Part number
6ES7132-6MD00-0BB1
Model no
RQ 4x120 V DC ... 230 V AC/5 A NO MA ST
$171.81 On request Dispatch — · From TürkiyeGet a Quote
SIMATIC ET 200SP

Siemens 6ES7132-6MD00-0BB1 SIMATIC ET 200SP RQ NO-MA 4x120VDC-230VAC/5A ST Module

SIMATIC ET 200SP relay module, 4x NO with manual operation, 5A, 24-120VDC/24-230VAC.

Rated current
5 A
Rated operational voltage
24–230 V AC
Communication
PROFINET, PROFIBUS (via GSD)
EAN
4047623406624
Description

About the RQ 4x120 V DC ... 230 V AC/5 A NO MA ST

The Siemens 6ES7132-6MD00-0BB1 is a SIMATIC ET 200SP relay module with 4 normally-open outputs rated 5 A at 24-120 V DC or 24-230 V AC, fitted with a manual operation feature for each channel. It runs on 24 V DC, mounts on BU type B0 or B1, and is rated for 7,000,000 operating cycles per relay.

Selection Notes

The manual-operation feature on each of the 4 normally-open contacts lets a technician force a channel during commissioning or maintenance without touching the PLC program, which is the main reason to choose this variant over a plain relay output module. Its 7,000,000 operating-cycle rating is well above the isolated CO relay module's 1,000,000 cycles, so it suits circuits with more frequent switching. Protect each output with the specified 6 A quick-response fuse before commissioning.

Specification

Full specification

102 values · Last verified 01 Nov 2026

General information 16

Product type designation RQ 4x120 V DC ... 230 V AC/5 A NO MA ST
HW functional status From FS03
Firmware version: FW update possible Yes
usable BaseUnits BU type B0, B1
Color code for module-specific color-coded label CC40
Product function: I&M data Yes; I&M0 to I&M3
Product function: Isochronous mode No
Engineering with: STEP 7 TIA Portal configurable/integrated from version V13 SP1
Engineering with: STEP 7 configurable/integrated from version V5.5 SP3 / -
Engineering with: PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
Engineering with: PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode: DQ Yes
Operating mode: DQ with energy-saving function No
Operating mode: PWM No
Operating mode: Oversampling No
Operating mode: MSO No

Supply voltage 4

Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes

Input current 1

Current consumption, max. 100 mA; without load
Show all 102 specifications ↓ Show less ↑81 more values in Identification, Power loss, Address area, Hardware configuration, Digital outputs, Interrupts/diagnostics/status information, Potential separation, Permissible potential difference, Isolation, Standards, approvals, certificates, Ambient conditions, Dimensions, Weights, Logistics.

Identification 10

Part number 6ES7132-6MD00-0BB1
Type designation RQ 4x120 V DC ... 230 V AC/5 A NO MA ST
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4047623406624
ETIM class EC001599
eCl@ss 27242604

Power loss 1

Power loss, typ. 1.5 W

Address area 2

Address space per module: Inputs 1 byte; + 1 byte for QI information
Address space per module: Outputs 1 byte

Hardware configuration 5

Automatic encoding Yes
Mechanical coding element Yes
Type of mechanical coding element type C
Selection of BaseUnit for connection variants: 2-wire connection BU type B1
Selection of BaseUnit for connection variants: 3-wire connection BU type B0

Digital outputs 25

Type of digital output Relays
Number of digital outputs 4
Current-sinking Yes
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection No
Switching frequency: with resistive load, max. 2 Hz
Switching frequency: with inductive load (acc. to IEC 60947-5-1, DC13), max. 0.5 Hz; provide one freewheeling diode for switching frequencies higher than 0.1 Hz
Switching frequency: on lamp load, max. 2 Hz
Total current of the outputs: Current per channel, max. 5 A
Total current of the outputs: Current per module, max. 20 A
Total current of the outputs (per module) horizontal installation: up to 50 °C, max. 20 A
Relay outputs: Number of relay outputs 4
Relay outputs: Rated supply voltage of relay coil L+ (DC) 24 V
Relay outputs: Current consumption of relays (coil current of all relays), max. 40 mA
Relay outputs: external protection for relay outputs Yes, with miniature fuse max. 6 A tripping current and quick-response tripping characteristic
Relay outputs: Number of operating cycles, max. Switching capacity of contacts 7 000 000; see additional description in the manual
Relay outputs: with inductive load, max. 2 A; see additional description in the manual
Relay outputs: with resistive load, max. 5 A; see additional description in the manual
Relay outputs: Thermal continuous current, max. 5 A
Relay outputs: Switching current, min. 100 mA; 5 V DC
Relay outputs: Rated switching voltage (DC) 24 V DC to 120 V DC
Relay outputs: Rated switching voltage (AC) 24V AC to 230V AC
Cable length: shielded, max. 1 000 m
Cable length: unshielded, max. 200 m

