Contactors for Data Center PDU and UPS Systems: Selection Guide
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
TeSys Deca 3P contactor, 65 A AC-3 (30 kW at 400 V), 120 V AC 60 Hz coil, 1NO+1NC, EverLink BTR power terminals.
The Schneider Electric LC1D65AG7 is a TeSys Deca 3-pole contactor rated 65 A in AC-3 at up to 440 V, which corresponds to 30 kW at 380/400 V. It has three normally open power poles, a 120 V AC 60 Hz coil and a built-in 1NO+1NC auxiliary block with a mirror-certified NC contact. Power connection uses EverLink BTR screw connectors, and the 55 mm wide body mounts on DIN rail or plate.
The 120 V AC 60 Hz coil suits North American 120 V control circuits, so no control transformer is needed when the panel control supply is already 120 V. The key rating is 65 A AC-3 at up to 440 V (30 kW at 400 V); the 80 A figure applies only to resistive AC-1 loads and should not be used for motor sizing. The coil has no built-in suppressor module, so surge suppression has to be added externally where the control circuit requires it. Lower and higher motor ratings and other coil voltages exist in the same LC1D family, so the contactor can be matched to the motor current of each feeder.
| Range | TeSys, TeSys Deca |
|---|---|
| Range of Product | TeSys Deca Advanced |
| Product or Component Type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control, Resistive load |
| Utilisation category | AC-3, AC-3e, AC-1, AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz, Power circuit <= 300 V DC |
| [Ie] rated operational current | 80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit, 65 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit, 65 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit |
| [Uc] control circuit voltage | 120 V AC 60 Hz |
| Motor power kW | 18.5 kW at 220/230 V AC 50/60 Hz (AC-3), 30 kW at 380/400 V AC 50/60 Hz (AC-3), 37 kW at 500 V AC 50/60 Hz (AC-3), 37 kW at 660/690 V AC 50/60 Hz (AC-3), 18.5 kW at 220/230 V AC 50/60 Hz (AC-3e), 30 kW at 380/400 V AC 50/60 Hz (AC-3e), 37 kW at 500 V AC 50/60 Hz (AC-3e), 37 kW at 660/690 V AC 50/60 Hz (AC-3e), 11 kW at 400 V AC 50/60 Hz (AC-4) |
|---|---|
| Maximum Horse Power Rating | 40 hp at 460/480 V AC 50/60 Hz for 3 phase motors, 5 hp at 115 V AC 50/60 Hz for 1 phase motors, 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors, 20 hp at 200/208 V AC 50/60 Hz for 3 phase motors, 20 hp at 230/240 V AC 50/60 Hz for 3 phase motors, 50 hp at 575/600 V AC 50/60 Hz for 3 phase motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) for signalling circuit, 80 A (at 140 °F (60 °C)) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 640 A 104 °F (40 °C) - 10 s for power circuit, 900 A 104 °F (40 °C) - 1 s for power circuit, 110 A 104 °F (40 °C) - 10 min for power circuit, 260 A 104 °F (40 °C) - 1 min for power circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1, 125 A gG at <= 690 V coordination type 1 for power circuit, 125 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 1.5 mOhm - Ith 80 A 50 Hz for power circuit |
| Power dissipation per pole | 9.6 W AC-1, 6.3 W AC-3, 6.3 W AC-3e |
| [Ui] rated insulation voltage | Power circuit 600 V CSA, Power circuit 600 V UL, Signalling circuit 690 V IEC 60947-1, Signalling circuit 600 V CSA, Signalling circuit 600 V UL, Power circuit 690 V IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 6 Mcycles |
| Electrical durability | 1.4 Mcycles 80 A AC-1 <= 440 V, 1.45 Mcycles 65 A AC-3 <= 440 V, 1.45 Mcycles 65 A AC-3e <= 440 V |
| Control circuit type | AC 60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 60 Hz, 0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 60 Hz, 1...1.1 Uc (140…158 °F (60…70 °C)):operational AC 60 Hz |
| Inrush power in VA | 140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) |
| Hold-in power consumption in VA | 13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| Heat dissipation | 4…5 W at 60 Hz |
| Operating time | 4...19 ms opening, 12...26 ms closing |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end, Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end, Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end, Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end, Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end, Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end, Power circuit: screw clamp terminals 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible without cable end, Power circuit: screw clamp terminals 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible without cable end, Power circuit: screw clamp terminals 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible with cable end, Power circuit: screw clamp terminals 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible with cable end, Power circuit: screw clamp terminals 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end, Power circuit: screw clamp terminals 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: solid without cable end |
| Tightening torque | Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors flat Ø 6 mm, Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors Philips No 2, Power circuit 70.8 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagonal 0.2 in (4 mm), Power circuit 44.3 lbf.in (5 N.m) EverLink BTR screw connectors 0.002…0.04 in² (1…25 mm²) hexagonal 0.2 in (4 mm), Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors pozidriv No 2, Power circuit 22.1 lbf.in (2.5 N.m) EverLink BTR screw connectors pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1, Mirror contact 1 NC IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact |
| Mounting Support | Rail, Plate |
| Standards | EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, CSA C22.2 No 14, UL 60947-4-1, IEC 60335-2-40:Annex JJ, UL 60335-2-40:Annex JJ, IEC 60335-1:Clause 30.2 |
|---|---|
| Product Certifications | CCC, UL, CB Scheme, CSA, CE, UKCA, Marine, EAC |
| IP degree of protection | IP20 front face IEC 60529 |
| Protective treatment | THIEC 60068-2-30 |
| Climatic withstand | IACS E10 exposure to damp heat, IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…140 °F (-40…60 °C), 140…158 °F (60…70 °C) with derating |
| Operating altitude | 0...9842.52 ft (0...3000 m) |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open 2 Gn, 5...300 Hz), Vibrations contactor closed 4 Gn, 5...300 Hz), Shocks contactor closed 15 Gn for 11 ms), Shocks contactor open 10 Gn for 11 ms) |
| Height | 4.8 in (122 mm) |
| Width | 2.2 in (55 mm) |
| Depth | 4.7 in (120 mm) |
| Net Weight | 1.90 lb(US) (0.86 kg) |
| Part number | LC1D65AG7 |
|---|---|
| Type designation | LC1D |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3389119408998 |
| Warranty (in months) | 18 |
|---|
| Country of origin | ID |
|---|---|
| Shipping weight | 0.86 kg |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 24 Nov 2026
The rated current of LC1D is 65 A.
The rated operational voltage of LC1D is 690 V AC.
The rated motor power of LC1D is 30 kW.
The control voltage range of LC1D is 120 V.
The tariff (HS) code on file for LC1D is 853649.
The EAN (GTIN) of LC1D is 3389119408998.
LC1D ships worldwide by express courier, with tracking. Shipping and import duties calculated at checkout · nothing to pay on delivery.
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Master AC3 rating selection with our complete contactor checklist covering load sizing, utilization categories, derating, and coordination. Shop at Stoklink.