Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens 6ES7143-5AH00-0BA0 is a SIMATIC ET 200AL I/O module with 16 channels parameterizable as digital input, output, or fast counter, rated 24 V DC / 0.5 A. Eight M12 ports give it IP65/67 protection for machine-mounted installation, and up to 4 channels can run as 2 kHz counters with 32-bit width.
Every one of the 16 channels can be set as input, output, or counter in the engineering tool, so this module replaces a fixed-ratio I/O card when a station's DI/DO mix changes between projects or machine variants. The 2 kHz, 32-bit counting function on up to 4 channels covers basic encoder or flow-pulse counting without adding a dedicated counter module. Choose the fixed DIQ 4+DQ 4 variant instead when the mix is known and the smaller 30 mm housing width matters more than channel flexibility.
Suits IP67 machine-mounted stations where the digital I/O ratio isn't fixed at design time, or where a handful of channels need pulse counting alongside standard DI/DO, such as packaging or conveyor cells with integrated encoders.
| Product type designation | DIQ 16x24VDC/0.5A |
|---|---|
| HW functional status | FS06 |
| Firmware version | V2.0.x |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | STEP 7 V14 or higher |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP4 Hotfix 7 or higher |
| Engineering with: PROFIBUS from GSD version/GSD revision | GSD as of Revision 5 |
| Engineering with: PROFINET from GSD version/GSD revision | GSDML V2.3.1 |
| Operating mode: DI | Yes |
| Operating mode: Counter | Yes |
| Operating mode: DQ | Yes |
| power supply according to NEC Class 2 required | No |
|---|---|
| Load voltage 1L+: Rated value (DC) | 24 V |
| Load voltage 1L+: permissible range, lower limit (DC) | 20.4 V |
| Load voltage 1L+: permissible range, upper limit (DC) | 28.8 V |
| Load voltage 1L+: Reverse polarity protection | Yes; Against destruction; encoder power supply outputs applied with reversed polarity, loads pick up |
| Load voltage 2L+: Rated value (DC) | 24 V |
| Load voltage 2L+: permissible range, lower limit (DC) | 20.4 V |
| Load voltage 2L+: permissible range, upper limit (DC) | 28.8 V |
| Load voltage 2L+: Reverse polarity protection | Yes; Against destruction; encoder power supply outputs applied with reversed polarity, loads pick up |
| Current consumption (rated value) | 60 mA; 60 mA (1L+) / 40 mA (2L+); without load |
|---|---|
| from load voltage 1L+ (unswitched voltage) | 4 A; Maximum value |
| from load voltage 2L+, max. | 4 A; Maximum value |
| Part number | 6ES7143-5AH00-0BA0 |
|---|---|
| Type designation | DIQ 16x24VDC/0.5A |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623405917 |
| ETIM class | EC001599 |
| eCl@ss | 27242604 |
| Number of outputs | 8 |
|---|---|
| 24 V encoder supply: Short-circuit protection | Yes; Per load voltage, electronic |
| 24 V encoder supply: Output current, max. | 1.4 A; Total current of all encoders, max. 0.7 A per load voltage |
| Power loss, typ. | 4 W |
|---|
| Number of digital inputs | 16; Parameterizable as DIQ |
|---|---|
| Sourcing/sinking input | P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
| Number of simultaneously controllable inputs all mounting positions: up to 55 °C, max. | 16 |
| Digital input functions, parameterizable: Freely usable digital input | Yes |
| Digital input functions, parameterizable: Counter | Yes |
| Digital input functions, parameterizable: Number, max. | 4 |
| Digital input functions, parameterizable: Counting frequency, max. | 2 kHz |
| Digital input functions, parameterizable: Counting width | 32 bit; Incl. sign |
| Digital input functions, parameterizable: Counting direction up/down | Yes |
| Input voltage: Rated value (DC) | 24 V |
| Input voltage: for signal "0" | -3 to +5V |
| Input voltage: for signal "1" | +11 to +30V |
| Input current: for signal "1", typ. | 3 mA |
| Input delay (for rated value of input voltage) for standard inputs: parameterizable | Yes |
| Cable length: unshielded, max. | 30 m |
| Number of digital outputs | 16; Parameterizable as DIQ |
|---|---|
| in groups of | 8; 2 load groups for 8 outputs each |
| Current-sourcing | Yes |
| output type acc. to IEC 61131, type 0.5 | Yes |
| Short-circuit protection | Yes; per channel, electronic |
| Response threshold, typ. | 0.7 A |
| Limitation of inductive shutdown voltage to Digital output functions, parameterizable | L+ (-53 V) |
| Switching tripped by comparison values | Yes |
| Freely usable digital output | Yes |
| Switching capacity of the outputs: on lamp load, max. | 5 W |
| Load resistance range: lower limit | 48 Ω |
| Load resistance range: upper limit | 4 kΩ |
| Output voltage: for signal "1", min. | L+ (-0.8 V) |
| Output current: for signal "1" rated value | 0.5 A |
| Output current: for signal "0" residual current, max. | 0.5 mA |
| Switching frequency: with resistive load, max. | 100 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz |
| Switching frequency: on lamp load, max. | 1 Hz |
| Total current of the outputs: Current per group, max. | 4 A |
| Cable length: unshielded, max. | 30 m |
| Connectable encoders: 2-wire sensor | Yes |
|---|---|
| Connectable encoders: permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Substitute values connectable | Yes; channel by channel, parameterizable |
|---|---|
| Alarms: Diagnostic alarm | Yes; Parameterizable |
| Diagnoses: short-circuit | Yes; Outputs to M; encoder supply to M; module by module |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for module diagnostics | Yes; green/red LED |
| Diagnostics indication LED: For load voltage monitoring | Yes; green LED |
| between the load voltages | Yes |
|---|---|
| Potential separation channels: between the channels, in groups of | 8 |
| Potential separation channels: between the channels and backplane bus | Yes |
| Potential separation channels: between the channels and the power supply of the | No; 8 channels are non-isolated and 8 channels are isolated from supply |
| electronics | voltage 1L+ |
| Isolation tested with | 707 V DC (type test) |
|---|
| IP degree of protection | IP65/67 |
|---|
| Suitable for safety-related tripping of standard modules | No |
|---|
| signed firmware update | Yes |
|---|---|
| data integrity | Yes |
| Ambient temperature during operation: min. | -30 °C |
|---|---|
| Ambient temperature during operation: max. | 55 °C |
| Altitude during operation relating to sea level: Ambient air temperature-barometric pressure-altitude | Up to max. 5 000 m, at installation height > 2 000 m additional restrictions |
| Design of electrical connection for the inputs and outputs | M12, 5-pole |
|---|---|
| Design of electrical connection for supply voltage | M8, 4-pole |
| ET-Connection: ET-Connection | M8, 4-pin, shielded |
| Width | 45 mm |
|---|---|
| Height | 159 mm |
| Depth | 40 mm |
| Weight, approx. | 195 g |
|---|
| eClass | 7.1 27-24-26-04 |
|---|---|
| ETIM | 10 EC001599 |
| IDEA | 4 3566 |
| UNSPSC | 15 32-15-17-05 |
| Net weight | 0.217 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.717 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of DIQ 16x24VDC/0.5A is 0.5 A.
The rated operational voltage of DIQ 16x24VDC/0.5A is 24 V AC.
The tariff (HS) code on file for DIQ 16x24VDC/0.5A is 85389091.
The EAN (GTIN) of DIQ 16x24VDC/0.5A is 4047623405917.
DIQ 16x24VDC/0.5A ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.