The Siemens 6ES7135-7TD00-0AB0 is an ET200iSP electronic module with 4 analog current outputs for HART field devices, certified Ex ib [ia Ga] IIC T4 Gb for ATEX and IECEx Zone 1 hazardous areas. It drives a 4-20 mA or 0-20 mA signal over a two-wire connection up to 750 ohm load, with HART protocol version 6.0 and 14-bit resolution.
The 750 ohm max. load impedance and two-wire current output cover most HART positioners and I/P converters wired directly from the classified zone, without a separate isolation barrier for the output signal. Pick this 4AO HART module over the 4AI HART input card when the ET200iSP station needs to drive field actuators rather than read transmitters; the two share the same Ex ib Zone 1 rating and IECEx approval family.
| Product type designation | 4AQ I HART |
|---|---|
| HW functional status | 17 |
| Firmware version | V3.0.4 |
| Rack mounting | No |
|---|---|
| Front mounting | Yes |
| Rail mounting | Yes |
| Wall mounting/direct mounting | No |
| Type of supply voltage | DC |
|---|---|
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Part number | 6ES7135-7TD00-0AB0 |
|---|---|
| Type designation | 4AQ I HART |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4019169131681 |
| ETIM class | EC001596 |
| eCl@ss | 27242601 |
| Current consumption, typ. | 295 mA |
|---|---|
| from load voltage (power bus), max. | 330 mA |
| Power loss, typ. | 2.7 W |
|---|
| Fieldbus connection via separate transceiver | Yes |
|---|
| Number of analog outputs | 4 |
|---|---|
| Cycle time (all channels) max. | 3.6 ms |
| Voltage signal at analog output | No |
| Current signal at analog output | Yes |
| Output ranges, current: 0 to 20 mA | Yes |
| Output ranges, current: 4 mA to 20 mA | Yes |
| Connection of actuators: for current output two-wire connection | Yes |
| Load impedance (in rated range of output): with current outputs, max. | 750 Ω |
| Cable length: shielded, max. | 500 m |
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 14 bit |
|---|---|
| Settling time: for resistive load | 4 ms |
| Settling time: for capacitive load | 40 ms |
| Settling time: for inductive load | 40 ms |
| Linearity error (relative to output range), (+/-) | 0.015 % |
|---|---|
| Temperature error (relative to output range), (+/-) | 0.005 %/K |
| Crosstalk between the outputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.01 % |
| Operational error limit in overall temperature range: Current, relative to output range, (+/-) | 0.15 % |
| Basic error limit (operational limit at 25 °C): Current, relative to output range, (+/-) | 0.1 % |
| Number of PROFINET interfaces | 0 |
|---|
| PROFINET IO | No |
|---|---|
| PROFIsafe | No |
| PROFIBUS | No |
| Further protocols: other bus systems | No |
| Substitute values connectable | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes |
| Diagnoses: Diagnostic information readable | Yes |
| Diagnoses: Wire break | Yes; I load > 1 mA |
| Diagnoses: Short-circuit | Yes; I load > 1 mA |
| Diagnostics indication LED: Group error SF (red) | Yes |
| Module for Ex(i) protection | Yes; for more Co/Lo combinations, see certificate IECEx KEM 05.0012 |
|---|---|
| maximum values for connecting terminals for gas group IIC: Uo (no-load voltage), max. | 27.6 V |
| maximum values for connecting terminals for gas group IIC: Io (short-circuit current), max. | 88.2 mA |
| maximum values for connecting terminals for gas group IIC: Po (power output), max. | 0.61 mW |
| maximum values for connecting terminals for gas group IIC: Co (permissible external capacity), max. | 83 nF |
| maximum values for connecting terminals for gas group IIC: Lo (permissible external inductivity), max. | 3 mH |
| between channels and powerbus | Yes |
|---|---|
| Potential separation analog outputs: between the channels | No |
| Potential separation analog outputs: between the channels and backplane bus | Yes |
| IP degree of protection | IP30 |
|---|
| CE mark | CE 0344 |
|---|---|
| UKCA mark | DEKRA 21UKEX0091 Importer UK: Siemens plc Manchester M20 2UR |
| cULus | LISTED E334384 |
| FM approval | CLASSIFIED 3025852 |
| Suitable for safety functions | No |
| INMETRO certificate | UL-BR 12.0070 |
| reference designation according to IEC 81346-2 (2009) | K |
| Use in hazardous areas: ATEX marking | II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb |
| Use in hazardous areas: ATEX certificate | KEMA 04 ATEX 1250 |
| Use in hazardous areas: IECEx | IECEx KEM 05.0012 |
| Use in hazardous areas: CCC Ex | 2020322316002946 |
| Use in hazardous areas: EAC Ex | PB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC |
| Use in hazardous areas: FM marking | Class I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G |
| Use in hazardous areas: Explosion protection category for gas | ATEX gas explosion protection, Zone 1 |
| Use in hazardous areas: Explosion protection category for dust | ATEX dust explosion protection, Zone 21 always install in corresponding enclosure |
| Use in hazardous areas: associated equipment (Ex ia) | Yes |
| Use in hazardous areas: associated equipment (Ex ib) | Yes |
| Design of electrical connection | Screw/spring-type terminal |
|---|
| Width | 30 mm |
|---|---|
| Height | 129 mm |
| Depth | 136.5 mm |
| Weight, approx. | 265 g |
|---|
| Net weight | 0.337 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.837 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for 4AQ I HART is 85389091.
The EAN (GTIN) of 4AQ I HART is 4019169131681.
4AQ I HART ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.