The Schneider Electric BMXDDO3202K is a Modicon X80 discrete output module with 32 transistor outputs in positive (sink) logic, built for Modicon M340 and M580 programmable automation controllers. Each channel switches 0.125 A at 19-30 V DC (3.2 A per module), with reverse-polarity, short-circuit, overload, and overvoltage protection and a 1.2 ms output response time.
Technical Specifications
| Reference | BMXDDO3202K |
| GTIN | 3595863910476 |
| Brand | Schneider Electric |
| Range | Modicon X80 |
| Product Type | Discrete output module |
| Discrete Output Logic | Positive (sink) |
| Number of Outputs | 32 |
| Current per Channel | 0.125 A |
| Maximum Current per Module | 3.2 A |
| Output Voltage Range | 19-30 V DC (24 V nominal) |
| Response Time (Output) | 1.2 ms |
| Maximum Voltage Drop | <1.5 V at state 1 |
| Insulation Resistance | >10 MOhm at 500 V DC |
| Paralleling of Outputs | Yes, 3 maximum |
| Load Impedance | >=220 Ohm |
| Protection Type | Reverse polarity, external short-circuit, overload, overvoltage |
| MTBF | 290,000 h |
| Dielectric Strength | 1500 V AC (output/ground, output/internal logic); 500 V DC (between channel groups) |
| IP Degree of Protection | IP20 |
| Net Weight | 0.11 kg |
Certifications & Standards
- EAC
- Merchant Navy
- CSA
- RCM
- CE
- UL
- EN 61131-2
- EN 61000-6-4
- EN 61000-6-2
- EN 61010-2-201
Selection Notes
The BMXDDO3202K gives 32 transistor output points per module in positive (sink) logic, so it fits Modicon X80 racks where channel density matters more than per-point current headroom - each channel is individually rated 0.125 A, and up to 3 outputs can be paralleled to raise the switching current for a single load. Its 290,000-hour MTBF and 1.2 ms response time suit discrete actuator and solenoid switching on M340 and M580-based process racks; where a load needs more than 0.125 A per point without paralleling, a lower-count, higher-current output module in the same X80 range is the better fit.
Applications