Siemens 6ES7134-6JD00-0DA1 is a SIMATIC ET 200SP analog input module with 4 thermocouple channels (AI 4xTC HS), 16-bit resolution, and channel-level diagnostics. It mounts on BaseUnit type A0 or A1 with color code CC00 and runs from a 24 V DC supply drawing 37 mA typical. The module supports temperature compensation with an internal reference channel and configurable measuring ranges down to plus/minus 50 mV.
The 4xTC HS variant targets fast, multi-type thermocouple measurement where standard ET 200SP AI modules are limited to fewer types or slower cycles: +/-0.01% linearity and a 5 ms minimum cycle time across all channels support tight temperature loops. Internal cold-junction compensation is available only with BaseUnit type A1 - use BU A0 if an external reference channel is acceptable, or A1 to avoid a separate cold-junction sensor. The 16-bit resolution with sign and 0.005%/K temperature error make this variant suitable where absolute accuracy across a wide ambient range matters more than channel count.
Verified AMS 2750 and CQI-9 declarations of conformity make this module applicable to heat-treat furnace temperature surveys and pyrometry systems that require traceable thermocouple accuracy. The 4-channel thermocouple input also fits general process temperature monitoring on ET 200SP stations - extruders, ovens, and thermal chambers - where channel diagnostics (wire-break, group error) are needed for unattended operation.
| Product type designation | AI 4xTC HS |
|---|---|
| HW functional status | FS22 or higher |
| Firmware version | V2.0.0 |
| FW update possible | Yes |
| usable BaseUnits | BU type A0, A1 |
| Color code for module-specific color-coded label | CC00 |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Measuring range scalable | Yes |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V21.1 or higher |
| Engineering with: STEP 7 configurable/integrated from version | configurable as of V5.7.3.3 with HSP0348 V3.0 / integrated as of V5.7.5.0 |
| Engineering with: PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| Engineering with: PROFINET from GSD version/GSD revision | GSDML V2.50 |
| Operating mode: Oversampling | No |
| Operating mode: MSI | Yes |
| Reparameterization possible in RUN | Yes |
|---|---|
| Calibration possible in RUN | Yes |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Part number | 6ES7134-6JD00-0DA1 |
|---|---|
| Type designation | AI 4xTC HS |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623410270 |
| ETIM class | EC001596 |
| eCl@ss | 27242601 |
| Current consumption (rated value) | 37 mA |
|---|---|
| Current consumption, max. | 50 mA |
| Power loss, typ. | 0.9 W |
|---|
| Address space per module: Address space per module, max. | 16 byte; + 1 byte for QI information |
|---|
| Automatic encoding | Yes |
|---|---|
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| Selection of BaseUnit for connection variants: 2-wire connection | BU type A0, A1 |
| Number of analog inputs | 4 |
|---|---|
| For voltage measurement | 4 |
| For thermocouple measurement | 4 |
| permissible input voltage for voltage input (destruction limit), max. | 30 V |
| Cycle time (all channels), min. | 5 ms; Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels) |
| Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
| Input ranges (rated values), voltages: -1 V to +1 V | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages: Input resistance (-1 V to +1 V) | 1 MΩ |
| Input ranges (rated values), voltages: -250 mV to +250 mV | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages: Input resistance (-250 mV to +250 mV) | 1 MΩ |
| Input ranges (rated values), voltages: -50 mV to +50 mV | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages: Input resistance (-50 mV to +50 mV) | 1 MΩ |
| Input ranges (rated values), voltages: -80 mV to +80 mV | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages: Input resistance (-80 mV to +80 mV) | 1 MΩ |
| Input ranges (rated values), thermocouples: type B | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Input resistance (Type B) | 1 MΩ |
| Input ranges (rated values), thermocouples: type C | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type E | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type J | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type K | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type L | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type N | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type R | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type S | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type T | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type U | Yes; 16 bit incl. sign |
