Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Once production ends, supply depends on remaining stock.
No replacement announced yet. Tell us the application and we will propose an alternative.
The Siemens 6ES7157-1AA00-0AB0 is the IM 157-1 DP interface module for the SIMATIC ET 200AL distributed I/O line, rated IP65/67 with two M12 B-coded PROFIBUS ports for direct field mounting. It runs from 24 V DC, supports PROFIBUS DP up to 12 Mbit/s, and is rated PL d / Cat. 3 / SIL 2 for safety-related tripping of standard modules.
Two independent load voltage inputs (1L+ and 2L+), each fused to 4 A, let this interface module feed sensor and actuator power separately from the station logic supply, so a short on the field wiring does not take down the head module. Direct data exchange (slave-to-slave communication) lets other ET 200AL stations read this one's inputs without routing through the DP master, useful for local interlocks. Safety-related tripping to PL d / Cat. 3 / SIL 2 (from FS01) means a hardwired safety chain can trip standard I/O modules on this station without a separate F-module, an option worth checking against the specific safety function before design-in.
PROFIBUS DP head module for SIMATIC ET 200AL field-mounted I/O stations in IP65/67 environments outside a control cabinet, including installations that use a hardwired safety trip through standard modules.
| Product type designation | IM 157-1 DP |
|---|---|
| HW functional status | FS02 |
| Firmware version | V1.0.x |
| Vendor identification (VendorID) | 81A9H |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | STEP 7 V13 SP1 or higher |
| Engineering with: STEP 7 configurable/integrated from version | From V5.5 SP4 Hotfix 3 |
| Engineering with: PROFIBUS from GSD version/GSD revision | GSD as of Revision 5 |
| via dataset | Yes |
|---|
| power supply according to NEC Class 2 required | No |
|---|---|
| Load voltage 1L+: Rated value (DC) | 24 V |
| Load voltage 1L+: permissible range, lower limit (DC) | 20.4 V |
| Load voltage 1L+: permissible range, upper limit (DC) | 28.8 V |
| Load voltage 1L+: Reverse polarity protection | Yes; against destruction |
| Part number | 6ES7157-1AA00-0AB0 |
|---|---|
| Type designation | IM 157-1 DP |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Phase-out announced by the manufacturer |
| EAN | 4047623403494 |
| ETIM class | EC001604 |
| eCl@ss | 27242608 |
| Current consumption (rated value) | 50 mA |
|---|---|
| from load voltage 1L+ (unswitched voltage) | 4 A; Maximum value |
| from load voltage 2L+, max. | 4 A; Maximum value |
| Power loss, typ. | 1.7 W |
|---|
| Address space per station: Address space per station, max. | 244 byte |
|---|
| Number of PROFIBUS interfaces | 1 |
|---|
| Interface type | PROFIBUS DP |
|---|---|
| Interface types: RS 485 | Yes |
| Interface types: M12 port | Yes; 2x M12 B-coded |
| Protocols: PROFIBUS DP device | Yes |
| RS 485: Transmission rate, max. | 12 Mbit/s |
|---|
| Supports protocol for PROFINET IO | No |
|---|---|
| PROFIsafe | No |
| PROFIBUS | Yes |
| EtherNet/IP | No |
| PROFIBUS DP Services: SYNC capability | Yes |
| PROFIBUS DP Services: FREEZE capability | Yes |
| PROFIBUS DP Services: Direct data exchange (slave-to-slave communication) | Yes |
| PROFIBUS DP Services: DPV0 | Yes |
| PROFIBUS DP Services: DPV1 | Yes |
| Diagnostics function | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes |
| Diagnostics indication LED: RUN LED | Yes; green LED |
| Diagnostics indication LED: ERROR LED | Yes; red LED |
| Diagnostics indication LED: MAINT LED | Yes; Yellow LED |
| Diagnostics indication LED: Connection display DP | Yes; green LED |
| between the load voltages | Yes |
|---|---|
| between PROFIBUS DP and all other circuit components | Yes |
| Isolation tested with | 707 V DC (type test) |
|---|
| IP degree of protection | IP65/67 |
|---|
| Suitable for safety-related tripping of standard modules | Yes; from FS01 |
|---|---|
| Highest safety class achievable for safety-related tripping of standard modules: Performance level according to ISO 13849-1 | PL d |
| Ambient temperature during operation: min. | -30 °C |
|---|---|
| Ambient temperature during operation: max. | 55 °C |
| Design of electrical connection for supply voltage | M8, 4-pole |
|---|---|
| ET-Connection: ET-Connection | M8, 4-pin, shielded |
| Width | 45 mm |
|---|---|
| Height | 159 mm |
| Depth | 46 mm |
| Weight, approx. | 211 g |
|---|
| eClass | 9.1 27-24-26-08 |
|---|---|
| ETIM | 10 EC001604 |
| IDEA | 4 3564 |
| UNSPSC | 15 32-15-17-05 |
| China RoHS Manufacturer Declara- | tion |
|---|---|
| EMV Maritime application | NK / Nippon Kaiji Ky- okai Industrial Commu- |
| Maritime application other | nication |
| Net weight | 0.246 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.746 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of IM 157-1 DP is 4 A.
The tariff (HS) code on file for IM 157-1 DP is 85176200.
The EAN (GTIN) of IM 157-1 DP is 4047623403494.
IM 157-1 DP ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.