How to Select an Interface Relay for PLC Outputs
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
The Siemens 6ED1052-1MD08-0BA2 is a LOGO! 12/24RCE logic module with 8 digital inputs (4 usable as 0-10 V analog), 4 relay outputs rated 10 A, and a built-in Ethernet port with web server. It runs 400 function blocks, supports MQTT cloud connectivity, and accepts 12 V or 24 V DC supply.
This is the display, Ethernet, and relay-output (RCE) variant with 12/24 V DC supply; pick a transistor-output variant instead of this relay version when the load needs faster switching rather than the 10 A resistive / 3 A inductive contact rating this model provides. The built-in Ethernet port with web server and MQTT support lets it push data to a cloud or SCADA system without an added communication module, relevant when 400 function blocks covers the logic complexity and a full PLC would be oversized for the task.
Small standalone machine control, building or utility automation, and remote monitoring panels that need local relay switching plus cloud connectivity.
| with display | Yes |
|---|
| Mounting | on 35 mm DIN rail, 4 spacing units wide |
|---|
| Rated value (DC): 12 V DC | Yes |
|---|---|
| Rated value (DC): 24 V DC | Yes |
| permissible range, lower limit (DC) | 10.8 V |
| permissible range, upper limit (DC) | 28.8 V |
| Part number | 6ED1052-1MD08-0BA2 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4034106034474 |
| ETIM class | EC001417 |
| eCl@ss | 27242216 |
| Time switching clocks: Number | 400; Max. 400, function-specific |
|---|---|
| Time switching clocks: Power reserve | 480 h |
| Number of digital inputs | 8; Of which 4 can be used in analog mode (0 to 10 V) |
|---|
| Number of digital outputs | 4; Relays |
|---|---|
| Short-circuit protection | No; external fusing necessary |
| Output current: for signal "1" permissible range for 0 to 55 °C, max. | 10 A |
| Relay outputs Switching capacity of contacts: with inductive load, max. | 3 A |
| Relay outputs Switching capacity of contacts: with resistive load, max. | 10 A |
| Emission of radio interference acc. to EN 55 011: Limit class B, for use in residential areas | Yes; Radio interference suppression according to EN55011, Limit Value Class B |
|---|
| Siemens Eco Profile (SEP) | Siemens EcoTech |
|---|---|
| CE mark | Yes |
| CSA approval | Yes; covered by UL cert |
| UL approval | Yes |
| FM approval | Yes |
| developed in accordance with IEC 61131 | Yes |
| according to VDE 0631 | Yes |
| Marine approval | Yes |
| Ecological footprint: environmental product declaration Global warming potential | Yes |
| Ecological footprint: global warming potential, (total) [CO2 eq] | 51.5 kg |
| Ecological footprint: global warming potential, (during production) [CO2 eq] | 9.64 kg |
| Ecological footprint: global warming potential, (during operation) [CO2 eq] | 42.1 kg |
| Ecological footprint: global warming potential, (after end of life cycle) [CO2 eq] | -0.364 kg |
| Ambient temperature during operation: min. | -20 °C; No condensation |
|---|---|
| Ambient temperature during operation: max. | 55 °C |
| Ambient temperature during storage/transportation: min. | -40 °C |
| Ambient temperature during storage/transportation: max. | 70 °C |
| Altitude during operation relating to sea level: Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
| Width | 71.5 mm; 4 modular widths (MW) |
|---|---|
| Height | 90 mm |
| Depth | 60 mm |
| Net weight | 0.269 kg |
|---|---|
| Country of origin | CN |
| Shipping weight | 0.769 kg |
| Ships from | Türkiye |
| Dispatch | 13 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 6ED1052-1MD08-0BA2 is 10 A.
The rated operational voltage of 6ED1052-1MD08-0BA2 is 12–24 V DC.
The tariff (HS) code on file for 6ED1052-1MD08-0BA2 is 85371091.
The EAN (GTIN) of 6ED1052-1MD08-0BA2 is 4034106034474.
6ED1052-1MD08-0BA2 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
A step-by-step guide to matching PLC output type, coil voltage and current, contact rating, and socket style when selecting an interface relay.
Compare the 5 main PLC types, IEC 61131-3 languages, scan-time sizing, and brand options to choose the right controller for your plant. Shop at...
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.