| Input ranges (rated values), thermocouples: Type TXK/TXK(L) to GOST | Yes; 16 bit incl. sign |
| Thermocouple (TC) Temperature compensation: Parameterizable | Yes |
| Thermocouple (TC) Temperature compensation: Reference channel of the module | No |
| Thermocouple (TC) Temperature compensation: internal comparison point | Yes; with BaseUnit type A1 |
| Thermocouple (TC) Temperature compensation: Number of reference channel groups | 4; Group 0 to 3 |
| Thermocouple (TC) Temperature compensation: fixed reference temperature | Yes |
| Cable length: shielded, max. | 200 m; 100 m for thermocouples |
| Measurement principle | Sigma Delta |
|---|---|
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 16 bit |
| Integration and conversion time/resolution per channel: Integration time, parameterizable | Yes |
| Basic conversion time, including integration time (ms): additional processing time for wire-break check | 1 ms |
| Basic conversion time, including integration time (ms): Interference voltage suppression for interference frequency f1 in Hz | 16.6 / 50 / 60 Hz / off |
| Basic conversion time, including integration time (ms): Conversion time (per channel) | 180/60/50/1.25 ms |
| Smoothing of measured values: Number of smoothing levels | 4 |
| Smoothing of measured values: parameterizable | Yes |
| Smoothing of measured values: Step: None | Yes; 1x conversion time |
| Smoothing of measured values: Step: low | Yes; 4x conversion time |
| Smoothing of measured values: Step: Medium | Yes; 8x conversion time |
| Smoothing of measured values: Step: High | Yes; 16x conversion time |
| Connection of signal encoders: for voltage measurement | Yes |
|---|
| Linearity error (relative to input range), (+/-) | 0.01 % |
|---|---|
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, min. | -70 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.03 % |
| Operational error limit in overall temperature range: Voltage, relative to input range, (+/-) | 0.1 %; 0.3 % when SFU OFF |
| Basic error limit (operational limit at 25 °C): Voltage, relative to input range, (+/-) | 0.05 %; 0.2 % when SFU OFF |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency: Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
| Diagnostics function | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes |
| Alarms: Limit value alarm | Yes; two upper and two lower limit values in each case |
| Diagnoses: Monitoring the supply voltage | Yes |
| Diagnoses: Wire break | Yes; channel by channel |
| Diagnoses: Overflow/Underflow | Yes; channel by channel |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | Yes; red LED |
| Diagnostics indication LED: for module diagnostics | Yes; green/red LED |
| Potential separation channels: between the channels | No |
|---|---|
| Potential separation channels: between the channels and backplane bus | Yes |
| Potential separation channels: between the channels and the power supply of the electronics | Yes |
| between the inputs (UCM) | 60 Vpp |
|---|
| Isolation tested with | 707 V DC (type test) |
|---|
| Suitable for applications according to AMS 2750 | Yes; Declaration of Conformity, see online support entry 109757262 |
|---|---|
| Suitable for applications according to CQI-9 | Yes; Based on AMS 2750 E |
| Ecological footprint: environmental product declaration Global warming potential | Yes |
| Ecological footprint: global warming potential, (total) [CO2 eq] | 9.32 kg |
| Ecological footprint: global warming potential, (during production) [CO2 eq] | 4.97 kg |
| Ecological footprint: global warming potential, (during operation) [CO2 eq] | 4.79 kg |
| Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] | -0.449 kg |
| signed firmware update | Yes; firmware V2.0.0 or higher |
|---|
| Ambient temperature during operation: horizontal installation, min. | -30 °C; < 0 °C as of FS02 |
|---|---|
| Ambient temperature during operation: vertical installation, min. | -30 °C; < 0 °C as of FS02 |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Absolute humidity: dew point, min. | -60 °C; suitable for dry room applications |
| Width | 15 mm |
|---|---|
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 33 g |
|---|
| Net weight | 0.039 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.539 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of AI 4xTC HS is 24 V AC.
The tariff (HS) code on file for AI 4xTC HS is 85389091.
The EAN (GTIN) of AI 4xTC HS is 4047623410270.
AI 4xTC HS ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.