Part number
6ES7134-7TD00-0AB0
Model no
4AI I 2WIRE HART
$734.85 On request Dispatch — · From TürkiyeGet a Quote
SIMATIC ET 200SP

Siemens 6ES7134-7TD00-0AB0 ET200iSP 4AI HART 2-Wire Ex Zone 1 Remote I/O Module

ET200iSP 4AI HART 2-wire module, 4-20mA, HART 6.0, Ex ib Zone 1, 23mA transmitter supply.

Communication
HART protocol V6.0
EAN
4019169131667
Description

About the 4AI I 2WIRE HART

The Siemens 6ES7134-7TD00-0AB0 is an ET200iSP electronic module with 4 analog current inputs for 2-wire HART transmitters, certified Ex ib [ia Ga] IIC T4 Gb for ATEX and IECEx Zone 1 hazardous areas. It supports HART protocol version 6.0 over a 4-20 mA signal, with a short-circuit-proof 23 mA transmitter supply per channel and 13-bit resolution.

Certifications & Standards

  • GL
  • ABS
  • BV
  • DNV

Selection Notes

The 750 ohm burden and 23 mA short-circuit-proof transmitter supply per channel mean this module can power a 2-wire HART transmitter directly over the same loop it reads, without an external barrier for signal power. Choose this HART variant over the plain 4AI TC thermocouple module when the field device is a 4-20 mA loop-powered transmitter rather than a bare thermocouple junction, since HART 6.0 support lets diagnostic and configuration data ride the same current loop.

Specification

Full specification

115 values · Last verified 01 Nov 2026

General information 4

Product type designation 4AI I 2WIRE HART
HW functional status 17
Firmware version V3.0.4
Product function: Isochronous mode No

Installation type/mounting 4

Rack mounting No
Front mounting Yes
Rail mounting Yes
Wall mounting/direct mounting No

Supply voltage 3

Type of supply voltage DC
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Show all 115 specifications ↓ Show less ↑104 more values in Identification, Input current, Output voltage, Power loss, Hardware configuration, Analog inputs, Analog value generation for the inputs, Encoder, Errors/accuracies, Interfaces, Protocols, Interrupts/diagnostics/status information, Ex(i) characteristics, Potential separation, Degree and class of protection, Standards, approvals, certificates, Connection method, Dimensions, Weights, EClass 6 27-24-26-01, Logistics.

Identification 10

Part number 6ES7134-7TD00-0AB0
Type designation 4AI I 2WIRE HART
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4019169131667
ETIM class EC001596
eCl@ss 27242601

Input current 2

Current consumption, typ. 280 mA
from load voltage (power bus), max. 320 mA

Output voltage 2

Power supply to the transmitters: short-circuit proof Yes
Power supply to the transmitters: Supply current, max. 23 mA; per channel

Power loss 1

Power loss, typ. 2.7 W

Hardware configuration 1

Fieldbus connection via separate transceiver Yes

Analog inputs 11

Number of analog inputs 4
permissible input current for current input (destruction limit), max. 90 mA
Cycle time (all channels) max. 120 ms; 30 ms basic conversion time x4 channels with 60 Hz, 50 Hz interference frequency suppression
Technical unit for temperature measurement adjustable Yes
Input ranges: Voltage No
Input ranges: Current Yes
Input ranges: Thermocouple No
Input ranges: Resistance thermometer No
Input ranges: Resistance No
Input ranges (rated values), currents: 4 mA to 20 mA Yes
Cable length: shielded, max. 500 m

Analog value generation for the inputs 9

Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. 13 bit
Integration and conversion time/resolution per channel: Integration time, parameterizable No
Integration and conversion time/resolution per channel: Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
Smoothing of measured values: parameterizable Yes; in 4 stages
Smoothing of measured values: Step: None Yes; 1x cycle time
Smoothing of measured values: Step: low Yes; 4x cycle time
Smoothing of measured values: Step: Medium Yes; 32x cycle time
Smoothing of measured values: Step: High Yes; 64x cycle time

Encoder 2

Connection of signal encoders: for current measurement as 2-wire transducer Yes
Connection of signal encoders: Burden of 2-wire transmitter, max. 750 Ω

Errors/accuracies 7

Linearity error (relative to input range), (+/-) 0.015 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.01 %
Operational error limit in overall temperature range: Current, relative to input range, (+/-) 0.15 %
Basic error limit (operational limit at 25 °C): Current, relative to input range, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency: Series mode interference (peak value of interference < rated value of input range), min. 70 dB

