Part number
LC1D150AEHE
Model no
LC1D
$716.45 On request Dispatch —· Worldwide delivery

Schneider Electric LC1D150AEHE TeSys Deca Advanced Contactor 3P 3NO AC-3 150 A 48-130 V AC/DC Coil Contactor

TeSys Deca Advanced 3P contactor, 150 A AC-3, 48-130 V AC/DC electronic coil, 1NO+1NC auxiliary, EverLink terminals.

Rated current
150 A
Rated operational voltage
1000 V AC
Motor power
75 kW
Control voltage
48–130–DC V
Poles
3P
EAN
3606486977040
Description

About the LC1D

The Schneider Electric LC1D150AEHE is a TeSys Deca Advanced 3-pole (3NO) contactor rated 150 A in AC-3 at up to 440 V AC, driven by a 48-130 V AC/DC wide-band electronic coil. It switches 75 kW at 400 V AC, includes integrated 1 NO + 1 NC auxiliary contacts and uses EverLink power terminals accepting 10-120 mm2 conductors.

Certifications & Standards

  • CB Scheme
  • CCC
  • cULus
  • CE
  • UKCA
  • EU-RO-MR by DNV-GL
  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • JIS C8201-4-1
  • JIS C8201-5-1
  • GB/T 14048.4
  • GB/T 14048.5

Selection Notes

The 48-130 V AC/DC coil range covers 120 V AC control circuits, since 120 V lies inside the band, and it also accepts DC control supplies, so one coil code serves both. Hold-in draw is 5.1 W, which keeps control transformer loading low. The 150 A figure is the AC-3 motor-duty rating; the 200 A value applies only to AC-1 resistive loads, so the AC-3 rating is the one to size against motor current. This is the current-generation 150 A contactor body, and an LRD43 thermal overload relay can be mounted directly below it.

Specification

Full specification

75 values · Last verified 24 Nov 2026

Main 10

Range TeSys Deca
Range of Product TeSys Deca Advanced
Product or Component Type Contactor
Device short name LC1D
Contactor application Motor control, Resistive load
Utilisation category AC-3, AC-3e, AC-1, AC-4, DC-1, DC-3, DC-5
Poles description 3P
[Ue] rated operational voltage Power circuit <= 1000 V AC 16.67...400 Hz, Power circuit <= 300 V DC
[Ie] rated operational current 150 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit, 150 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit, 200 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 48...130 V AC 50/60 Hz, 48...130 V DC

Complementary 39

Motor power kW 40 kW at 230 V AC 50/60 Hz (AC-3), 75 kW at 400 V AC 50/60 Hz (AC-3), 80 kW at 415 V AC 50/60 Hz (AC-3), 90 kW at 440 V AC 50/60 Hz (AC-3), 90 kW at 500 V AC 50/60 Hz (AC-3), 100 kW at 690 V AC 50/60 Hz (AC-3), 75 kW at 1000 V AC 50/60 Hz (AC-3), 40 kW at 230 V AC 50/60 Hz (AC-3e), 75 kW at 400 V AC 50/60 Hz (AC-3e), 80 kW at 415 V AC 50/60 Hz (AC-3e), 90 kW at 440 V AC 50/60 Hz (AC-3e), 90 kW at 500 V AC 50/60 Hz (AC-3e), 100 kW at 690 V AC 50/60 Hz (AC-3e), 75 kW at 1000 V AC 50/60 Hz (AC-3e), 37 kW at 230 V AC 50/60 Hz (AC-4), 75 kW at 400 V AC 50/60 Hz (AC-4), 75 kW at 440 V AC 50/60 Hz (AC-4), 75 kW at 500 V AC 50/60 Hz (AC-4), 80 kW at 690 V AC 50/60 Hz (AC-4), 65 kW at 1000 V AC 50/60 Hz (AC-4)
Maximum Horse Power Rating 40 hp at 200/208 V 60 Hz, 50 hp at 230/240 V 60 Hz, 100 hp at 460/480 V 60 Hz, 125 hp at 575/600 V 60 Hz
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 200 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 1885 A at 440 V for power circuit conforming to IEC 60947, 140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 1440 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 350 A 104 °F (40 °C) - 10 min for power circuit, 600 A 104 °F (40 °C) - 1 min for power circuit, 1280 A 104 °F (40 °C) - 10 s for power circuit, 1800 A 104 °F (40 °C) - 1 s for power circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit
Associated fuse rating 160 A aM at <= 440 V for power circuit, 125 A aM at <= 690 V for power circuit, 250 A gG at <= 690 V for power circuit, 10 A gG for signalling circuit, 0.63 A gG for control circuit
Average impedance 0.45 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole 8 W AC-3, 8 W AC-3e, 22 W AC-1
[Ui] rated insulation voltage Power circuit 600 V CSA, Power circuit 600 V UL, Power circuit 1000 V IEC 60947-4-1, Signalling circuit 690 V IEC 60947-1, Signalling circuit 600 V CSA, Signalling circuit 600 V UL
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Safety reliability level B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1, B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 8 Mcycles
Electrical durability 0.85 Mcycles 150 A AC-3 <= 440 V, 0.85 Mcycles 150 A AC-3e <= 440 V, 0.5 Mcycles 200 A AC-1 <= 440 V
Control circuit type AC 50/60 Hz, DC
Coil technology Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits 0.8 Uc Min...1.1 Uc Max (-40…140 °F (-40…60 °C)):operational AC/DC, 0.1 Uc Max (-40…140 °F (-40…60 °C)):drop-out AC/DC
Inrush power in VA 170 VA (at 68 °F (20 °C))
Inrush power in W 120 W 68 °F (20 °C))
Hold-in power consumption in VA 7.5 VA (at 68 °F (20 °C))
Hold-in power consumption in W 5.1 W 68 °F (20 °C)
Heat dissipation 1.5 W at 20 °C
Operating time 10...80 ms opening, 20...90 ms closing
Maximum operating rate 2400 cyc/h at 60 °C, 3600 cyc/h at Uc at 20 ºC
Connections - terminals Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible without cable end, Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible without cable end, Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible with cable end, Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible with cable end, Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: solid without cable end, Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: solid without cable end, Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end, Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end, Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end, Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end, Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end, Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Tightening torque Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm), Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm, Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2, Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1, Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 16.67...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact
Mounting Support Plate

