Types of Molded Case Circuit Breakers: MCCB Guide for Engineers
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Schneider Electric C16M2TM125 ComPacT NSX160M 2P 125A TM-D AC/DC, 25 kA at 415 V AC.
The C16M2TM125 is a 2-pole Schneider Electric ComPacT NSX160M AC/DC moulded case circuit breaker rated 125 A, with a TM-D thermal-magnetic trip unit and 25 kA breaking capacity (Icu) at 380/415 V AC. It is dual-rated for 690 V AC or 500 V DC with both poles in series, with Ue given as 690 V AC on the AC side.
The C16M2TM125's 25 kA Icu at 415 V AC sits below the 3-pole NSX160F/H/N frames' 36–70 kA range, reflecting the 2-pole M-frame's focus on single-phase or DC branch circuits rather than 3-phase mains distribution. On DC duty its Icu reaches 85 kA at both 250 V (1 pole) and 500 V (2 poles in series), far above its AC figure. For the higher 160 A current rating in the same 2-pole body, the TM160 variant is the direct step up.
| Range | ComPacT |
|---|---|
| Product name | ComPacT NSX |
| Device short name | NSX160M |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 2P |
| Protected poles description | 2D |
| [In] rated current | 125 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz, 500 V DC |
| Network type | AC, DC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2, 25 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2, 18 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2, 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2, 85 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2 |
| Breaking capacity code | M 25 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 18 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2, 85 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 277 V In/2, 10000 cycles at 277 V In |
| Power dissipation per pole | 10.78 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical, Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (thermal), I : for short-circuit protection (magnetic) |
| Trip unit rating | 125 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Fixed |
| [Ir] long-time protection pick-up adjustment range | 1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 1000 A |
| Earth-leakage protection | Without |
| Width (W) | 70 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Net weight | 1.2 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating, 2000 m...5000 m with derating |
| Part number | C16M2TM125 |
|---|---|
| Type designation | NSX160M |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.0 cm |
| Package 1 Width | 13.0 cm |
| Package 1 Length | 17.5 cm |
| Package 1 Weight | 1.302 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 15.996 kg |
| Shipping weight | 1.2 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
The rated current of NSX160M is 125 A.
The rated operational voltage of NSX160M is 690 V AC.
The tariff (HS) code on file for NSX160M is 853620.
NSX160M ships from Türkiye. Shipping and import duties calculated at checkout · nothing to pay on delivery.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...