The Siemens 6ES7134-7SD51-0AB0 is a SIMATIC ET200iSP intrinsically safe electronic module with 4 analog inputs for resistance thermometers, PT100 and NI100, plus direct resistance measurement up to 600 ohms. It offers 16-bit resolution, 0.1 percent basic error limit, and ATEX/IECEx Ex ib [ia Ga] IIC T4 Gb certification for Zone 1 gas and Zone 21 dust areas, with IP30 screw/spring-type terminal connections.
Supports 2-, 3-, and 4-wire RTD connections on the same channel, so lead-resistance compensation can be matched to the sensor cable run without swapping modules; a 4-wire connection cancels lead resistance entirely for the tightest accuracy, while 2-wire is adequate for short runs. Basic error limit is 0.1% at 25 degC but widens to 0.15% across the full operating temperature range, worth checking against the process tolerance before specifying. The 320 ms max cycle time across all 4 channels is a real-time budget item if the RTD readings feed a fast control loop rather than slow trend monitoring.
Sized for temperature measurement circuits in ATEX/IECEx Zone 1 gas or Zone 21 dust areas and marine/offshore hazardous locations, such as process vessel or pipeline RTD monitoring on ET200iSP stations, where the sensor wiring itself must remain intrinsically safe.
| Product type designation | 4AI RTD |
|---|---|
| HW functional status | 4 |
| Firmware version | V1.1.0 |
| Product function: Isochronous mode | No |
| Reparameterization possible in RUN | Yes |
|---|
| Rack mounting | No |
|---|---|
| Front mounting | Yes |
| Rail mounting | Yes |
| Wall mounting/direct mounting | No |
| Part number | 6ES7134-7SD51-0AB0 |
|---|---|
| Type designation | 4AI RTD |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4019169182294 |
| ETIM class | EC001596 |
| eCl@ss | 27242601 |
| Type of supply voltage | DC |
|---|---|
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Current consumption, typ. | 19 mA |
|---|---|
| from load voltage (power bus), max. | 22 mA |
| Power loss, typ. | 0.4 W |
|---|
| Fieldbus connection via separate transceiver | Yes |
|---|
| Number of analog inputs | 4 |
|---|---|
| Cycle time (all channels) max. | 320 ms; 66 ms basic conversion time x 4 channels with interference frequency suppression 60 Hz, 80 ms basic conversion time x 4 channels with interference frequency suppression 50 Hz |
| Technical unit for temperature measurement adjustable | Yes |
| Input ranges: Voltage | No |
| Input ranges: Current | No |
| Input ranges: Thermocouple | No |
| Input ranges: Resistance thermometer | Yes |
| Input ranges: Resistance | Yes |
| Input ranges (rated values), resistance thermometer: Ni 100 | Yes |
| Input ranges (rated values), resistance thermometer: Input resistance (Ni 100) | 2 000 kΩ |
| Input ranges (rated values), resistance thermometer: Pt 100 | Yes |
| Input ranges (rated values), resistors: 0 to 600 ohms | Yes; also 1 000 ohms |
| Input ranges (rated values), resistors: Input resistance (0 to 600 ohms) | 1 000 kΩ |
| Characteristic linearization: Parameterizable | Yes |
| Characteristic linearization: for resistance thermometer | Yes |
| Cable length: shielded, max. | 500 m |
| Measurement principle | integrating (Sigma-Delta) |
|---|---|
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 16 bit |
| Integration and conversion time/resolution per channel: Integration time, parameterizable | Yes |
| Integration and conversion time/resolution per channel: Basic conversion time, including integration time (ms) | 80 ms at 50 Hz; 66 ms at 60 Hz |
| Integration and conversion time/resolution per channel: additional conversion time for wire-break monitoring | 5 ms |
| Integration and conversion time/resolution per channel: Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
| Smoothing of measured values: parameterizable | Yes; in 4 stages |
| Smoothing of measured values: Step: None | Yes; 1x cycle time |
| Smoothing of measured values: Step: low | Yes; 4x cycle time |
| Smoothing of measured values: Step: Medium | Yes; 32x cycle time |
| Smoothing of measured values: Step: High | Yes; 64x cycle time |
| Connection of signal encoders: for resistance measurement with two-wire connection | Yes |
|---|
