The Siemens 6ES7134-7TD00-0AB0 is an ET200iSP electronic module with 4 analog current inputs for 2-wire HART transmitters, certified Ex ib [ia Ga] IIC T4 Gb for ATEX and IECEx Zone 1 hazardous areas. It supports HART protocol version 6.0 over a 4-20 mA signal, with a short-circuit-proof 23 mA transmitter supply per channel and 13-bit resolution.
The 750 ohm burden and 23 mA short-circuit-proof transmitter supply per channel mean this module can power a 2-wire HART transmitter directly over the same loop it reads, without an external barrier for signal power. Choose this HART variant over the plain 4AI TC thermocouple module when the field device is a 4-20 mA loop-powered transmitter rather than a bare thermocouple junction, since HART 6.0 support lets diagnostic and configuration data ride the same current loop.
| Product type designation | 4AI I 2WIRE HART |
|---|---|
| HW functional status | 17 |
| Firmware version | V3.0.4 |
| Product function: Isochronous mode | No |
| Rack mounting | No |
|---|---|
| Front mounting | Yes |
| Rail mounting | Yes |
| Wall mounting/direct mounting | No |
| Type of supply voltage | DC |
|---|---|
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Part number | 6ES7134-7TD00-0AB0 |
|---|---|
| Type designation | 4AI I 2WIRE HART |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4019169131667 |
| ETIM class | EC001596 |
| eCl@ss | 27242601 |
| Current consumption, typ. | 280 mA |
|---|---|
| from load voltage (power bus), max. | 320 mA |
| Power supply to the transmitters: short-circuit proof | Yes |
|---|---|
| Power supply to the transmitters: Supply current, max. | 23 mA; per channel |
| Power loss, typ. | 2.7 W |
|---|
| Fieldbus connection via separate transceiver | Yes |
|---|
| Number of analog inputs | 4 |
|---|---|
| permissible input current for current input (destruction limit), max. | 90 mA |
| Cycle time (all channels) max. | 120 ms; 30 ms basic conversion time x4 channels with 60 Hz, 50 Hz interference frequency suppression |
| Technical unit for temperature measurement adjustable | Yes |
| Input ranges: Voltage | No |
| Input ranges: Current | Yes |
| Input ranges: Thermocouple | No |
| Input ranges: Resistance thermometer | No |
| Input ranges: Resistance | No |
| Input ranges (rated values), currents: 4 mA to 20 mA | Yes |
| Cable length: shielded, max. | 500 m |
| Measurement principle | integrating (Sigma-Delta) |
|---|---|
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 13 bit |
| Integration and conversion time/resolution per channel: Integration time, parameterizable | No |
| Integration and conversion time/resolution per channel: Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
| Smoothing of measured values: parameterizable | Yes; in 4 stages |
| Smoothing of measured values: Step: None | Yes; 1x cycle time |
| Smoothing of measured values: Step: low | Yes; 4x cycle time |
| Smoothing of measured values: Step: Medium | Yes; 32x cycle time |
| Smoothing of measured values: Step: High | Yes; 64x cycle time |
| Connection of signal encoders: for current measurement as 2-wire transducer | Yes |
|---|---|
| Connection of signal encoders: Burden of 2-wire transmitter, max. | 750 Ω |
| Linearity error (relative to input range), (+/-) | 0.015 % |
|---|---|
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.01 % |
| Operational error limit in overall temperature range: Current, relative to input range, (+/-) | 0.15 % |
| Basic error limit (operational limit at 25 °C): Current, relative to input range, (+/-) | 0.1 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency: Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
| Number of PROFINET interfaces | 0 |
|---|
| Supports protocol for PROFINET IO | No |
|---|---|
| PROFIsafe | No |
| PROFIBUS | No |
| Further protocols: other bus systems | No |
| Alarms: Diagnostic alarm | Yes; Parameterizable |
|---|---|
| Alarms: Limit value alarm | Yes; Parameterizable |
| Diagnoses: Diagnostic information readable | Yes |
| Diagnoses: Wire break | Yes; I load < 3.6 mA |
| Diagnoses: Short-circuit | Yes; I load > 25 mA |
| Diagnostics indication LED: Group error SF (red) | Yes |
| Module for Ex(i) protection | Yes; for more Co/Lo combinations, see certificate IECEx KEM 05.0006 |
|---|---|
| maximum values for connecting terminals for gas group IIC: Uo (no-load voltage), max. | 27.6 V |
| maximum values for connecting terminals for gas group IIC: Io (short-circuit current), max. | 88.2 mA |
| maximum values for connecting terminals for gas group IIC: Po (power output), max. | 610 mW |
| maximum values for connecting terminals for gas group IIC: Co (permissible external capacity), max. | 83 nF |
| maximum values for connecting terminals for gas group IIC: Lo (permissible external inductivity), max. | 3 mH |
| between channels and powerbus | Yes |
|---|---|
| Potential separation analog inputs: between the channels | No |
| Potential separation analog inputs: between the channels and backplane bus | Yes |
| IP degree of protection | IP30 |
|---|
| CE mark | CE 0344 |
|---|---|
| UKCA mark | DEKRA 21UKEX0089 Importer UK: Siemens plc Manchester M20 2UR |
| cULus | LISTED E334384 |
| FM approval | CLASSIFIED 3025852 |
| Suitable for safety functions | No |
| INMETRO certificate | UL-BR 12.0072 |
| reference designation according to IEC 81346-2 (2009) | K |
| Highest safety class achievable in safety mode: acc. to EN 954 | n.a. |
| Highest safety class achievable in safety mode: Performance level according to ISO 13849-1 | none |
| Highest safety class achievable in safety mode: SIL acc. to IEC 61508 | No |
| Use in hazardous areas: ATEX marking | II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb |
| Use in hazardous areas: ATEX certificate | KEMA 04 ATEX 1244 |
| Use in hazardous areas: IECEx | IECEx KEM 05.0006 |
| Use in hazardous areas: CCC Ex | 2020322316002941 |
| Use in hazardous areas: EAC Ex | PB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC |
| Use in hazardous areas: FM marking | Class I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G |
| Use in hazardous areas: Explosion protection category for gas | ATEX gas explosion protection, Zone 1 |
| Use in hazardous areas: Explosion protection category for dust | ATEX dust explosion protection, Zone 21 always install in corresponding enclosure |
| Use in hazardous areas: associated equipment (Ex ia) | Yes |
| Use in hazardous areas: associated equipment (Ex ib) | Yes |
| Marine approval: Germanischer Lloyd (GL) | Yes |
| Marine approval: American Bureau of Shipping (ABS) | Yes |
| Marine approval: Bureau Veritas (BV) | Yes |
| Marine approval: Det Norske Veritas (DNV) | Yes |
| Design of electrical connection | Screw/spring-type terminal |
|---|
| Width | 30 mm |
|---|---|
| Height | 129 mm |
| Depth | 136.5 mm |
| Weight, approx. | 230 g |
|---|
| ETIM | 10 EC001596 |
|---|---|
| IDEA | 4 3562 |
| UNSPSC | 15 32-15-17-05 |
| Net weight | 0.341 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.841 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for 4AI I 2WIRE HART is 85389091.
The EAN (GTIN) of 4AI I 2WIRE HART is 4019169131667.
4AI I 2WIRE HART ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.