The Schneider Electric C080L350FM is a 3-pole ComPacT NS800L moulded case circuit breaker rated 800 A, with a 150 kA breaking capacity (Icu) at 380/415 V AC and a 690 V AC operational voltage. It carries the MicroLogic 5.0 trip unit for overload (L), short-time delayed short-circuit (S) and instantaneous (I) protection, and mounts fixed with front-connected upstream and downstream terminals.
Technical Specifications
| Reference | C080L350FM |
| Brand | Schneider Electric |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Circuit breaker |
| Number of poles | 3P |
| [In] rated current | 800 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
| Breaking capacity (Icu) | 150 kA at 220/240 V AC, 150 kA at 380/415 V AC, 130 kA at 440 V AC, 100 kA at 500/525 V AC, conforming to IEC 60947-2 |
| Rated service breaking capacity (Ics) | 150 kA at 220/240 V AC, 150 kA at 380/415 V AC, 130 kA at 440 V AC, 100 kA at 500/525 V AC, conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 19.2 kA for 1 s |
| Utilisation category | Category A |
| Suitability for isolation | Yes, conforming to EN/IEC 60947-2 |
| Trip unit name | MicroLogic 5.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSI (overload (L), short-time delayed short-circuit (S) and instantaneous (I) protection) |
| [Ir] long-time pick-up adjustment range | 0.4...1 x In, adjustable, 9 settings |
| [Isd] short-time pick-up adjustment range | 1.5...10 x Ir, adjustable, 9 settings |
| [Ii] instantaneous pick-up adjustment range | Off, or 2...15 x In |
| Earth-leakage protection | Without |
| Zone selective interlocking (ZSI) | Without |
| Control type | Manually operated |
| Mounting mode | Fixed, backplate-mounted |
| Connection (upside / downside) | Front / Front |
| Dimensions (W x H x D) | 210 x 327 x 147 mm |
| Net weight | 14 kg |
| IP / IK degree of protection | IP40 / IK07 |
Certifications & Standards
- IECEE CB Scheme
- EN/IEC 60947-2
Selection Notes
The MicroLogic 5.0 trip unit on the C080L350FM is configured for overload (L), short-time delayed short-circuit (S) and instantaneous (I) protection. Adding the S (short-time delay) stage to L-I lets this trip unit hold off tripping briefly on a downstream fault, so an upstream breaker can coordinate selectively with devices further down the circuit. In the NS800 case size, this L-frame breaker is the very high breaking capacity option (150 kA Icu at 380/415 V AC); the H-frame (70 kA Icu) and the N-frame (50 kA Icu) versions share the same case and accessories but trade breaking capacity for cost or vice versa. The A- and E-suffix trip units in the same frame add an ammeter or energy meter respectively, for installations that want local metering without extra hardware. As a 3-pole unit it protects the three phases only; the 4-pole version of the same frame adds switched or protected neutral handling.