Part number
6ES7135-7TD00-0AB0
Model no
4AQ I HART
$767.97 On request Dispatch — · From TürkiyeGet a Quote
SIMATIC ET 200SP

Siemens 6ES7135-7TD00-0AB0 ET200iSP 4AO HART 4-20mA Ex Zone 1 Remote I/O Module

ET200iSP 4AO HART module, 4-20mA current output, Ex ib Zone 1, 14-bit, 750 ohm load.

Communication
HART protocol V6.0
EAN
4019169131681
Description

About the 4AQ I HART

The Siemens 6ES7135-7TD00-0AB0 is an ET200iSP electronic module with 4 analog current outputs for HART field devices, certified Ex ib [ia Ga] IIC T4 Gb for ATEX and IECEx Zone 1 hazardous areas. It drives a 4-20 mA or 0-20 mA signal over a two-wire connection up to 750 ohm load, with HART protocol version 6.0 and 14-bit resolution.

Selection Notes

The 750 ohm max. load impedance and two-wire current output cover most HART positioners and I/P converters wired directly from the classified zone, without a separate isolation barrier for the output signal. Pick this 4AO HART module over the 4AI HART input card when the ET200iSP station needs to drive field actuators rather than read transmitters; the two share the same Ex ib Zone 1 rating and IECEx approval family.

Specification

Full specification

92 values · Last verified 01 Nov 2026

General information 3

Product type designation 4AQ I HART
HW functional status 17
Firmware version V3.0.4

Installation type/mounting 4

Rack mounting No
Front mounting Yes
Rail mounting Yes
Wall mounting/direct mounting No

Supply voltage 3

Type of supply voltage DC
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Show all 92 specifications ↓ Show less ↑82 more values in Identification, Input current, Power loss, Hardware configuration, Analog outputs, Analog value generation for the outputs, Errors/accuracies, Interfaces, Protocols, Interrupts/diagnostics/status information, Ex(i) characteristics, Potential separation, Degree and class of protection, Standards, approvals, certificates, Connection method, Dimensions, Weights, Logistics.

Identification 10

Part number 6ES7135-7TD00-0AB0
Type designation 4AQ I HART
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4019169131681
ETIM class EC001596
eCl@ss 27242601

Input current 2

Current consumption, typ. 295 mA
from load voltage (power bus), max. 330 mA

Power loss 1

Power loss, typ. 2.7 W

Hardware configuration 1

Fieldbus connection via separate transceiver Yes

Analog outputs 9

Number of analog outputs 4
Cycle time (all channels) max. 3.6 ms
Voltage signal at analog output No
Current signal at analog output Yes
Output ranges, current: 0 to 20 mA Yes
Output ranges, current: 4 mA to 20 mA Yes
Connection of actuators: for current output two-wire connection Yes
Load impedance (in rated range of output): with current outputs, max. 750 Ω
Cable length: shielded, max. 500 m

Analog value generation for the outputs 4

Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. 14 bit
Settling time: for resistive load 4 ms
Settling time: for capacitive load 40 ms
Settling time: for inductive load 40 ms

Errors/accuracies 6

Linearity error (relative to output range), (+/-) 0.015 %
Temperature error (relative to output range), (+/-) 0.005 %/K
Crosstalk between the outputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.01 %
Operational error limit in overall temperature range: Current, relative to output range, (+/-) 0.15 %
Basic error limit (operational limit at 25 °C): Current, relative to output range, (+/-) 0.1 %

Interfaces 1

Number of PROFINET interfaces 0

Protocols 4

PROFINET IO No
PROFIsafe No
PROFIBUS No
Further protocols: other bus systems No

Interrupts/diagnostics/status information 6

Substitute values connectable Yes
Alarms: Diagnostic alarm Yes
Diagnoses: Diagnostic information readable Yes
Diagnoses: Wire break Yes; I load > 1 mA
Diagnoses: Short-circuit Yes; I load > 1 mA
Diagnostics indication LED: Group error SF (red) Yes

Ex(i) characteristics 6

Module for Ex(i) protection Yes; for more Co/Lo combinations, see certificate IECEx KEM 05.0012
maximum values for connecting terminals for gas group IIC: Uo (no-load voltage), max. 27.6 V
maximum values for connecting terminals for gas group IIC: Io (short-circuit current), max. 88.2 mA
maximum values for connecting terminals for gas group IIC: Po (power output), max. 0.61 mW
maximum values for connecting terminals for gas group IIC: Co (permissible external capacity), max. 83 nF
maximum values for connecting terminals for gas group IIC: Lo (permissible external inductivity), max. 3 mH

Potential separation 3

between channels and powerbus Yes
Potential separation analog outputs: between the channels No
Potential separation analog outputs: between the channels and backplane bus Yes

Degree and class of protection 1

IP degree of protection IP30

Standards, approvals, certificates 17

CE mark CE 0344
UKCA mark DEKRA 21UKEX0091 Importer UK: Siemens plc Manchester M20 2UR
cULus LISTED E334384
FM approval CLASSIFIED 3025852
Suitable for safety functions No
INMETRO certificate UL-BR 12.0070
reference designation according to IEC 81346-2 (2009) K
Use in hazardous areas: ATEX marking II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
Use in hazardous areas: ATEX certificate KEMA 04 ATEX 1250
Use in hazardous areas: IECEx IECEx KEM 05.0012
Use in hazardous areas: CCC Ex 2020322316002946
Use in hazardous areas: EAC Ex PB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC
Use in hazardous areas: FM marking Class I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G
Use in hazardous areas: Explosion protection category for gas ATEX gas explosion protection, Zone 1
Use in hazardous areas: Explosion protection category for dust ATEX dust explosion protection, Zone 21 always install in corresponding enclosure
Use in hazardous areas: associated equipment (Ex ia) Yes
Use in hazardous areas: associated equipment (Ex ib) Yes

Connection method 1

Design of electrical connection Screw/spring-type terminal

Dimensions 3

Width 30 mm
Height 129 mm
Depth 136.5 mm

Weights 1

Weight, approx. 265 g

Logistics 6

Net weight 0.337 kg
Country of origin DE
Shipping weight 0.837 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6ES7135-7TD00-0AB0

No documents are on file for this part yet.

Ask us for the datasheet
Quick answers

Questions about the 4AQ I HART

What is the HS code of 4AQ I HART for customs?

The tariff (HS) code on file for 4AQ I HART is 85389091.

What is the EAN of 4AQ I HART?

The EAN (GTIN) of 4AQ I HART is 4019169131681.

Where does 4AQ I HART ship from, and how fast?

4AQ I HART ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for PLC & controllers

All guides for PLC & controllers
Reviews

Customer reviews

Series

Siemens SIMATIC ET 200SP

Brand
Siemens
Series
SIMATIC ET 200SP
$767.97 On request
Get a Quote
Quote

Get a Quote

4AQ I HART

Genuine parts

Genuine, factory-sealed parts

Siemens · 6ES7135-7TD00-0AB0

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart