How to Select an Interface Relay for PLC Outputs
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
The Siemens 6ED1055-1NB10-0BA2 is a LOGO! 8 DM16 24R expansion module adding 8 digital inputs and 8 relay outputs to a LOGO! base unit, rated 24V DC in and 5A per relay output. It mounts on a 35mm DIN rail, occupies 4 module-width spacing units, and switches loads up to 1000W lamp or 3A inductive per contact.
The 5A relay-rated outputs on this DM16 24R handle direct contactor coils and small motor loads that a transistor-output expansion module couldn't switch without an interposing relay — pick the transistor variant instead where fast, high-cycle switching matters more than raw current capacity. Occupying 4 spacing units for 8DI/8DO, it adds a full input-and-output block in one slot on the DIN rail rather than splitting inputs and outputs across two smaller modules.
Expands a LOGO! 8 base unit's I/O count for small automation tasks — building services, pump/lighting control, and simple machine interlocks needing relay-switched outputs on 24V DC.
| Mounting | on 35 mm DIN rail, 4 spacing units wide |
|---|
| Rated value (DC): 24 V DC | Yes |
|---|---|
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Rated value (AC): 24 V AC | No |
| Number of digital inputs | 8 |
|---|---|
| Input voltage: Type of input voltage | DC |
| Input voltage: for signal "0" | < 5 V DC |
| Input voltage: for signal "1" | > 12 V DC |
| Input current: for signal "0", max. (permissible quiescent current) | 0.85 mA |
| Input current: for signal "1", typ. | 2 mA |
| Input delay (for rated value of input voltage) for standard inputs: at "0" to "1", max. | 1.5 ms |
| Part number | 6ED1055-1NB10-0BA2 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4034106029500 |
| ETIM class | EC001419 |
| eCl@ss | 27242204 |
| Number of digital outputs | 8; Relays |
|---|---|
| Short-circuit protection | No |
| Controlling a digital input | Yes |
| Switching capacity of the outputs: on lamp load, max. | 1 000 W |
| Output current: for signal "1" rated value | 5 A |
| Output current: for signal "1" minimum load current | 100 mA |
| Parallel switching of two outputs: for uprating | No |
| Switching frequency: with resistive load, max. | 2 Hz |
| Switching frequency: with inductive load, max. | 0.5 Hz |
| Switching frequency: mechanical, max. | 10 Hz |
| Relay outputs Switching capacity of contacts: with inductive load, max. | 3 A |
| Relay outputs Switching capacity of contacts: with resistive load, max. | 5 A |
| Emission of radio interference acc. to EN 55 011: Limit class B, for use in residential areas | Yes |
|---|
| IP degree of protection | IP20 |
|---|
| CE mark | Yes |
|---|---|
| CSA approval | Yes |
| UL approval | Yes |
| FM approval | Yes |
| developed in accordance with IEC 61131 | Yes |
| according to VDE 0631 | Yes |
| Marine approval | Yes |
| Ecological footprint: environmental product declaration Global warming potential | Yes |
| Ecological footprint: global warming potential, (total) [CO2 eq] | 59.1 kg |
| Ecological footprint: global warming potential, (during production) [CO2 eq] | 5.82 kg |
| Ecological footprint: global warming potential, (during operation) [CO2 eq] | 53.6 kg |
| Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] | -0.373 kg |
| Ambient temperature during operation: min. | -20 °C; No condensation |
|---|---|
| Ambient temperature during operation: max. | 55 °C |
| Width | 71.5 mm |
|---|---|
| Height | 90 mm |
| Depth | 58 mm |
| Miscellaneous Manufacturer Declara-General Product Approval | tion |
|---|
| Net weight | 0.29 kg |
|---|---|
| Country of origin | CN |
| Shipping weight | 0.79 kg |
| Ships from | Türkiye |
| Dispatch | 13 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 6ED1055-1NB10-0BA2 is 5 A.
The rated operational voltage of 6ED1055-1NB10-0BA2 is 24 V AC.
The tariff (HS) code on file for 6ED1055-1NB10-0BA2 is 85389091.
The EAN (GTIN) of 6ED1055-1NB10-0BA2 is 4034106029500.
6ED1055-1NB10-0BA2 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
Compare the 5 main PLC types, IEC 61131-3 languages, scan-time sizing, and brand options to choose the right controller for your plant. Shop at...
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.