- Home
- Schneider TeSys Deca Contactors
- Schneider Electric LC1DT200A6KUE TeSys Deca Advanced 4P 4NO AC-1 200 A 100-250 V AC/DC Coil Contactor Schneider Electric LC1DT200A6KUE TeSys Deca Advanced 4P 4NO AC-1 200 A 100-250 V AC/DC Coil Contactor
Schneider Electric LC1DT200A6KUE TeSys Deca Advanced 4P 4NO AC-1 200 A 100-250 V AC/DC Coil Contactor
Schneider Electric LC1DT200A6KUE TeSys Deca Advanced 4P 4NO AC-1 200 A 100-250 V AC/DC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1DT200A6KUE is a TeSys Deca Advanced 4-pole (4NO) contactor rated 200 A AC-1 at up to 440 V, carrying a 55 kW AC-3 motor rating at 400 V. Its sealed 100-250 V AC/DC electronic coil spans the widest control band in the family, and the power circuit connects through lugs-ring terminals or busbars.
Technical Specifications
| Reference | LC1DT200A6KUE |
| Brand | Schneider Electric |
| Range | TeSys Deca Advanced |
| GTIN | 3606487155980 |
| Product Type | Contactor |
| Poles | 4P (4NO) |
| Utilisation Category | AC-1, AC-3, AC-3e, AC-4, DC-1, DC-3, DC-5 |
| Rated Operational Voltage (Ue) | ≤ 1000 V AC, 16.67-400 Hz / ≤ 300 V DC |
| Rated Operational Current (Ie), AC-1, ≤440V | 200 A |
| Motor Power, AC-3 at 400 V | 55 kW |
| Control Circuit Voltage (Uc) | 100-250 V AC/DC, electronic |
| Hold-In Power Consumption | 4.5 W |
| Rated Breaking Capacity at 440 V | 1100 A, IEC 60947 |
| Rated Short-Time Withstand Current (Icw), 1 s | 1800 A at 40 degrees C |
| Rated Insulation Voltage (Ui) | 1000 V, IEC 60947-4-1 |
| Auxiliary Contact Composition | 1 NO + 1 NC, mirror contact |
| Terminal Type | Lugs-ring terminals or bars (power), screw clamp (control) |
| Maximum Operating Rate | 2400 cyc/h at 60 degrees C |
| Mounting | Screw-fixing plate |
| IP Degree of Protection | IP20, front face |
| Dimensions (H x W x D) | 152 x 134 x 155 mm |
| Net Weight | 2600 g |
Certifications & Standards
- IEC 60947-4-1
- cULus
- CCC
- CE
- UKCA
Selection Notes
A single LC1DT200A6KUE reference covers 110 V, 230 V AC or common DC control rails at 200 A AC-1 and 55 kW AC-3 at 400 V, matching the EHE sibling electrically but running a wider 100-250 V coil band. Lugs-ring or busbar power terminations suit the switchgear panels this frame size targets. Where the control circuit is fixed at 48-130 V, the EHE variant uses the identical body and ratings.