Environment 13

Standards EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, JIS C8201-4-1, JIS C8201-5-1, GB/T 14048.4, GB/T 14048.5
Product Certifications CB Scheme, CCC, cULus, CE, UKCA, EU-RO-MR by DNV-GL
IP degree of protection IP20 front face IEC 60529
Protective treatment NoneIEC 60068-2-30
Climatic withstand IACS E10 exposure to damp heat, IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device -40…140 °F (-40…60 °C) operation, 140…158 °F (60…70 °C) with derating, -76…176 °F (-60…80 °C) storage
Operating altitude 0...9842.52 ft (0...3000 m) without derating
Fire resistance 1562 °F (850 °C) IEC 60695-2-11
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz) IEC 60068-2-6, Vibrations contactor closed 4 Gn, 5...300 Hz) IEC 60068-2-6, Shocks contactor open 10 Gn for 11 ms) IEC 60068-2-27, Shocks contactor closed 15 Gn for 11 ms) IEC 60068-2-27
Height 6.0 in (152 mm)
Width 3.8 in (97 mm)
Depth 6.1 in (155 mm)
Net Weight 5.3 lb(US) (2.4 kg)
Show all 75 specifications ↓ Show less ↑13 more values in Identification, Contractual warranty, Logistics.

Identification 8

Part number LC1D150AEHE
Type designation LC1D
Brand Schneider Electric
Condition New, factory sealed
Source Schneider Electric and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 3606486977040

Contractual warranty 1

Warranty (in months) 18

Logistics 4

Country of origin CN
Shipping weight 2.4 kg
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 24 Nov 2026

Documents

Documents for LC1D150AEHE 3

Certifications

Certifications and standards

  • cULus
  • CE
  • UKCA
  • CCC
  • CB Scheme
  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • JIS C8201-4-1
  • JIS C8201-5-1
  • GB/T 14048.4
  • GB/T 14048.5
Quick answers

Questions about the LC1D

What is the rated current of LC1D?

The rated current of LC1D is 150 A.

Which supply voltage is LC1D rated for?

The rated operational voltage of LC1D is 1000 V AC.

What motor power is LC1D rated for?

The rated motor power of LC1D is 75 kW.

Which control voltage does LC1D need?

The control voltage range of LC1D is 48–130–DC V.

What is the HS code of LC1D for customs?

The tariff (HS) code on file for LC1D is 853649.

What is the EAN of LC1D?

The EAN (GTIN) of LC1D is 3606486977040.

How is LC1D delivered, and how fast?

LC1D ships worldwide by express courier, with tracking. Shipping and import duties calculated at checkout · nothing to pay on delivery.

Guides

Guides for contactors

All guides for contactors
Reviews

Customer reviews

Series

Schneider Electric Schneider TeSys Deca

Brand
Schneider Electric
Series
Schneider TeSys Deca
Series page →
Series

Other series in Contactors

$716.45 On request
Quote

Get a Quote

LC1D

Genuine parts

Genuine, factory-sealed parts

Schneider Electric · LC1D150AEHE

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Schneider Electric and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart