Types of Molded Case Circuit Breakers: MCCB Guide for Engineers
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
3P 1600A ComPacT NS1600H MCCB, 70kA Icu at 415V AC, MicroLogic 2.0 trip unit, fixed, manually operated.
The Schneider Electric C160H320FM is a 3-pole, 1600 A ComPacT NS1600H moulded case circuit breaker rated for 70 kA breaking capacity (Icu) at 380/415 V AC. Fixed-mounted and manually operated, it carries a MicroLogic 2.0 electronic trip unit delivering long-time overload and instantaneous short-circuit protection, and is rated up to 690 V AC for high-breaking-capacity distribution duty in the ComPacT NS630b...1600 new generation line.
The H-frame classification gives the C160H320FM 70 kA Icu at 380/415 V AC — choose it over the N-frame version of the same 1600 A frame when prospective short-circuit current at the installation point runs above standard distribution levels. Its MicroLogic 2.0 trip unit covers long-time overload and instantaneous protection only (LI), with no short-time delay stage — choose a 5.0 (LSI) or 6.0 (LSIG) trip unit from this same frame where selective coordination with downstream breakers is required. The base MicroLogic 2.0 unit has no digital display — settings are read off the dial markings, with no RMS or energy readout. At 210 mm wide on 3 poles, it suits 3-phase-only distribution with no neutral protection; the 4-pole version of the same frame is available where the neutral conductor must be switched and protected.
| Range | ComPacT |
|---|---|
| Product name | ComPacT NS new generation |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Number of poles | 3P |
| Protected poles description | 3D |
| [In] rated current | 1600 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category B |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | H 70 kA 415 V AC |
| Trip unit name | MicroLogic 2.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LI |
| Control type | Manually operated |
| Mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 19.2 kA 1 s conforming to IEC 60947-2 |
| Mechanical durability | 10000 cycles |
| Electrical durability | 1000 cycles at 690 V In, 2000 cycles at 690 V In/2, 2000 cycles at 440 V In, 5000 cycles at 440 V In/2 |
| Power losses | 74 W |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 70 mm |
| Protection type | L : for overload protection (long time), I : for instantaneous short-circuit protection |
| Trip unit rating | 1600 A at 50 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 12.5…600 s at 1.5 x Ir, 0.5…24 s at 6 x Ir, 0.7…16.6 s at 7.2 x Ir |
| Thermal memory | 20 mn |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...10 x Ir |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | Without |
| Auxiliary contact composition | 1 NO/NC |
| Local signalling | 4 LEDs (red) for fault indication, 1 LED (yellow) for overload |
| Width (W) | 210 mm |
| Height (H) | 327 mm |
| Depth (D) | 147 mm |
| Net weight | 14 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Product certifications | IECEE CB Scheme |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60947 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating, 2000 m...5000 m with derating |
| Part number | C160H320FM |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 30.000 cm |
| Package 1 Width | 40.000 cm |
| Package 1 Length | 60.000 cm |
| Package 1 Weight | 13.842 kg |
| Unit Type of Package 2 | P12 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 45.000 cm |
| Package 2 Width | 80.000 cm |
| Package 2 Length | 120.000 cm |
| Package 2 Weight | 69.968 kg |
| Shipping weight | 14.0 kg |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
The rated current of C160H320FM is 1600 A.
The rated operational voltage of C160H320FM is 690 V AC.
The tariff (HS) code on file for C160H320FM is 853620.
C160H320FM ships worldwide by express courier, with tracking. Shipping and import duties calculated at checkout · nothing to pay on delivery.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...