NSX630HB1 3P 630 A 75 kA MicroLogic 5.3 E MCCB, fixed backplate mount.
The Schneider Electric C63V35E630 is a three-pole ComPacT NSX630HB1 moulded case circuit breaker, rated 630 A at 40 °C with a 75 kA breaking capacity at 380/415 V AC and 690 V AC rated operational voltage. It carries a MicroLogic 5.3 E trip unit giving LSI protection, fixed for backplate mounting with front upside and downside connections on a 45 mm pitch.
The HB1 frame trades breaking capacity for 690 V AC suitability, so pick it over the standard R frame when the installation runs at 690 V AC and a 75 kA breaking capacity at that voltage is sufficient. The MicroLogic 5.3 E trip unit adds an adjustable short-time delay and instantaneous pickup from 1.5 to 11 x In, plus zone-selective interlocking and an LCD energy meter, so the breaker can coordinate selectively with downstream devices. Pick the 6.3 E variant instead when ground-fault protection is required, or the 2.3 unit when a simpler, non-communicating trip unit is enough.
| Range | ComPacT |
|---|---|
| Product name | ComPacT NSX |
| Device short name | NSX630HB1 |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 630 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2, 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | HB1 75 kA 690 V AC |
| Trip unit name | MicroLogic 5.3 E |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service breaking capacity | 85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2, 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2, 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 15000 cycles |
| Electrical durability | 8000 cycles at 440 V In/2, 4000 cycles at 440 V In, 6000 cycles at 690 V In/2, 2000 cycles at 690 V In |
| Power dissipation per pole | 39.7 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical, Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 45 mm |
| Protection type | L : for overload protection (long time), S : for short time short-circuit protection, I : for instantaneous short-circuit protection |
| Trip unit rating | 630 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 250...630 A |
| Long-time protection delay adjustment type tr | Adjustable |
| [tr] long-time delay adjustment range | 15…400 s at 1.5 x Ir, 0.5…16 s at 6 x Ir, 0.35…11 s at 7.2 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable 5 settings |
| [tsd] short-time delay adjustment range | 0…0.4 s I²t=off, 0.1…0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...11 x In |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | With |
| Number of slots | 6 slot(s) |
| Local signalling | Flashing LED (green) for ready to operate, LED 105 % Ir (red) for overload, LED 90 % Ir (orange) for overload |
| Display type | LCD display |
| Type of measurement | Energy meter |
| Communication of data | Energy metering, Maximeters/minimeters, Protection and alarm settings, Maintenance indicators, Instantaneous and demand values, Power quality, Time-stamped histories and event tables, Demand current and power |
| Width (W) | 140 mm |
| Height (H) | 255 mm |
| Depth (D) | 110 mm |
| Net weight | 6.2 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating, 2000 m...5000 m with derating |
| Part number | C63V35E630 |
|---|---|
| Type designation | NSX630HB1 |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.200 cm |
| Package 1 Width | 15.200 cm |
| Package 1 Length | 29.200 cm |
| Package 1 Weight | 5.857 kg |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 30 cm |
| Package 2 Width | 40 cm |
| Package 2 Length | 60 cm |
| Package 2 Weight | 18.221 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 12 |
| Package 3 Height | 45.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 120.000 cm |
| Package 3 Weight | 84.884 kg |
| Shipping weight | 6.2 kg |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
The rated current of NSX630HB1 is 630 A.
The rated operational voltage of NSX630HB1 is 690 V AC.
The tariff (HS) code on file for NSX630HB1 is 853620.
NSX630HB1 ships worldwide by express courier, with tracking. Shipping and import duties calculated at checkout · nothing to pay on delivery.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...