- Home
- All Products
- Siemens 6ES7155-6AR01-0AN0 SIMATIC ET 200SP IM 155-6 PN Basic PROFINET Interface Module Siemens 6ES7155-6AR01-0AN0 SIMATIC ET 200SP IM 155-6 PN Basic PROFINET Interface Module
Siemens 6ES7155-6AR01-0AN0 SIMATIC ET 200SP IM 155-6 PN Basic PROFINET Interface Module
Get Quote
- Description
The Siemens 6ES7155-6AR01-0AN0 is a SIMATIC ET 200SP IM 155-6 PN Basic PROFINET interface module that heads a station of up to 16 ET 200SP I/O modules over two integrated RJ45 ports. It supports PROFINET IRT down to 1ms cycle time, MRP media redundancy, hot swapping, and runs on 24V DC drawing 200mA typical.
Technical Specifications
| Order No. (MLFB) | 6ES7155-6AR01-0AN0 |
| EAN | 4047623416012 |
| Brand | Siemens |
| Series | SIMATIC ET 200SP |
| Product Type | PROFINET Interface Module |
| Firmware Version | V6.4.0 |
| Max. ET 200SP I/O Modules | 16 |
| Max. Submodules per Station | 256 |
| Supply Voltage | 24 V DC (19.2-28.8 V) |
| Current Consumption | 200 mA rated / 300 mA max. |
| Power Loss | 1.8 W typ. |
| Interfaces | 2x RJ45 (integrated switch), 100BASE-TX |
| PROFINET Security Class | 1 |
| Isochronous Real-Time (IRT) | 1-4 ms at 125 µs intervals |
| Media Redundancy | MRP, MRPD |
| Module Swapping | Hot swap (multi-hot swap) |
| Address Space per Station | 128 bytes max. |
| Max. Installation Altitude | 5000 m |
| Dimensions (W x H x D) | 35 x 117 x 74 mm |
| Weight | 125 g |
| Ambient Temperature (Operation) | -30 to +60 °C (horizontal); -30 to +50 °C (vertical) |
Selection Notes
The two-port integrated switch and MRP/MRPD support let this IM 155-6 PN Basic head unit sit in a ring topology for bumpless recovery from a single cable break — choose a High Feature or High Speed IM variant instead if the application needs isochronous PROFINET below the 1ms cycle time or more than the 6 local coupling channels this Basic module offers. Hot-swap support (multi-hot swap) means individual I/O modules downstream can be replaced without powering down the whole station, which matters for stations with 16 modules where a single fault shouldn't force a full station stop. PROFINET Security Class 1 with signed firmware updates is the baseline security level in the ET 200SP interface-module range — confirm the security class needed at commissioning before assuming this Basic variant meets a higher-class network security policy.
Applications
Heads a decentralized ET 200SP I/O station on a PROFINET line — machine-local or remote I/O drops in packaging, material handling, and process automation where up to 16 I/O modules and ring-redundant PROFINET are needed.