The Siemens 6ES7134-6HD01-0BA1 is a SIMATIC ET 200SP analog input module with 4 differential channels, each individually configurable for voltage or current measurement, resolving up to 16 bit including sign, fitted to BU type A0 or A1 with color code CC03.
Each of the 4 channels is independently parameterizable as a 0-10V, 1-5V, ±10V, or ±5V voltage input, or a 0-20mA/4-20mA current input on a 2-wire connection only - there is no 4-wire mode on this variant, so it fits transducers that provide their own loop supply. The ±0.3% basic error limit and CQI-9 suitability make this module a fit for heat-treat furnace pyrometry and temperature-uniformity survey instrumentation where that automotive heat-treatment standard is specified, not just general process feedback. The 4-level smoothing (none, 4x, 8x, or 16x the conversion time) lets a noisy 4-20mA loop be filtered in TIA Portal without adding external RC filtering.
Mixed voltage/current analog input for ET 200SP stations: process transmitter feedback (0-10V, 4-20mA) and, given CQI-9 suitability, furnace pyrometry and heat-treatment temperature-uniformity survey instrumentation.
| Product type designation | AI 4x U/I 2-wire ST |
|---|---|
| HW functional status | FS22 or higher |
| Firmware version | V3.0.0 |
| FW update possible | Yes |
| usable BaseUnits | BU type A0, A1 |
| Color code for module-specific color-coded label | CC03 |
| Product function: I&M data | Yes; I&M0 to I&M3 |
| Product function: Isochronous mode | No |
| Product function: Measuring range scalable | No |
| Engineering with: STEP 7 TIA Portal configurable/integrated from version | V21.1 or higher |
| Engineering with: STEP 7 configurable/integrated from version | configurable as of V5.7.3.3 with HSP0348 V3.0 / integrated as of V5.7.5.0 |
| Engineering with: PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| Engineering with: PROFINET from GSD version/GSD revision | GSDML V2.50 |
| Operating mode: Oversampling | No |
| Operating mode: MSI | No |
| Reparameterization possible in RUN | Yes |
|---|---|
| Calibration possible in RUN | No |
| Rated value (DC) | 24 V |
|---|---|
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Part number | 6ES7134-6HD01-0BA1 |
|---|---|
| Type designation | AI 4x U/I 2-wire ST |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047623409236 |
| ETIM class | EC001596 |
| eCl@ss | 27242601 |
| Current consumption (rated value) | 30 mA |
|---|---|
| Current consumption, max. | 117 mA |
| 24 V encoder supply: 24 V | Yes; For current measurement |
|---|---|
| 24 V encoder supply: Short-circuit protection | Yes |
| 24 V encoder supply: Output current, max. | 20 mA; max. 50 mA per channel for a duration < 10 s |
| Power loss, typ. | 0.85 W |
|---|
| Address space per module: Address space per module, max. | 8 byte; + 1 byte for QI information |
|---|
| Automatic encoding | Yes |
|---|---|
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| Selection of BaseUnit for connection variants: 2-wire connection | BU type A0, A1 |
| Number of analog inputs | 4; Differential inputs |
|---|---|
| For current measurement | 4 |
| For voltage measurement | 4 |
| permissible input voltage for voltage input (destruction limit), max. | 30 V |
| permissible input current for current input (destruction limit), max. | 50 mA |
| Cycle time (all channels), min. | Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels) |
| Input ranges (rated values), voltages: 0 to +10 V | Yes; 15 bit |
| Input ranges (rated values), voltages: Input resistance (0 to 10 V) | 120 kΩ |
| Input ranges (rated values), voltages: 1 V to 5 V | Yes; 15 bit |
| Input ranges (rated values), voltages: Input resistance (1 V to 5 V) | 120 kΩ |
| Input ranges (rated values), voltages: -10 V to +10 V | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages: Input resistance (-10 V to +10 V) | 120 kΩ |
| Input ranges (rated values), voltages: -5 V to +5 V | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages: Input resistance (-5 V to +5 V) | 120 kΩ |
| Input ranges (rated values), currents: 0 to 20 mA | Yes; 15 bit |
| Input ranges (rated values), currents: Input resistance (0 to 20 mA) | 100 Ω; + approx. 0.7 V diode forward voltage |
| Input ranges (rated values), currents: 4 mA to 20 mA | Yes; 15 bit |
