The Siemens 6ES7138-7FN00-0AB0 is a fail-safe SIMATIC ET 200iSP digital input module with 8 NAMUR-encoder channels for Zone 1 gas areas, certified SIL 3 per IEC 61508 and PLe per ISO 13849-1, reaching Category 4 in two-channel wiring or Category 3 single-channel per EN 954-1. It draws 145 mA typical from its DC supply and reads wire-break and short-circuit faults per channel.
NAMUR-only wiring per DIN 19234 is what limits this module to proximity switches and mechanical contacts with the standard 10 kohm parallel resistor rather than general-purpose 24 V sensors. Two-channel wiring of a NAMUR sensor pair reaches Category 4 / SIL 3, while a single-channel sensor is limited to Category 3, so the wiring scheme should match the interlock's required safety integrity. The 8-channel count and 500 m shielded cable length suit spreading sensors across a large hazardous-area skid from one module.
| Product type designation | 8F-DI ExNAMUR |
|---|
| Rack mounting | No |
|---|---|
| Front mounting | Yes |
| Rail mounting | Yes |
| Wall mounting/direct mounting | Yes |
| Type of supply voltage | DC |
|---|
| Part number | 6ES7138-7FN00-0AB0 |
|---|---|
| Type designation | 8F-DI ExNAMUR |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 4019169227360 |
| Current consumption, typ. | 145 mA |
|---|---|
| from supply voltage L+, max. | 150 mA; int. Powerbus |
| Number of outputs | 8 |
|---|---|
| Output voltage (DC) | 8 V |
| Power loss, typ. | 1.4 W |
|---|
| Address space per module: Inputs | 6 byte |
|---|---|
| Address space per module: Outputs | 4 byte |
| Fieldbus connection via separate transceiver | Yes |
|---|
| Number of digital inputs | 8 |
|---|---|
| Input voltage: Type of input voltage | DC |
| Input current: for signal "0", max. (permissible quiescent current) | 1.2 mA |
| Input current: for signal "1", min. | 2.1 mA |
| Input current: for signal "1", typ. | 9.5 mA |
| Input delay (for rated value of input voltage): Delay time for signal change, min. | 0.7 ms |
| Input delay (for rated value of input voltage): at "0" to "1", min. | 0.7 ms |
| Input delay (for rated value of input voltage): at "0" to "1", max. | 16 ms; Parameterizable |
| Input delay (for rated value of input voltage): at "1" to "0", min. | 0.7 ms |
| Input delay (for rated value of input voltage): at "1" to "0", max. | 16 ms; Parameterizable |
| Cable length: shielded, max. | 500 m |
| Cable length: unshielded, max. | 200 m |
| Number of connectable encoders, max. | 8 |
|---|---|
| Connectable encoders: NAMUR encoder | Yes |
| Number of PROFINET interfaces | 0 |
|---|---|
| Number of RS 485 interfaces | 0 |
| Supports protocol for PROFINET IO | No |
|---|---|
| PROFIBUS | No |
| Diagnostics function | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes; Parameterizable |
| Alarms: Hardware interrupt | No |
| Diagnoses: Diagnostic information readable | Yes |
| Diagnoses: Wire break | Yes; NAMUR encoders or single contact with 10 kOhm parallel resistor |
| Diagnoses: Short-circuit | Yes; R load < 150 ohms with NAMUR sensor/sensor and NAMUR changeover contact/sensor to DIN 19234 |
| Diagnostics indication LED: Group error SF (red) | Yes |
| Potential separation digital inputs: between the channels | No |
|---|---|
| Potential separation digital inputs: between the channels and backplane bus | Yes |
| between different circuits | 60 V DC/30 V AC |
|---|
| Isolation tested with | 350 V AC/1 min between the shield and backplane bus connection 350 V AC/1 min between the shield and I/O 2830 V AC/1 min between backplane bus connection and I/O |
|---|
| IP degree of protection | IP30 |
|---|
| CE mark | Yes |
|---|---|
| Suitable for safety functions | Yes |
| reference designation according to IEC 81346-2 (2009) | K |
| Highest safety class achievable in safety mode: acc. to EN 954 | Cat. 3 (single-channel), Cat. 4 (two-channel) |
| Highest safety class achievable in safety mode: Performance level according to ISO 13849-1 | PLe |
| Highest safety class achievable in safety mode: SIL acc. to IEC 61508 | SIL 3 |
| Use in hazardous areas: ATEX marking | II 2 G (1) GD Ex ib[ia Ga][ia IIIC Da] IIC T4 GB and I M2 Ex ib[ia Ma] I Mb |
| Use in hazardous areas: ATEX certificate | 10 ATEX 0056 |
| Use in hazardous areas: Explosion protection category for gas | ATEX gas explosion protection, Cat. 2 |
| Use in hazardous areas: associated equipment (Ex ia) | Yes |
| Use in hazardous areas: associated equipment (Ex ib) | Yes |
| Design of electrical connection | Screw/spring-type terminal |
|---|
| Width | 30 mm |
|---|---|
| Height | 129 mm |
| Depth | 136.5 mm |
| Weight, approx. | 288 g |
|---|
| eClass | 16 27-24-26-04 |
|---|---|
| ETIM | 10 EC001599 |
| IDEA | 4 3566 |
| UNSPSC | 15 32-15-17-05 |
| Shipping weight | 0.857 kg |
|---|---|
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for 8F-DI ExNAMUR is 85389091.
The EAN (GTIN) of 8F-DI ExNAMUR is 4019169227360.
8F-DI ExNAMUR ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.