The Siemens 6ES7132-7RD11-0AB0 is a SIMATIC ET 200iSP electronic module with 4 intrinsically safe digital outputs rated 17.4 V DC at 27 mA, built for Ex ib (ia Ga) IIC T4 Gb gas zones and Ex ib [ia IIIC Da] IIC T4 Gb dust zones with an H-shutdown input circuit. It mounts on the ET200iSP rail with screw or spring terminals and IP30 protection.
Electrically this module matches the L-shutdown 17.4 V/27 mA variant point for point - same Uao, Ri, and Uo/Io/Po loop values - and differs only in carrying the H-shutdown input circuit instead of L. Choose between the two strictly by which shutdown-circuit threshold the safety loop documentation calls for; the output-side wiring and Ex loop calculations are identical either way. The two-output parallel-switching option for uprating still applies.
| Product type designation | 4DQ 17.4 V DC/27 mA |
|---|---|
| HW functional status | 7 |
| Firmware version | V3.0.0 |
| Rack mounting | No |
|---|---|
| Front mounting | Yes |
| Rail mounting | Yes |
| Wall mounting/direct mounting | No |
| Type of supply voltage | DC |
|---|
| Part number | 6ES7132-7RD11-0AB0 |
|---|---|
| Type designation | 4DQ 17.4 V DC/27 mA |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4019169150217 |
| ETIM class | EC001599 |
| eCl@ss | 27242604 |
| Current consumption, typ. | 260 mA |
|---|---|
| from load voltage (power bus), max. | 300 mA |
| Power loss, typ. | 2.1 W |
|---|
| Address space per module: Address space per module, max. | 2 byte |
|---|
| Fieldbus connection via separate transceiver | Yes |
|---|
| Type of digital output | Transistor |
|---|---|
| Number of digital outputs | 4; additionally 1 intrinsically-safe input for H shutdown |
| Short-circuit protection | Yes |
| No-load voltage Uao (DC) | 17.4 V |
| Internal resistor Ri | 150 Ω |
| Trend key points E: Voltage Ue (DC) | 13.3 V |
| Trend key points E: Current Ie | 27 mA |
| Output voltage: Type of output voltage | DC |
| Output current: for signal "1" rated value | 0.027 A |
| Output delay with resistive load: "0" to "1", max. | 2 ms |
| Output delay with resistive load: "1" to "0", max. | 1.5 ms |
| Parallel switching of two outputs: for uprating | Yes |
| Switching frequency: with resistive load, max. | 100 Hz |
| Switching frequency: with inductive load, max. | 2 Hz |
| Cable length: shielded, max. | 500 m |
| Cable length: unshielded, max. | 500 m |
| Number of PROFINET interfaces | 0 |
|---|---|
| Number of RS 485 interfaces | 0 |
| Supports protocol for PROFINET IO | No |
|---|---|
| PROFIsafe | No |
| PROFIBUS | No |
| Diagnostics function | Yes |
|---|---|
| Alarms: Diagnostic alarm | Yes; Parameterizable |
| Alarms: Hardware interrupt | No |
| Diagnoses: Diagnostic information readable | Yes |
| Diagnoses: Wire break | Yes |
| Diagnoses: Short-circuit | Yes |
| Diagnostics indication LED: Group error SF (red) | Yes |
| Diagnostics indication LED: Status indicator digital output (green) | Yes |
| Module for Ex(i) protection | Yes; for more Co/Lo combinations, see certificate IECEx KEM 05.0011 |
|---|---|
| maximum values for connecting terminals for gas group IIC: Uo (no-load voltage), max. | 19.4 V |
| maximum values for connecting terminals for gas group IIC: Io (short-circuit current), max. | 132 mA |
| maximum values for connecting terminals for gas group IIC: Po (power output), max. | 0.64 W |
| maximum values for connecting terminals for gas group IIC: Co (permissible external capacity), max. | 0.23 µF |
| maximum values for connecting terminals for gas group IIC: Lo (permissible external inductivity), max. | 1.9 mH |
| maximum values for connecting terminals for gas group IIC: Ui (intrinsically safe input voltage), max. | 28 V; switch input circuit |
| maximum values for connecting terminals for gas group IIC: Pi (intrinsically safe input power), max. | 1.2 W; switch input circuit |
| maximum values for connecting terminals for gas group IIC: Ci (internal capacity), max. | 3 nF; switch input circuit |
| Potential separation digital outputs: between the channels | No |
|---|---|
| Potential separation digital outputs: between the channels and backplane bus | Yes |
| IP degree of protection | IP30 |
|---|
| CE mark | CE 0344 |
|---|---|
| UKCA mark | DEKRA 21UKEX0085 Importer UK: Siemens plc Manchester M20 2UR |
| cULus | LISTED E334384 |
| FM approval | CLASSIFIED 3025852 |
| Suitable for safety functions | No |
| INMETRO certificate | UL-BR 12.0073 |
| reference designation according to IEC 81346-2 (2009) | K |
| Use in hazardous areas: ATEX marking | II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb |
| Use in hazardous areas: ATEX certificate | KEMA 04 ATEX 1249 |
| Use in hazardous areas: IECEx | IECEx KEM 05.0011 |
| Use in hazardous areas: CCC Ex | 2020322316002945 |
| Use in hazardous areas: EAC Ex | PB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC |
| Use in hazardous areas: FM marking | Class I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G |
| Use in hazardous areas: Explosion protection category for gas | ATEX gas explosion protection, Zone 1 |
| Use in hazardous areas: Explosion protection category for dust | ATEX dust explosion protection, Zone 21 always install in corresponding enclosure |
| Use in hazardous areas: associated equipment (Ex ia) | Yes |
| Use in hazardous areas: associated equipment (Ex ib) | Yes |
| Marine approval: Germanischer Lloyd (GL) | Yes |
| Marine approval: American Bureau of Shipping (ABS) | Yes |
| Marine approval: Bureau Veritas (BV) | Yes |
| Marine approval: Det Norske Veritas (DNV) | Yes |
| Design of electrical connection | Screw/spring-type terminal |
|---|
| Width | 30 mm |
|---|---|
| Height | 129 mm |
| Depth | 136.5 mm |
| Weight, approx. | 255 g |
|---|
| Net weight | 0.341 kg |
|---|---|
| Country of origin | DE |
| Shipping weight | 0.841 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 4DQ 17.4 V DC/27 mA is 0.027 A.
The tariff (HS) code on file for 4DQ 17.4 V DC/27 mA is 85389091.
The EAN (GTIN) of 4DQ 17.4 V DC/27 mA is 4019169150217.
4DQ 17.4 V DC/27 mA ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.