rated operational voltage of BU type A1 is 24 V DC.
The tariff (HS) code on file for BU type A1 is 85369010.
The EAN (GTIN) of BU type A1 is 4025515080893.
BU type A1 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
Compare the 5 main PLC types, IEC 61131-3 languages, scan-time sizing, and brand options to choose the right controller for your plant. Shop at...
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.