Interfaces 1

Number of PROFINET interfaces 0

Protocols 4

Supports protocol for PROFINET IO No
PROFIsafe No
PROFIBUS No
Further protocols: other bus systems No

Interrupts/diagnostics/status information 6

Alarms: Diagnostic alarm Yes; Parameterizable
Alarms: Limit value alarm Yes; Parameterizable
Diagnoses: Diagnostic information readable Yes
Diagnoses: Wire break Yes; I load < 3.6 mA
Diagnoses: Short-circuit Yes; I load > 25 mA
Diagnostics indication LED: Group error SF (red) Yes

Ex(i) characteristics 6

Module for Ex(i) protection Yes; for more Co/Lo combinations, see certificate IECEx KEM 05.0006
maximum values for connecting terminals for gas group IIC: Uo (no-load voltage), max. 27.6 V
maximum values for connecting terminals for gas group IIC: Io (short-circuit current), max. 88.2 mA
maximum values for connecting terminals for gas group IIC: Po (power output), max. 610 mW
maximum values for connecting terminals for gas group IIC: Co (permissible external capacity), max. 83 nF
maximum values for connecting terminals for gas group IIC: Lo (permissible external inductivity), max. 3 mH

Potential separation 3

between channels and powerbus Yes
Potential separation analog inputs: between the channels No
Potential separation analog inputs: between the channels and backplane bus Yes

Degree and class of protection 1

IP degree of protection IP30

Standards, approvals, certificates 24

CE mark CE 0344
UKCA mark DEKRA 21UKEX0089 Importer UK: Siemens plc Manchester M20 2UR
cULus LISTED E334384
FM approval CLASSIFIED 3025852
Suitable for safety functions No
INMETRO certificate UL-BR 12.0072
reference designation according to IEC 81346-2 (2009) K
Highest safety class achievable in safety mode: acc. to EN 954 n.a.
Highest safety class achievable in safety mode: Performance level according to ISO 13849-1 none
Highest safety class achievable in safety mode: SIL acc. to IEC 61508 No
Use in hazardous areas: ATEX marking II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
Use in hazardous areas: ATEX certificate KEMA 04 ATEX 1244
Use in hazardous areas: IECEx IECEx KEM 05.0006
Use in hazardous areas: CCC Ex 2020322316002941
Use in hazardous areas: EAC Ex PB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC
Use in hazardous areas: FM marking Class I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G
Use in hazardous areas: Explosion protection category for gas ATEX gas explosion protection, Zone 1
Use in hazardous areas: Explosion protection category for dust ATEX dust explosion protection, Zone 21 always install in corresponding enclosure
Use in hazardous areas: associated equipment (Ex ia) Yes
Use in hazardous areas: associated equipment (Ex ib) Yes
Marine approval: Germanischer Lloyd (GL) Yes
Marine approval: American Bureau of Shipping (ABS) Yes
Marine approval: Bureau Veritas (BV) Yes
Marine approval: Det Norske Veritas (DNV) Yes

Connection method 1

Design of electrical connection Screw/spring-type terminal

Dimensions 3

Width 30 mm
Height 129 mm
Depth 136.5 mm

Weights 1

Weight, approx. 230 g

EClass 6 27-24-26-01 3

ETIM 10 EC001596
IDEA 4 3562
UNSPSC 15 32-15-17-05

Logistics 6

Net weight 0.341 kg
Country of origin DE
Shipping weight 0.841 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6ES7134-7TD00-0AB0

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • Germanischer Lloyd (GL)
  • American Bureau of Shipping (ABS)
  • Bureau Veritas (BV)
  • Det Norske Veritas (DNV)
Quick answers

Questions about the 4AI I 2WIRE HART

What is the HS code of 4AI I 2WIRE HART for customs?

The tariff (HS) code on file for 4AI I 2WIRE HART is 85389091.

What is the EAN of 4AI I 2WIRE HART?

The EAN (GTIN) of 4AI I 2WIRE HART is 4019169131667.

Where does 4AI I 2WIRE HART ship from, and how fast?

4AI I 2WIRE HART ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for PLC & controllers

All guides for PLC & controllers
Reviews

Customer reviews

Series

Siemens SIMATIC ET 200SP

Brand
Siemens
Series
SIMATIC ET 200SP
$734.85 On request
Get a Quote
Quote

Get a Quote

4AI I 2WIRE HART

Genuine parts

Genuine, factory-sealed parts

Siemens · 6ES7134-7TD00-0AB0

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart

View cart