| Input ranges (rated values), currents: Input resistance (4 mA to 20 mA) | 100 Ω; + approx. 0.7 V diode forward voltage |
| Cable length: shielded, max. | 1 000 m; 200 m for voltage measurement |
| Measurement principle | Sigma Delta |
|---|---|
| Integration and conversion time/resolution per channel: Resolution with overrange (bit including sign), max. | 16 bit |
| Integration and conversion time/resolution per channel: Integration time, parameterizable | Yes |
| Integration and conversion time/resolution per channel: Interference voltage suppression for interference frequency f1 in Hz | 16.6 / 50 / 60 Hz |
| Integration and conversion time/resolution per channel: Conversion time (per channel) | 180 / 60 / 50 ms |
| Smoothing of measured values: Number of smoothing levels | 4 |
| Smoothing of measured values: parameterizable | Yes |
| Smoothing of measured values: Step: None | Yes; 1x conversion time |
| Smoothing of measured values: Step: low | Yes; 4x conversion time |
| Smoothing of measured values: Step: Medium | Yes; 8x conversion time |
| Smoothing of measured values: Step: High | Yes; 16x conversion time |
| Connection of signal encoders: for voltage measurement | Yes |
|---|---|
| Connection of signal encoders: for current measurement as 2-wire transducer | Yes |
| Connection of signal encoders: Burden of 2-wire transmitter, max. | 650 Ω |
| Linearity error (relative to input range), (+/-) | 0.01 % |
|---|---|
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
| Operational error limit in overall temperature range: Voltage, relative to input range, (+/-) | 0.5 % |
| Operational error limit in overall temperature range: Current, relative to input range, (+/-) | 0.5 % |
| Basic error limit (operational limit at 25 °C): Voltage, relative to input range, (+/-) | 0.3 % |
| Basic error limit (operational limit at 25 °C): Current, relative to input range, (+/-) | 0.3 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency: Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
| Diagnostics function | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes |
| Alarms: Limit value alarm | No |
| Diagnoses: Monitoring the supply voltage | Yes |
| Diagnoses: Wire break | Yes; at 4 to 20 mA |
| Diagnoses: Short-circuit | Yes; with 1 to 5 V or 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply |
| Diagnoses: Overflow/Underflow | Yes |
| Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Diagnostics indication LED: Channel status display | Yes; green LED |
| Diagnostics indication LED: for channel diagnostics | No |
| Diagnostics indication LED: for module diagnostics | Yes; green/red LED |
| Potential separation channels: between the channels | Yes; channel group-specific between 2-wire current input group and voltage input group |
|---|---|
| Potential separation channels: between the channels and backplane bus | Yes |
| Potential separation channels: between the channels and the power supply of the electronics | Yes; only for voltage inputs |
| between the inputs (UCM) | 10 Vpp |
|---|
| Isolation tested with | 707 V DC (type test) |
|---|
| Ecological footprint: environmental product declaration Global warming potential | Yes |
|---|---|
| Ecological footprint: global warming potential, (total) [CO2 eq] | 9.32 kg |
| Ecological footprint: global warming potential, (during production) [CO2 eq] | 4.97 kg |
| Ecological footprint: global warming potential, (during operation) [CO2 eq] | 4.79 kg |
| Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] | -0.449 kg |
| signed firmware update | Yes; firmware V3.0.0 or higher |
|---|
| Ambient temperature during operation: horizontal installation, min. | -30 °C; < 0 °C as of FS02 |
|---|---|
| Ambient temperature during operation: vertical installation, min. | -30 °C; < 0 °C as of FS02 |
| Altitude during operation relating to sea level: Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| eClass | 16 27-24-26-01 |
|---|---|
| ETIM | 10 EC001596 |
| IDEA | 4 3562 |
| UNSPSC | 15 32-15-17-05 |
| Net weight | 0.039 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.539 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of AI 4x U/I 2-wire ST is 24 V DC.
The tariff (HS) code on file for AI 4x U/I 2-wire ST is 85389091.
The EAN (GTIN) of AI 4x U/I 2-wire ST is 4047623409236.
AI 4x U/I 2-wire ST ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.