| Linearity error (relative to input range), (+/-) | 0.015 % |
|---|---|
| Temperature error (relative to input range), (+/-) | 0.02 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.01 % |
| Operational error limit in overall temperature range: Resistance thermometer, relative to input range, (+/-) | 0.15 %; Applies to resistances standard ±0.8 K, climatic ±0.3 K |
| Basic error limit (operational limit at 25 °C): Resistance thermometer, relative to input range, (+/-) | 0.1 %; Applies to resistances standard ±0.5 K, climatic ±0.2 K |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency: Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
| Number of PROFINET interfaces | 0 |
|---|
| Supports protocol for PROFINET IO | No |
|---|---|
| PROFIsafe | No |
| PROFIBUS | No |
| Further protocols: other bus systems | No |
| Alarms: Diagnostic alarm | Yes |
|---|---|
| Alarms: Limit value alarm | Yes |
| Diagnoses: Diagnostic information readable | Yes |
| Diagnoses: Wire break | Yes; R > 2 kOhm |
| Diagnoses: Short-circuit | Yes |
| Diagnoses: Group error | Yes |
| Diagnostics indication LED: Group error SF (red) | Yes |
| Module for Ex(i) protection | Yes; for more Co/Lo combinations, see certificate IECEx KEM 05.0009 |
|---|---|
| maximum values for connecting terminals for gas group IIC: Uo (no-load voltage), max. | 5.9 V |
| maximum values for connecting terminals for gas group IIC: Io (short-circuit current), max. | 24 mA |
| maximum values for connecting terminals for gas group IIC: Po (power output), max. | 36 mW |
| maximum values for connecting terminals for gas group IIC: Co (permissible external capacity), max. | 43 µF |
| maximum values for connecting terminals for gas group IIC: Lo (permissible external inductivity), max. | 50 mH |
| Potential separation analog inputs: between the channels | No |
|---|---|
| Potential separation analog inputs: between the channels and backplane bus | Yes |
| IP degree of protection | IP30 |
|---|
| CE mark | CE 0344 |
|---|---|
| UKCA mark | DEKRA 21UKEX0088 Importer UK: Siemens plc Manchester M20 2UR |
| cULus | LISTED E334384 |
| FM approval | CLASSIFIED 3025852 |
| Suitable for safety functions | No |
| INMETRO certificate | UL-BR 12.0069 |
| reference designation according to IEC 81346-2 (2009) | K |
| Highest safety class achievable in safety mode: acc. to EN 954 | n.a. |
| Highest safety class achievable in safety mode: Performance level according to ISO 13849-1 | none |
| Highest safety class achievable in safety mode: SIL acc. to IEC 61508 | No |
| Use in hazardous areas: ATEX marking | II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb |
| Use in hazardous areas: ATEX certificate | KEMA 04 ATEX 1247 |
| Use in hazardous areas: IECEx | IECEx KEM 05.0009 |
| Use in hazardous areas: CCC Ex | 2020322316002944 |
| Use in hazardous areas: EAC Ex | PB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC |
| Use in hazardous areas: FM marking | Class I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G |
| Use in hazardous areas: Explosion protection category for gas | ATEX gas explosion protection, Zone 1 |
| Use in hazardous areas: Explosion protection category for dust | ATEX dust explosion protection, Zone 21 always install in corresponding enclosure |
| Use in hazardous areas: associated equipment (Ex ia) | Yes |
| Use in hazardous areas: associated equipment (Ex ib) | Yes |
| Marine approval: Germanischer Lloyd (GL) | Yes |
| Marine approval: American Bureau of Shipping (ABS) | Yes |
| Marine approval: Bureau Veritas (BV) | Yes |
| Marine approval: Det Norske Veritas (DNV) | Yes |
| Design of electrical connection | Screw/spring-type terminal |
|---|
| Width | 30 mm |
|---|---|
| Height | 129 mm |
| Depth | 136.5 mm |
| Weight, approx. | 230 g |
|---|
| eClass | 16 27-24-26-01 |
|---|---|
| ETIM | 10 EC001596 |
| IDEA | 4 3562 |
| UNSPSC | 15 32-15-17-05 |
| Net weight | 0.302 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.802 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | Critical stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for 4AI RTD is 85389091.
The EAN (GTIN) of 4AI RTD is 4019169182294.
4AI RTD ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.