Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Siemens 6ES7143-4BF00-0AA0 is a SIMATIC ET 200pro combination module with 4 fixed digital outputs plus 4 channels that can be parameterized as either input or output, all rated 24 V DC at 0.5 A. It is suitable for safety-related tripping of standard modules to Performance Level d (Category 3) and SIL 2.
The 4 parameterizable DIO channels are what separate this module from a fixed 4DO or 8DO card: each of the 4 can be configured as input or output independently, so one module covers a mixed sensor/actuator station slot without dedicating a second module to a handful of extra inputs. Outputs are split into 2 load groups of up to 2 A each, a limit to check when wiring several 0.5 A loads per group. Because it is suitable for safety-related tripping of standard modules to PL d / SIL 2, a fail-safe CPU can switch a standard actuator through this channel without a dedicated F-DQ module. The connection module IO 6ES7194-4CB50-0AA0 must be ordered separately to complete the backplane slot.
Mixed digital I/O in distributed SIMATIC ET 200pro stations where a slot needs both extra sensor inputs and low-current actuator outputs - proximity switches paired with pilot lamps or small solenoids on the same module.
| Rated value (DC) | 24 V |
|---|---|
| Reverse polarity protection | Yes; Against destruction; encoder power supply outputs applied with reversed polarity |
| Load voltage 2L+: Rated value (DC) | 24 V |
| Load voltage 2L+: Short-circuit protection | Yes |
| Load voltage 2L+: Reverse polarity protection | Yes; against destruction; load increasing |
| from supply voltage 1L+, max. | 20 mA |
|---|---|
| from load voltage 2L+ (without load), max. | 20 mA |
| from backplane bus 3.3 V DC, max. | 30 mA |
| Short-circuit protection | Yes; per module, electronic |
|---|---|
| Output current: up to 55 °C, max. | 1 A |
| Part number | 6ES7143-4BF00-0AA0 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515079477 |
| ETIM class | EC001599 |
| eCl@ss | 27242604 |
| Power loss, typ. | 3 W |
|---|
| Number of digital inputs | 4; 4 DIOs can be parameterized |
|---|---|
| Sourcing/sinking input | P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
| Number of simultaneously controllable inputs all mounting positions: up to 55 °C, max. | 4 |
| Input voltage: Rated value (DC) | 24 V |
| Input voltage: for signal "0" | -3 to +5V |
| Input voltage: for signal "1" | +11 to +30V |
| Input current: for signal "1", typ. | 7 mA |
| Input delay (for rated value of input voltage) for standard inputs: at "0" to "1", min. | 1.2 ms |
| Cable length: unshielded, max. | 30 m |
| Number of digital outputs | 8; 4 DO fixed, 4 DIO parameterizable |
|---|---|
| in groups of | 4; 2 load groups for 4 outputs each |
| Current-sourcing | Yes |
| output type acc. to IEC 61131, type 0.5 | Yes |
| Short-circuit protection | Yes; per channel, electronic |
| Response threshold, typ. | 0.7 A |
| Limitation of inductive shutdown voltage to | Typ. (L1+, L2+) -47 V |
| Controlling a digital input | Yes |
| Switching capacity of the outputs: on lamp load, max. | 5 W |
| Load resistance range: lower limit | 48 Ω |
| Load resistance range: upper limit | 4 kΩ |
| Output voltage: for signal "1", min. | 2L+ (-0,8 V) |
| Output current: for signal "1" rated value | 0.5 A |
| Output current: for signal "0" residual current, max. | 0.5 mA |
| Parallel switching of two outputs: for uprating | No |
| Parallel switching of two outputs: for redundant control of a load | Yes |
| Switching frequency: with resistive load, max. | 100 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz |
| Switching frequency: on lamp load, max. | 1 Hz |
| Total current of the outputs (per group) all mounting positions: up to 55 °C, max. | 2 A |
| Cable length: unshielded, max. | 30 m |
| Connectable encoders: 2-wire sensor | Yes |
|---|---|
| Connectable encoders: permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Diagnostics function | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes |
| Diagnoses: Diagnostic information readable | Yes |
| Diagnoses: Short-circuit | Yes; Short-circuit of outputs to ground; module by module |
| Diagnostics indication LED: Group error SF (red) | Yes |
| Diagnostics indication LED: Status indicator digital input (green) | Yes |
| Diagnostics indication LED: Status indicator digital output (green) | Yes |
| between backplane bus and all other circuit components | Yes |
|---|---|
| Potential separation digital inputs: between the channels | No |
| Potential separation digital inputs: between the channels and backplane bus | Yes |
| Potential separation digital outputs: between the channels and backplane bus | Yes |
| Isolation tested with | 707 V DC (type test) |
|---|
| Suitable for safety-related tripping of standard modules | Yes |
|---|---|
| Highest safety class achievable for safety-related tripping of standard modules: Performance level according to ISO 13849-1 | PL d |
| Width | 45 mm |
|---|---|
| Height | 130 mm |
| Depth | 35 mm |
| Weight, approx. | 140 g |
|---|
| China RoHS Manufacturer Declara- | tion |
|---|---|
| Maritime application | NK / Nippon Kaiji Ky- okai |
| Net weight | 0.176 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.676 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 6ES7143-4BF00-0AA0 is 0.5 A.
The rated operational voltage of 6ES7143-4BF00-0AA0 is 24 V AC.
The tariff (HS) code on file for 6ES7143-4BF00-0AA0 is 85389091.
The EAN (GTIN) of 6ES7143-4BF00-0AA0 is 4025515079477.
6ES7143-4BF00-0AA0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.