The Siemens 6ES7134-6TD00-0CA1 is a SIMATIC ET 200SP analog input module with 4 HART-capable channels for 2-wire 4-20 mA transmitters, delivering 15-bit-plus-sign resolution and channel-by-channel diagnostics. It mounts on BU type A0 or A1 base units, runs from a 24 V DC supply (19.2-28.8 V range), and supports reparameterization while the station is in RUN.
The HART channel support is the reason to pick this module over a standard ET 200SP AI 4xI without HART: it reads the superimposed HART signal from 2-wire loop-powered transmitters for diagnostics and remote configuration while still delivering the process value through the normal 4-20 mA path. Reparameterization in RUN means channel ranges and smoothing can be adjusted without pulling the station out of service, which matters when a HART transmitter needs to be recalibrated on a live line. The BU type A0/A1 requirement fixes the base unit choice at station design time, so confirm the BaseUnit slot before ordering.
Fits ET 200SP distributed I/O stations that read HART pressure, flow, level, or temperature transmitters and need channel diagnostics (wire break, short-circuit) reported back to the controller without separate HART multiplexer hardware.
| Product type designation | AI 4xI 2-wire HART |
|---|---|
| Firmware version | V1.0 |
| FW update possible | Yes |
| usable BaseUnits | BU type A0, A1 |
| Color code for module-specific color-coded label | CC03 |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V13 SP1 |
| Engineering with: STEP 7 configurable/integrated from version | V5.5 SP4 and higher |
| Engineering with: PCS 7 configurable/integrated from version | V8.1 SP1 |
| Engineering with: PROFIBUS from GSD version/GSD revision | GSD Revision 5 |
| Engineering with: PROFINET from GSD version/GSD revision | GSDML V2.3 |
| Operating mode: Oversampling | No |
| Operating mode: MSI | No |
| Reparameterization possible in RUN | Yes |
|---|---|
| Calibration possible in RUN | No |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Part number | 6ES7134-6TD00-0CA1 |
|---|---|
| Type designation | AI 4xI 2-wire HART |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623404972 |
| ETIM class | EC001596 |
| eCl@ss | 27242601 |
| Current consumption, max. | 25 mA; without sensor supply |
|---|
| 24 V encoder supply: 24 V | Yes |
|---|---|
| 24 V encoder supply: Short-circuit protection | Yes |
| 24 V encoder supply: Output current, max. | 20 mA; max. 50 mA per channel for a duration < 10 s |
| Power loss, typ. | 0.65 W; without sensor supply |
|---|
| Address space per module: Address space per module, max. | 8 byte; + 1 byte for QI information |
|---|---|
| Address space per module: Address space per module with HART, max. | 28 byte; + 1 byte for QI information |
| Automatic encoding | Yes |
|---|---|
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| Number of analog inputs | 4; Differential inputs |
|---|---|
| For current measurement | 4 |
| permissible input current for current input (destruction limit), max. | 50 mA |
| Input ranges (rated values), currents: 0 to 20 mA | No |
| Input ranges (rated values), currents: -20 mA to +20 mA | No |
| Input ranges (rated values), currents: 4 mA to 20 mA | Yes; 15 bit + sign |
| Input ranges (rated values), currents: Input resistance (4 mA to 20 mA) | 280 Ω; + approx. 0.35 V diode forward voltage |
| Cable length: shielded, max. | 800 m |
| Measurement principle | integrating (Sigma-Delta) |
|---|---|
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 16 bit |
| Integration and conversion time/resolution per channel: Integration time, parameterizable | Yes; channel by channel |
| Integration and conversion time/resolution per channel: Interference voltage suppression for interference frequency f1 in Hz | 10 / 50 / 60 Hz |
| Smoothing of measured values: Number of smoothing levels | 4; None; 4/8/16 times |
| Smoothing of measured values: parameterizable | Yes |
| Connection of signal encoders: for voltage measurement | No |
|---|---|
| Connection of signal encoders: for current measurement as 2-wire transducer | Yes |
| Linearity error (relative to input range), (+/-) | 0.01 % |
|---|---|
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, min. | 60 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
| Operational error limit in overall temperature range: Current, relative to input range, (+/-) | 0.5 % |
| Basic error limit (operational limit at 25 °C): Current, relative to input range, (+/-) | 0.3 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency: Series mode interference (peak value of interference < rated value of input range), min. | 60 dB |
| Diagnostics function | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes |
| Alarms: Limit value alarm | Yes |
| Diagnoses: Monitoring the supply voltage | Yes |
| Diagnoses: Wire break | Yes; channel by channel |
| Diagnoses: Short-circuit | Yes; Channel-by-channel, short-circuit of the encoder supply to ground or of an input to the encoder supply |
| Diagnoses: Group error | Yes |
| Diagnoses: Overflow/Underflow | Yes; channel by channel |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | Yes; red LED |
| Diagnostics indication LED: for module diagnostics | Yes; green/red DIAG LED |
| Potential separation channels: between the channels | No |
|---|---|
| Potential separation channels: between the channels and backplane bus | Yes |
| Potential separation channels: between the channels and the power supply of the electronics | No |
| Isolation tested with | 707 V DC (type test) |
|---|
| Ambient temperature during operation: horizontal installation, min. | -30 °C |
|---|---|
| Ambient temperature during operation: vertical installation, min. | -30 °C |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual |
| Width | 15 mm |
|---|---|
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 31 g |
|---|
| Net weight | 0.037 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.537 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of AI 4xI 2-wire HART is 24 V AC.
The tariff (HS) code on file for AI 4xI 2-wire HART is 85389091.
The EAN (GTIN) of AI 4xI 2-wire HART is 4047623404972.
AI 4xI 2-wire HART ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.