Interrupts/diagnostics/status information 11

Diagnostics function Yes
Substitute values connectable Yes
Alarms: Diagnostic alarm Yes
Diagnoses: Monitoring the supply voltage Yes
Diagnoses: Wire break No
Diagnoses: Short-circuit No
Diagnoses: Group error Yes
Diagnostics indication LED: Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
Diagnostics indication LED: Channel status display Yes; green LED
Diagnostics indication LED: for channel diagnostics No
Diagnostics indication LED: for module diagnostics Yes; green/red DIAG LED

Potential separation 3

Potential separation channels: between the channels Yes
Potential separation channels: between the channels and backplane bus Yes
Potential separation channels: between the channels and the power supply of the electronics Yes

Permissible potential difference 1

between channels and backplane bus/supply voltage 240 V AC

Isolation 3

Isolation tested with tested with 2 500 V DC (type test)
between channels and backplane bus/supply voltage 2 500 V DC
between backplane bus and supply voltage 707 V DC (type test)

Standards, approvals, certificates 6

Suitable for safety functions No
Ecological footprint: environmental product declaration Global warming potential Yes
Ecological footprint: global warming potential, (total) [CO2 eq] 25.5 kg
Ecological footprint: global warming potential, (during production) [CO2 eq] 3.54 kg
Ecological footprint: global warming potential, (during operation) [CO2 eq] 22.1 kg
Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] -0.137 kg

Ambient conditions 4

Ambient temperature during operation: horizontal installation, min. -30 °C
Ambient temperature during operation: vertical installation, min. -30 °C
Altitude during operation relating to sea level: Installation altitude above sea level, max. 2 000 m; On request: Installation altitudes greater than 2 000 m
Absolute humidity: dew point, min. -60 °C; suitable for dry room applications

Dimensions 3

Width 20 mm
Height 73 mm
Depth 58 mm

Weights 1

Weight, approx. 45 g

Logistics 6

Net weight 0.054 kg
Country of origin DE
Shipping weight 0.554 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6ES7132-6MD00-0BB1

No documents are on file for this part yet.

Ask us for the datasheet
Quick answers

Questions about the RQ 4x120 V DC ... 230 V AC/5 A NO MA ST

What is the rated current of RQ 4x120 V DC ... 230 V AC/5 A NO MA ST?

The rated current of RQ 4x120 V DC ... 230 V AC/5 A NO MA ST is 5 A.

Which supply voltage is RQ 4x120 V DC ... 230 V AC/5 A NO MA ST rated for?

The rated operational voltage of RQ 4x120 V DC ... 230 V AC/5 A NO MA ST is 24–230 V AC.

What is the HS code of RQ 4x120 V DC ... 230 V AC/5 A NO MA ST for customs?

The tariff (HS) code on file for RQ 4x120 V DC ... 230 V AC/5 A NO MA ST is 85389091.

What is the EAN of RQ 4x120 V DC ... 230 V AC/5 A NO MA ST?

The EAN (GTIN) of RQ 4x120 V DC ... 230 V AC/5 A NO MA ST is 4047623406624.

Where does RQ 4x120 V DC ... 230 V AC/5 A NO MA ST ship from, and how fast?

RQ 4x120 V DC ... 230 V AC/5 A NO MA ST ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for PLC & controllers

All guides for PLC & controllers
Reviews

Customer reviews

Series

Siemens SIMATIC ET 200SP

Brand
Siemens
Series
SIMATIC ET 200SP
$171.81 On request
Get a Quote
Quote

Get a Quote

RQ 4x120 V DC ... 230 V AC/5 A NO MA ST

Genuine parts

Genuine, factory-sealed parts

Siemens · 6ES7132-6MD00-0BB1

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart