Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens 6ES7144-4JF00-0AB0 is a SIMATIC ET 200pro High Feature analog input module with 4 RTD channels covering Pt100/200/500/1000 and Ni100/120/200/500/1000 sensors, plus direct resistance ranges to 3000 ohms. It supports 2-, 3- and 4-wire connections, resolves 15 bit with overrange, and holds a temperature error of only 0.002%/K across four independently wired channels on the ET 200pro backplane.
Support for both Pt and Ni resistance thermometers across nine sensor types, plus direct resistance ranges to 3000 ohms, means one module covers most RTD wiring already in a plant without matching a specific sensor type at order time. The 4-wire connection option removes lead-resistance error over long cable runs, which the simpler 2-wire mode doesn't correct for; use 4-wire whenever the RTD run exceeds a few meters. Choose the AI-TC module instead when the sensors are thermocouples rather than resistance elements.
Fits ET 200pro stations measuring process or bearing temperature from RTD sensors, such as tank, oven or motor-winding temperature monitoring where 0.002%/K temperature stability matters over long production runs.
| Rated value (DC) | 24 V |
|---|---|
| Reverse polarity protection | Yes; against destruction |
| from supply voltage 1L+, max. | 27 mA; Typical |
|---|---|
| from backplane bus 3.3 V DC, max. | 10 mA; Typical |
| Power loss, typ. | 0.7 W |
|---|
| Part number | 6ES7144-4JF00-0AB0 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515073840 |
| ETIM class | EC001596 |
| eCl@ss | 27242601 |
| Address space per module: Address space per module, max. | 8 byte |
|---|
| Number of analog inputs | 4 |
|---|---|
| Constant measurement current for resistance-type transmitter, typ. | 1.25 mA; 1.25 / 0.5 mA depending on measuring range |
| Cycle time (all channels) max. | 83 ms; 83 ms at 50 Hz; 69 ms at 60 Hz |
| Technical unit for temperature measurement adjustable | Yes; Degrees Celsius/degrees Fahrenheit |
| Input ranges (rated values), resistance thermometer: Cu 10 | No |
| Input ranges (rated values), resistance thermometer: Ni 100 | Yes |
| Input ranges (rated values), resistance thermometer: Input resistance (Ni 100) | 10 000 kΩ |
| Input ranges (rated values), resistance thermometer: Ni 1000 | Yes |
| Input ranges (rated values), resistance thermometer: Ni 120 | Yes |
| Input ranges (rated values), resistance thermometer: Ni 200 | Yes |
| Input ranges (rated values), resistance thermometer: Ni 500 | Yes |
| Input ranges (rated values), resistance thermometer: Pt 100 | Yes |
| Input ranges (rated values), resistance thermometer: Pt 1000 | Yes |
| Input ranges (rated values), resistance thermometer: Pt 200 | Yes |
| Input ranges (rated values), resistance thermometer: Pt 500 | Yes |
| Input ranges (rated values), resistors: 0 to 150 ohms | Yes |
| Input ranges (rated values), resistors: Input resistance (0 to 150 ohms) | 10 000 kΩ |
| Input ranges (rated values), resistors: 0 to 300 ohms | Yes |
| Input ranges (rated values), resistors: Input resistance (0 to 300 ohms) | 10 000 kΩ |
| Input ranges (rated values), resistors: 0 to 600 ohms | Yes |
| Input ranges (rated values), resistors: Input resistance (0 to 600 ohms) | 10 000 kΩ |
| Input ranges (rated values), resistors: 0 to 3000 ohms | Yes |
| Input ranges (rated values), resistors: PTC | Yes |
| Input ranges (rated values), resistors: Input resistance (PTC) | 10 000 kΩ |
| Characteristic linearization: Parameterizable | Yes |
| Characteristic linearization: for resistance thermometer | Ptxxx, Nixxx |
| Cable length: shielded, max. | 30 m |
| Measurement principle | integrating |
|---|---|
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 15 bit; at 150, 300, 600 und 3 000 ohms; otherwise 15 bits + sign |
| Integration and conversion time/resolution per channel: Integration time (ms) | 20 / 16,667 |
| Integration and conversion time/resolution per channel: Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
| Integration and conversion time/resolution per channel: Conversion time (per channel) | 20.625 ms; 20.625 ms at 50 Hz; 17.25 ms at 60 Hz |
| Smoothing of measured values: Parameterizable | Yes |
| Smoothing of measured values: Step: None | Yes; 1x cycle time |
| Smoothing of measured values: Step: low | Yes; 4x cycle time |
| Smoothing of measured values: Step: Medium | Yes; 16x cycle time |
| Smoothing of measured values: Step: High | Yes; 64x cycle time |
| Connection of signal encoders: for resistance measurement with two-wire connection | Yes; Line resistances are also measured |
|---|
| Linearity error (relative to input range), (+/-) | 0.05 % |
|---|---|
| Temperature error (relative to input range), (+/-) | 0.002 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.015 % |
| Operational error limit in overall temperature range: Resistance thermometer, relative to input range, (+/-) | 0.175 % |
| Basic error limit (operational limit at 25 °C): Resistance thermometer, relative to input range, (+/-) | 0.125 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency: Series mode interference (peak value of interference < rated value of input range), min. | 50 dB |
| Diagnostics function | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes; Parameterizable |
| Alarms: Hardware interrupt | No |
| Diagnoses: Diagnostic information readable | Yes |
| Diagnoses: Wire break | Yes |
| Diagnoses: Overflow/Underflow | Yes |
| Diagnostics indication LED: Group error SF (red) | Yes |
| eClass | 16 27-24-26-01 |
|---|---|
| ETIM | 10 EC001596 |
| IDEA | 4 3562 |
| UNSPSC | 15 32-15-17-05 |
| Net weight | 0.179 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.679 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of 6ES7144-4JF00-0AB0 is 24 V AC.
The tariff (HS) code on file for 6ES7144-4JF00-0AB0 is 85389091.
The EAN (GTIN) of 6ES7144-4JF00-0AB0 is 4025515073840.
6ES7144-4JF00-0AB0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.